Acceptance Test Capacity Guarantee Sample Clauses

Acceptance Test Capacity Guarantee. The “Minimum Required Capacity” for each Facility for purposes of this Agreement shall be equal to 90% of the Expected Capacity of such Facility. At the end of the Acceptance Testing Period under Section 11.2.3, it is expected that each of the three Facilities shall have demonstrated the capability to produce 7.0MW-DC (5.0 MW AC), subject to final as-build system size (the “Expected Capacity”), based upon the Acceptance Testing results. Contractor hereby guarantees that each Facility shall perform at not less than 97% of the Expected Capacity by the end of the Acceptance Testing Period (the “Acceptance Test Capacity Guarantee”). Contractor and the Testing Engineer shall be entitled to conduct and verify satisfaction of the Acceptance Tests in stages and in such order as may be appropriate given the available testing conditions. In the event that a Facility fails to meet the Acceptance Test Capacity Guarantee, the following shall apply:
AutoNDA by SimpleDocs
Acceptance Test Capacity Guarantee. At the end of Acceptance Testing Period under Section 11.2.3, the Facility shall have demonstrated the capability to produce 7.0 MW-DC, subject to final as-build system size, based upon the Acceptance Testing results. Contractor hereby guarantees that the Facility shall perform at not less than 97% of the Promised Capacity by the end of the Acceptance Testing Period (the “Acceptance Test Capacity Guarantee”). Contractor and the Testing Engineer shall be entitled to conduct and verify satisfaction of the Acceptance Tests in stages and in such order as may be appropriate given the available testing conditions. In the event that the Facility fails to meet the Acceptance Test Capacity Guarantee, the following shall apply:
Acceptance Test Capacity Guarantee. At the end of Acceptance Testing Period under Section 11.2.3, the Facility shall have demonstrated the capability to produce the following: (a) 20,000 tons (which is equal to 12,000 British Thermal Units per hour) of chilled water (the “Promised Chilled Water Capacity”); and (b) 400,000 lbs/hour of steam (the “Promised Steam Capacity”) based upon the Acceptance Testing results. MGE Construct hereby guarantees that the Facility shall provide not less than ninety-seven percent (97%) of the Promised Chilled Water Capacity and the Promised Steam Capacity by the end of the Acceptance Testing Period (the “Acceptance Test Capacity Guarantee”). MGE Construct and the Testing Engineer shall be entitled to conduct and verify satisfaction of the Acceptance Tests in stages and in such order as may be appropriate given the available testing conditions, including, without limitation, separating the Acceptance Tests to demonstrate steam capacity from the Acceptance Tests to demonstrate chilled water capacity. In the event that the Facility fails to meet the Acceptance Test Capacity Guarantee, the following shall apply:
Acceptance Test Capacity Guarantee. At the end of Acceptance Testing Period under Section 11.2.3, the Facility shall have demonstrated the capability to produce [Specification of performance standard for production of electricity], based upon the Acceptance Testing results. Contractor hereby guarantees that the Facility shall perform at not less than 97% of the Promised Capacity by the end of the Acceptance Testing Period (the “Acceptance Test Capacity Guarantee”). Contractor and the Testing Engineer shall be entitled to conduct and verify satisfaction of the Acceptance Tests in stages and in such order as may be appropriate given the available testing conditions. In the event that the Facility fails to meet the Acceptance Test Capacity Guarantee, the following shall apply:
Acceptance Test Capacity Guarantee. At the end of Acceptance Testing Period under Section 10.2.3, each Plant shall have demonstrated the capability to produce the following: (a) 10.2 MWh of gross electric energy capacity (the “promised electric energy capacity”) based upon the Acceptance Testing Results. The CONTRACTOR hereby guarantees that the Plant shall provide not less than ninety-seven percent (97%) of the promised electric energy capacity by the end of the Acceptance Testing Period (the “Acceptance Test Capacity Guarantee”). The CONTRACTOR and the Testing Engineer shall be entitled to conduct and verify satisfaction of the Acceptance Tests in stages and in such order as may be appropriate given the available testing conditions, including, without limitation, separating the Acceptance Tests to demonstrate steam capacity from the Acceptance Tests to demonstrate chilled water capacity. In the event that the Facility fails to meet the Acceptance Test Capacity Guarantee, the following shall apply:

Related to Acceptance Test Capacity Guarantee

  • Acceptance Testing At the time of installation of a LIS trunk group, and at no additional charge, acceptance tests will be performed to ensure that the service is operational and meets the applicable technical parameters.

