Construction of Space. GTE will construct DTI's collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space: 1.11.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access. 1.11.2 a standard 100 square foot cage shall have the following standard features: (a) eight-foot high, nine gauge chain link panels; (b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet; (c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link; (d) the cage shall be provided with one padlock set, with GTE retaining one master key; (e) one ac electrical outlet; (f) one charger circuit system; (g) one electrical sub-panel; (h) such additional lighting as may be necessary; (i) one fire detection requirement evaluation; (j) grounding for the cage consistent with COEI. 1.11.3 Modifications to the standard configuration set forth in Section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI to implement such additional modifications as may be necessary to ensure that DTI's collocated space is protected from unauthorized access. 1.11.4 At such time as construction of DTI's collocation space is approximately 50 percent completed, GTE will give DTI notification, and such notification shall include scheduled completion and turnover dates. 1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTI. Should DTI note any deviations from the plan agreed upon by GTE and DTI at the customer meeting, and if such deviations were not requested by DTI or not required by law, GTE shall correct such deviations at its own expense within 5 Business Days.
Appears in 2 contracts
Samples: Interconnection, Resale and Unbundling Agreement (Dti Holdings Inc), Interconnection, Resale and Unbundling Agreement (Dti Holdings Inc)
Construction of Space. GTE will construct DTIMEBTEL's collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access.
1.11.2 a A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac AC electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEI.
1.11.3 Modifications to the standard configuration set forth in Section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI MEBTEL to implement such additional modifications as may be necessary to ensure that DTIMEBTEL's collocated space is protected from unauthorized access.
1.11.4 At such time as construction of DTIMEBTEL's collocation space is approximately 50 percent completed, GTE will give DTI MEBTEL notification, and such notification shall include scheduled completion and turnover dates.
1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTIMEBTEL. Should DTI MEBTEL note any deviations from the plan agreed upon by GTE and DTI MEBTEL at the customer meeting, and if such deviations were not requested by DTI MEBTEL or not required IX-3 by law, GTE shall correct such deviations at its own expense within 5 five (5) Business Days.
Appears in 1 contract
Samples: Interconnection, Resale and Unbundling Agreement (Madison River Capital LLC)
Construction of Space. GTE will construct DTITOUCHTONE's collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access.
1.11.2 a A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac AC electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEI.
1.11.3 Modifications to the standard configuration set forth in Section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI TOUCHTONE to implement such additional modifications as may be necessary to ensure that DTITOUCHTONE's collocated space is protected from unauthorized access.
1.11.4 At such time as construction of DTITOUCHTONE's collocation space is approximately 50 percent completed, GTE will give DTI TOUCHTONE notification, and such notification shall include scheduled completion and turnover dates.
1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTITOUCHTONE. Should DTI TOUCHTONE note any deviations from the plan agreed upon by GTE and DTI TOUCHTONE at the customer meeting, and if such deviations were not requested by DTI TOUCHTONE or not required by law, GTE shall correct such deviations at its own expense within 5 five (5) Business Days.
Appears in 1 contract
Construction of Space. GTE, or a GTE approved contractor selected by ACI, will construct DTIACI's collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 1.10.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access.
1.11.2 a 1.10.2 A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEI.
1.11.3 1.10.3 Modifications to the standard configuration set forth in Section 1.11.2 1.10.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI ACI to implement such additional modifications as may be necessary to ensure that DTIACI's collocated space is protected from unauthorized access.
1.11.4 1.10.4 At such time as construction of DTIACI's collocation space is approximately 50 percent completed, GTE will give DTI ACI notification, and such notification shall include scheduled completion and turnover dates.
1.11.5 1.10.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTIACI. Should DTI ACI note any deviations from the plan agreed upon by GTE and DTI ACI at the customer meeting, and if such deviations were not requested by DTI ACI or not required by law, GTE shall correct such deviations at its own expense within 5 Business Days.
Appears in 1 contract
Samples: Interconnection, Resale and Unbundling Agreement (Rhythms Net Connections Inc)
Construction of Space. GTE will construct DTIQTC's collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access.
