Interconnection Customer’s Interconnection Facilities. One (1) transformer, generator step-up, station service; three-phase, 7.25% impedance; 2500/3125 55 degreesC kVA; primary voltage 34.5 kV, 200 kV BIL; secondary voltage 480 V, 45 kV BIL; wye-wye; primary fuse XX0, 000X, Xxx. One (1) transformer, generator step-up, station service; three phase, 7.85% impedance; 2500/3125 55 degrees C, 2800/3500 65 degrees C; primary voltage 34,400, secondary voltage 480/277; wye-wye; primary fuse XX0, 000X, Xxx. One (1) primary fuse XX0, 000X, Xxx. transformer protection device, 34.5 kV nominal, 38 kV max; 200 kV BIL; 100 amp; interrupting capability 6250 kA. One (1) primary fuse XX0, 000X, Xxx. transformer protection device, 34.5 kV nominal, 38 kV max; 200 kV BIL; 100E amp, interrupting capability of 6250 kA. One (1) Alduti-Rupter three-phase manual/group operated disconnect switch, 34.5 kV nominal, 38 kV max, 200 kV BIL, 600 amp cont.,40 kA momentary, 600 amp interrupting capability. One (1) AR116SFCLW three phase, manual/group operated disconnect switch, 34.5 kV nominal, 38 kV max, 200 kV BIL, 600 amp cont., 40 kA momentary, 600 amp interrupting. Eighteen (18) surge arrestors type 27 kV, 22 kV, MCOV, intermediate class.

Appears in 5 contracts

Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

AutoNDA by SimpleDocs

Interconnection Customer’s Interconnection Facilities. One (1) transformer, generator step-up, station service; three-phase, 7.25% impedance; 2500/3125 55 degreesC kVA; primary voltage 34.5 kV, 200 kV BIL; secondary voltage 480 V, 45 kV BIL; wye-wye; primary fuse XX0, 000X, Xxx. One (1) transformer, generator step-up, station service; three phase, 7.85% impedance; 2500/3125 55 degrees C, 2800/3500 65 degrees C; primary voltage 34,400, secondary voltage 480/277; wye-wye; primary fuse XX0, 000X, Xxx. One (1) primary fuse XX0, 000X, Xxx. transformer protection device, 34.5 kV nominal, 38 kV max; 200 kV BIL; 100 amp; interrupting capability 6250 kA. One (1) primary fuse XX0, 000X, Xxx. transformer protection device, 34.5 kV nominal, 38 kV max; 200 kV BIL; 100E amp, interrupting capability of 6250 kA. One (1) Alduti-Rupter three-phase manual/group operated disconnect switch, 34.5 kV nominal, 38 kV max, 200 kV BIL, 600 amp cont.,40 kA momentary, 600 amp interrupting capability. One (1) AR116SFCLW three phase, manual/group operated disconnect switch, 34.5 kV nominal, 38 kV max, 200 kV BIL, 600 amp cont., 40 kA momentary, 600 amp interrupting. Eighteen (18) surge arrestors type 27 kV, 22 kV, MCOV, intermediate class.  One (1) current transformer for Utility Tie 1, type MRBCT, accuracy class X000, xxx-xxx.  Three (3) current transformers for Utility Tie 2, accuracy class C50, ratio 0000/0, xxx-xxx.  Three (3) voltage transformers for Bus 1, 480 V each; types 3VTN and JVA-0; accuracy class 0.6W and 0.3W; primary voltage 277V L-N and 480V L-L; secondary voltage 120 each; wye-wye and open delta-open delta; thermal rating 150 VA/Ph and 500 VA.  Three (3) voltage transformers for Bus 1, 480 V each; types 3VTN and JVA-0; accuracy class 0.6W and 0.3W; primary voltage 277V L-N and 480V L-L; secondary voltage 120 each; wye-wye and open delta-open delta; thermal rating 150 VA/Ph and 500 VA.  One (1) current transformer for Neut Bus Ground, accuracy class C100, ratio 1200/5, 1 Ph.  Approximately 1735 feet of parallel 34.kV line, 123.3 kc mil, 7 strand AAAC-6201, between the Small Generating Facility (Engines #5, 6 and 7) and the Point of Interconnection.  Approximately 75 feet of 34.5 kV line, 123.3 kc mil, 7 strand AAAC-6201, between the Small Generating Facility (Engines #1, 4A, 4B and 4C) and the Point of Interconnection.  Two (2) control houses equipped with protective relays and controls, communications systems, lighting, heating and cooling, AC and DC systems.

