Interconnection Customer’s Interconnection Facilities Sample Clauses

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer shall design, procure, construct, install, own and/or control the Interconnection Customer’s Interconnection Facilities described in Appendix A at its sole expense.
AutoNDA by SimpleDocs
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer shall, at its expense, design, procure, construct, own and install the Interconnection Customer’s Interconnection Facilities, as set forth in Appendix A. 5.10.1 Large Generating Facility and Interconnection Customer’s Interconnection Facilities Specifications. The Interconnection Customer shall submit initial specifications for the Interconnection Customer’s Interconnection Facilities and Large Generating Facility, including System Protection Facilities, to the Participating TO and the CAISO at least one hundred eighty (180) Calendar Days prior to the Initial Synchronization Date; and final specifications for review and comment at least ninety (90) Calendar Days prior to the Initial Synchronization Date. The Participating TO and the CAISO shall review such specifications pursuant to this LGIA and the LGIP to ensure that the Interconnection Customer’s Interconnection Facilities and Large Generating Facility are compatible with the technical specifications, operational control, safety requirements, and any other applicable requirements of the Participating TO and the CAISO and comment on such specifications within thirty (30) Calendar Days of the Interconnection Customer's submission. All specifications provided hereunder shall be deemed confidential.
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. As depicted on the one-line diagram in Attachment 3, the ICIF consist of the following:
Interconnection Customer’s Interconnection Facilities. ('ICIF'). Interconnection Customer shall, at its expense, design, procure, construct, own and install the ICIF, as set forth in Appendix A, Interconnection Facilities, Network Upgrades and Distribution Upgrades.
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- line diagram in Attachment 3, the ICIF consist of the following: 1. Grissom Solar Collector Substation
Interconnection Customer’s Interconnection Facilities. As depicted in Figure 1 in Attachment 3, the Interconnection Customer’s Interconnection Facilities (“ICIFs”) will consist of the following:
Interconnection Customer’s Interconnection Facilities. Interconnection Customer shall, at its expense, design, procure, construct, own and install the ICIF, as set forth in Appendix A. 5.10.1 Interconnection Customer’s Interconnection Facility Specifications. Interconnection Customer shall submit initial design and specifications for the ICIF, including Interconnection Customer’s System Protection Facilities, to Transmission Provider and Transmission Owner at least one hundred eighty 5.10.2 Transmission Provider’s and Transmission Owner’s Review. Transmission Provider’s and Transmission Owner’s review of Interconnection Customer’s final specifications shall not be construed as confirming, endorsing, or providing a warranty as to the design, fitness, safety, durability or reliability of the Generating Facility, or the ICIF. Interconnection Customer shall make such changes to the ICIF as may reasonably be required by Transmission Provider and Transmission Owner, in accordance with Good Utility Practice, to ensure that the ICIF are compatible with the technical specifications, operational control and safety requirements of Transmission Provider and Transmission Owner.
AutoNDA by SimpleDocs
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer shall: (i) Install a substation with one (1) 115/34.5/13.8kV wye grounded-wye grounded-delta main step-up transformer with a 9.5 percent impedance on a 94 MVA base. (ii) Install the Generation Tie-Line consisting of a new 2.25 mile, 1272 kcmil ACSR Bittern 115kV transmission line, with a normal (continuous) rating of 1184 Amps and a emergency (four-hour) rating of 1184 Amps, from the Large Generating Facility to a position designated by the Participating TO, outside of the Participating TO’s Coolwater 115kV Substation, where Interconnection Customer shall install a structure designed and engineered in accordance with the Participating TO’s specifications (“Last Structure”). The right-of-way for the Generation Tie-Line shall extend up to the edge of the Coolwater 115kV Substation property line. (iii) Install optical ground wire (“OPGW”) on the Generation Tie-Line to provide one of two telecommunication paths required for the line protection scheme and the remote terminal units (“RTUs”). A minimum of eight (8) strands within the OPGW shall be provided for the Participating TO’s exclusive use into Coolwater 115kV Substation. (iv) Install appropriate single-mode fiber optic cable from the Large Generating Facility to a point designated by the Participating TO near the Participating TO’s Coolwater 115kV Substation to provide the second telecommunication path required for the line protection scheme. A minimum of eight (8) strands within the single-mode fiber optic cable shall be provided for the Participating TO’s exclusive use. The telecommunication path shall meet the Applicable Reliability Standards criteria for diversity (v) Own, operate and maintain both telecommunication paths (including OPGW, any fiber-optic cables, and appurtenant facilities), with the exception of the terminal equipment at both Coolwater 115kV Substation and at the Large Generating Facility, which terminal equipment will be installed, owned, operated and maintained by the Participating TO. (vi) Allow the Participating TO to review the Interconnection Customer’s telecommunication equipment design and perform inspections to ensure compatibility with the Participating TO’s terminal equipment and protection engineering requirements; allow the Participating TO to perform acceptance testing of the telecommunication equipment and the right to request and/or to perform correction of installation deficiencies. (vii) Provide required data signals, make available adequ...
Interconnection Customer’s Interconnection Facilities. Interconnection Customer shall, at its expense, design, procure, construct, own and install the ICIF, as set forth in Appendix A. 5.10.1 Interconnection Customer’s Interconnection Facility Specifications. Interconnection Customer shall submit initial design and specifications for the ICIF, including Interconnection Customer’s System Protection Facilities, to Transmission Provider and Transmission Owner at least one hundred eighty 5.10.2 Transmission Provider’s and Transmission Owner’s Review. Transmission Provider’s and Transmission Owner’s review of Interconnection Customer’s final specifications shall not be construed as confirming, endorsing, or providing
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer constructed the Interconnection Customer’s Interconnection Facilities in accordance with the applicable requirements of Connecting Transmission Owner, to the extent not inconsistent with the terms of this Agreement or the NYISO OATT, and in accordance with the Connecting Transmission Owner’s project specific electrical requirements, to the extent not inconsistent with the terms of this Agreement or the NYISO OATT. As depicted in Attachment 3, Figures 1 and 2, the Interconnection Customer Interconnection Facilities consist of: The Collection Station (Jointly Owned Interconnection Facilities), including: One (1) 13.8 kV, 2500 A bus tie breaker; Relaying; (1) 3Ph, 75 kVA 13800/480-277V station service transformer; Six (6) 115 kV surge arresters; Two (2) 25/33/41.6 MVA 115/13.8Y kV transformers; Two (2) 13.8 kV, 2500 A breakers; Two (2) 115 kV, 1200A, 550 kV BIL oil circuit breakers; Two (2) 115 kV, 1200A motor operated, oil circuit breaker disconnect switches; Two (2) 115 kV, 1200 A, motor operated line disconnect switches; and Two (2) 115 kV, 1200 A, motor operated tie disconnect switches. Equipment in Switchgear, including, but not limited to: Two (2) 13.8 kV, 1200 A feeder breaker; Six (6) 12 kV station class surge arresters;