1.11.2 a A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac AC electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEI.
1.11.3 Modifications to the standard configuration set forth in Section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI QTC to implement such additional modifications as may be necessary to ensure that DTIQTC's collocated space is protected from unauthorized access.
1.11.4 At such time as construction of DTIQTC's collocation space is approximately 50 percent completed, GTE will give DTI QTC notification, and such notification shall include scheduled completion and turnover dates.
1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTIQTC. Should DTI QTC note any deviations from the plan agreed upon by GTE and DTI QTC at the customer meeting, and if such deviations were not requested by DTI QTC or not required by law, GTE shall correct such deviations at its own expense within 5 five (5) Business Days.
Appears in 1 contract
Construction of Space. GTE will construct DTI's Hyperion’s collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS collocation tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access.
1.11.2 a A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEI.
1.11.3 Modifications to the standard configuration set forth in Section section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI Hyperion to implement such additional modifications as may be necessary to ensure that DTI's Hyperion’s collocated space is protected from unauthorized access.
1.11.4 At such time as construction of DTI's Hyperion’s collocation space is approximately 50 percent completed, GTE will give DTI Hyperion notification, and such notification shall include scheduled completion and turnover dates.
1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTIHyperion. Should DTI Hyperion note any deviations from the plan agreed upon by GTE and DTI Hyperion at the customer meeting, and if such deviations were not requested by DTI or not required by laware due to the negligence of GTE, GTE shall correct such deviations at its own expense within 5 Business Daysdays.
Appears in 1 contract
Construction of Space. GTE will construct DTIELI's collocation space in --------------------- accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. In the alternative, XXX may arrange for a third party contractor that is acceptable to GTE to construct the collocation cage enclosure. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 Space will be constructed in 100 square foot increments, and but GTE shall work with XXX to construct space in less than a 100 square foot increment if insufficient space exists. The constructed space shall be designed so as to prevent unauthorized access.
1.11.2 a A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEI.
1.11.3 Modifications to the standard configuration set forth in Section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI XXX to implement such additional modifications as may be necessary to ensure that DTIELI's collocated space is protected from unauthorized access.
1.11.4 At such time as construction of DTIELI's collocation space is approximately 50 percent completed, GTE will give DTI XXX notification, and such notification shall include scheduled completion and turnover dates. GTE shall provide XXX with sufficient information to enable the Parties to establish firm CLLI codes and to order cross connections for the equipment XXX intends to locate in the space 30 days prior to the scheduled implementation date. The cross-connect circuits shall be provisioned in conjunction with the installation of the collocation equipment.
1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTIXXX within three (3) business days of completion of construction of collocated space. Should DTI XXX note any deviations from the plan agreed upon by GTE and DTI XXX at the customer meeting, and if such deviations were not requested by DTI XXX or not required by law, GTE shall correct such deviations at its own expense within 5 Business Days.
Appears in 1 contract
Samples: Interconnection, Resale and Unbundling Agreement (Pac-West Telecomm Inc)
Construction of Space. GTE will construct DTINT's collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access.
1.11.2 a A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac AC electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEI.
1.11.3 Modifications to the standard configuration set forth in Section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI NT to implement such additional modifications as may be necessary to ensure that DTINT's collocated space is protected from unauthorized access.
1.11.4 At such time as construction of DTINT's collocation space is approximately 50 percent completed, GTE will give DTI NT notification, and such notification shall include scheduled completion and turnover dates.
1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTINT. Should DTI NT note any deviations from the plan agreed upon by GTE and DTI NT at the customer meeting, and if such deviations were not requested by DTI NT or not required by law, GTE shall correct such deviations at its own expense within 5 five (5) Business Days.
Appears in 1 contract
Construction of Space. GTE will construct DTIKCC's collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access.
1.11.2 a A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEI.
1.11.3 Modifications to the standard configuration set forth in Section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI KCC to implement such additional modifications as may be necessary to ensure that DTIKCC's collocated space is protected from unauthorized access.