Appears in 3 contracts

Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Interconnection Customer’s Interconnection Facilities. One (1) transformer, generator step-up, station service; three-phase, 7.25% impedance; 2500/3125 55 degreesC kVA; primary voltage 34.5 kV, 200 kV BIL; secondary voltage 480 V, 45 kV BIL; wye-wye; primary fuse XX0SM4, 000X100E, XxxStd. One (1) transformer, generator step-up, station service; three phase, 7.85% impedance; 2500/3125 55 degrees C, 2800/3500 65 degrees C; primary voltage 34,400, secondary voltage 480/277; wye-wye; primary fuse XX0SM4, 000X100E, XxxStd. One (1) primary fuse XX0SM4, 000X100E, XxxStd. transformer protection device, 34.5 kV nominal, 38 kV max; 200 kV BIL; 100 amp; interrupting capability 6250 kA. One (1) primary fuse XX0SM4, 000X100E, XxxStd. transformer protection device, 34.5 kV nominal, 38 kV max; 200 kV BIL; 100E amp, interrupting capability of 6250 kA. One (1) Alduti-Rupter three-phase manual/group operated disconnect switch, 34.5 kV nominal, 38 kV max, 200 kV BIL, 600 amp cont.,40 kA momentary, 600 amp interrupting capability. One (1) AR116SFCLW three phase, manual/group operated disconnect switch, 34.5 kV nominal, 38 kV max, 200 kV BIL, 600 amp cont., 40 kA momentary, 600 amp interrupting. Eighteen (18) surge arrestors type 27 kV, 22 kV, MCOV, intermediate class.

Appears in 1 contract

Samples: Interconnection Agreement

AutoNDA by SimpleDocs

Interconnection Customer’s Interconnection Facilities. One (1) transformer, generator step-up, station service; three-phase, 7.25% impedance; 2500/3125 55 degreesC kVA; primary voltage 34.5 kV, 200 kV BIL; secondary voltage 480 V, 45 kV BIL; wye-wye; primary fuse XX0, 000X, Xxx. One (1) transformer, generator step-up, station service; three phase, 7.85% impedance; 2500/3125 55 degrees C, 2800/3500 65 degrees C; primary voltage 34,400, secondary voltage 480/277; wye-wye; primary fuse XX0, 000X, Xxx. One (1) primary fuse XX0, 000X, Xxx. transformer protection device, 34.5 kV nominal, 38 kV max; 200 kV BIL; 100 amp; interrupting capability 6250 kA. One (1) primary fuse XX0, 000X, Xxx. transformer protection device, 34.5 kV nominal, 38 kV max; 200 kV BIL; 100E amp, interrupting capability of 6250 kA. One (1) Alduti-Rupter three-phase manual/group operated disconnect switch, 34.5 kV nominal, 38 kV max, 200 kV BIL, 600 amp cont.,40 kA momentary, 600 amp interrupting capability. One (1) AR116SFCLW three phase, manual/group operated disconnect switch, 34.5 kV nominal, 38 kV max, 200 kV BIL, 600 amp cont., 40 kA momentary, 600 amp interrupting. Eighteen (18) surge arrestors type 27 kV, 22 kV, MCOV, intermediate class.

Appears in 1 contract

Samples: Interconnection Agreement

Time is Money Join Law Insider Premium to draft better contracts faster.