  • Performance Tests Contractor shall perform Performance Tests in accordance with Section 11.2 of the Agreement and Attachment S.

  • Quality Specifications SANMINA-SCI shall comply with the quality specifications set forth in its Quality Manual, incorporated by reference herein, a copy of which is available from SANMINA-SCI upon request.

  • Root Cause Analysis Upon Vendor's failure to provide the Services in accordance with the applicable Service Levels (for any reason other than a Force Majeure Event) Vendor will promptly (a) perform a root-cause analysis to identify the cause of such failure, (b) provide Prudential with a report detailing the cause of, and procedure for correcting, such failure, (c) obtain Prudential's written approval of the proposed procedure for correcting such failure, (d) correct such failure in accordance with the approved procedure, (e) provide weekly (or more frequent, if appropriate) reports on the status of the correction efforts, and (f) provide Prudential with assurances satisfactory to Prudential that such failure has been corrected and will not recur.

  • Final Acceptance When the Project/Service or any portion thereof, as designated by the COUNTY, is ready for its intended use, the COUNTY and any other invited parties shall make an inspection of the Project/Service, to verify its completeness and develop a punch list of items needing completion or correction before final payment will be made. CONTRACTOR shall have ten (10) calendar days to correct all deficiencies. An eighty-dollar ($80.00) re-inspection fee shall be applied for the third inspection and any required re-inspection thereafter. The COUNTY shall have the right to exclude CONTRACTOR from those portions of the work designated as complete after the inspection; provided, however, that CONTRACTOR will have reasonable access for the time allotted by the COUNTY to complete or correct items on the punch list. When the work provided for under this Agreement has been completely performed by CONTRACTOR, and the final inspection has been made by the COUNTY, a final invoice will be prepared by the CONTRACTOR. The amount of this invoice, less any sums that may have been deducted or retained under the provisions of this Agreement, will be paid to CONTRACTOR in accordance with this Agreement, and after CONTRACTOR has agreed in writing to accept the balance due, as determined by the COUNTY, as full settlement of the account under the contract and of all claims in connection therewith. Occupancy by the COUNTY alone does not constitute final acceptance.

  • Technical Specifications The Technical Specifications furnished on the CD are intended to establish the standards for quality, performance and technical requirements for all labor, workmanship, material, methods and equipment necessary to complete the Work. When specifications and drawings are provided or referenced by the County, these are to be considered part of the Scope of Work, and to be specifically documented in the Detailed Scope of Work. For convenience, the County supplied specifications, if any, and the Technical Specifications furnished on the CD.

  • Scope of Work The Contractor has overall responsibility for and shall provide and furnish all materials, equipment, tools and labor as necessary or reasonably inferable to complete the Work, or any phase of the Work, in accordance with the Owner’s requirements and the terms of the Contract Documents.

  • Statement of Work The Contractor shall provide the services and staff, and otherwise do all things necessary for or incidental to the performance of work, as set forth below:

  • Stability Testing Patheon may be requested to conduct stability testing on the Products in accordance with the protocols set out in the Specifications for the separate fees and during the time periods set out in Schedule C to a Product Agreement. Patheon will not make any changes to these testing protocols without prior written approval from Client. If a confirmed stability test failure occurs, Patheon will notify Client within one Business Day, after which Patheon and Client will jointly determine the proceedings and methods to be undertaken to investigate the cause of the failure, including which party will bear the cost of the investigation. Patheon will not be liable for these costs unless it has failed to perform the Manufacturing Services in accordance with the Specifications, cGMPs, and Applicable Laws. Patheon will give Client ail stability test data and results at Client’s request.

  • Acceptance; Rejection A holder of Notes may accept the offer to prepay made pursuant to this Section 8.3 by causing a notice of such acceptance to be delivered to the Company not later than 15 days after receipt by such holder of the most recent offer of prepayment. A failure by a holder of Notes to respond to an offer to prepay made pursuant to this Section 8.3 shall be deemed to constitute a rejection of such offer by such holder.

Time is Money Join Law Insider Premium to draft better contracts faster.