1.11.4 At such time as construction of DTIKCC's collocation space is approximately 50 percent completed, GTE will give DTI KCC notification, and such notification shall include scheduled completion and turnover dates.
1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTIKCC. Should DTI KCC note any deviations from the plan agreed upon by GTE and DTI KCC at the customer meeting, and if such deviations were not requested by DTI KCC or not required by law, GTE shall correct such deviations at its own expense within 5 Business Days.
Appears in 1 contract
Samples: Interconnection Agreement
Construction of Space. GTE will construct DTISETI's collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access.
1.11.2 a A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac AC electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEI.
1.11.3 Modifications to the standard configuration set forth in Section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI SETI to implement such additional modifications as may be necessary to ensure that DTISETI's collocated space is protected from unauthorized access.
1.11.4 At such time as construction of DTISETI's collocation space is approximately 50 percent completed, GTE will give DTI SETI notification, and such notification shall include scheduled completion and turnover dates.
1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTISETI. Should DTI SETI note any deviations from the plan agreed upon by GTE and DTI SETI at the customer meeting, and if such deviations were not requested by DTI SETI or not required by law, GTE shall correct such deviations at its own expense within 5 five (5) Business Days.
Appears in 1 contract
Construction of Space. GTE will construct DTIPhone Michigan's collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access.
1.11.2 a A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEI.
1.11.3 Modifications to the standard configuration set forth in Section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI Phone Michigan to implement such additional modifications as may be necessary to ensure that DTIPhone Michigan's collocated space is protected from unauthorized access.
1.11.4 At such time as construction of DTIPhone Michigan's collocation space is approximately 50 percent completed, GTE will give DTI Phone Michigan notification, and such notification shall include scheduled completion and turnover dates.
1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTIPhone Michigan. Should DTI Phone Michigan note any deviations from the plan agreed upon by GTE and DTI Phone Michigan at the customer meeting, and if such deviations were not requested by DTI Phone Michigan or not required by law, GTE shall correct such deviations at its own expense within 5 Business Days.
Appears in 1 contract
Construction of Space. GTE will construct DTIMEBTEL's collocation space in accord with the terms and conditions set forth in the applicable GTE state and federal EIS tariff. Additionally, GTE agrees to the following terms and conditions regarding construction of collocated space:
1.11.1 Space will be constructed in 100 square foot increments, and shall be designed so as to prevent unauthorized access.
1.11.2 a A standard 100 square foot cage shall have the following standard features:
(a) eight-foot high, nine gauge chain link panels;
(b) three of the panels listed at (a) above shall measure eight by ten feet, the fourth panel shall measure eight by seven feet;
(c) the door to the cage shall measure eight by three feet and shall also consist of nine gauge chain link;
(d) the cage shall be provided with one padlock set, with GTE retaining one master key;
(e) one ac AC electrical outlet;
(f) one charger circuit system;
(g) one electrical sub-panel;
(h) such additional lighting as may be necessary;
(i) one fire detection requirement evaluation;
(j) grounding for the cage consistent with COEICOEL.
1.11.3 Modifications to the standard configuration set forth in Section 1.11.2 can be made on an individual case basis. If modifications are agreed upon and made by the Parties, GTE will work with DTI MEBTEL to implement such additional modifications as may be necessary to ensure that DTIMEBTEL's collocated space is protected from unauthorized access.
1.11.4 At such time as construction of DTIMEBTEL's collocation space is approximately 50 percent completed, GTE will give DTI MEBTEL notification, and such notification shall include scheduled completion and turnover dates.
1.11.5 Upon completion of construction of collocated space, GTE will conduct a walk through of the collocated space with DTIMEBTEL. Should DTI MEBTEL note any deviations from the plan agreed upon by GTE and DTI MEBTEL at the customer meeting, and if such deviations were not requested by DTI MEBTEL or not required by law, GTE shall correct such deviations at its own expense within 5 five (5) Business Days.