Motor Control Centers Sample Clauses

Motor Control Centers. This section covers the engineering, design, manufacture, installation and testing of indoor motor control centers. The motor control centers shall supply the 480 volt station auxiliary loads. The equipment shall be suitable for operation on a 480/277 volt, three-phase, 60 hertz, grounded service. Motor control centers shall conform to the requirements of UL 845, NEMA ICS1, NEMA ICS2, NEMA ICS4, and NEMA ICS6. Each Motor Control Center shall consist of one or more vertical sections and shall be designed to permit future additions, changes, or regrouping. As a minimum, one equipped spare space for a size 2 starter shall be provided for each vertical section. In addition, one spare combination starter of each size and -------------------------------------------------------------------------------- EPC - Exhibit B -------------------- TENASKA GEORGIA GENERATION PROJECT Page 93 of 132 -------------------------------------------------------------------------------- type less than size 5 shall be supplied in each Motor Control Center. The Motor Control Center assembly shall be of a nonventilating type. All enclosure vertical sections shall be mounted on continuous front and back channel iron xxxxx and bolted firmly together to form a rigid, freestanding, dead-front, completely enclosed, front line assembly. Vertical sections shall be formed of manufacturer's standard gauge sheet steel with uniform, blemish-free surfaces. Each vertical section may contain a maximum of six unit compartments. End sections shall have removable end closing plates, and provisions shall be provided for access to horizontal bus and horizontal wireways. Easily removable blank hinged doors shall cover all unused unit spaces. Bolted covers shall be furnished on the rear of the section. The vertical bus and its insulation in the rear section shall be covered with sheet metal plates suitable for mounting control and other devices. Conduit entrance space and wire entry room greater or equal to cross-sectional area of vertical wireways shall be provided at both the top and bottom of each section. Top and bottom horizontal wireways with full length continuity shall be provided. Wireways shall be isolated from the bus bars by barriers. A vertical wireway shall extend from the top horizontal wireway to the bottom horizontal wireway for the purpose of routing cables to control units. The wireway shall be isolated from all units and the bus bars to guard against accidental contact. A separate hinge...
AutoNDA by SimpleDocs
Motor Control Centers. The motor control center contains circuit protective devices and power distribution equipment to supply electrical power to all packaged power plant devices as defined on the electrical one line diagram. The motor control center is manufactured and tested in accordance with NEMA ICS-2 and UL Standard No. 845. Vertical sections and individual units will be UL (CSA) Labeled where possible. The motor control center is located in the PEECC.
Motor Control Centers o Distributed Control System. o CEMS/
Motor Control Centers. Motor control centers (MCCs) shall be used to consolidate certain motor controllers as depicted in References Error! Reference source not found. and (3C). MCCs shall provide electrical services to motor-driven rotating machinery operating on 3-phase, 3-wire ungrounded circuits supplied with a nominal voltage of 480 VAC. Each MCC branch circuit motor and motor control system shall provide stand-alone functionality. MCCs shall provide a means of disconnecting and locking out individual motor circuits at the motor control center. The disconnect device is to indicate whether the device is open or closed. Construct each MCC to meet the degree of protection suitable for the intended location. Design and construct the equipment to provide a dead front degree of construction. Unless otherwise approved by the Owner's Representative, front access for all serviceable components is required. Service access from the rear shall be limited to maintenance of bus connections, circuit breaker stab connections to field loads and making up ship's cable and shipping splits on installation as applicable. MCCs shall be Square D or equal. Enough sections shall be provided at each MCC to house each motor controller shown in Reference (3C) with a 20% margin for future controller addition or two (2) additional sections, whichever is greater.

Related to Motor Control Centers

  • SPECIAL SERVICES Should the Trust have occasion to request the Adviser to perform services not herein contemplated or to request the Adviser to arrange for the services of others, the Adviser will act for the Trust on behalf of the Fund upon request to the best of its ability, with compensation for the Adviser's services to be agreed upon with respect to each such occasion as it arises.

  • Janitorial Services Tenant will not employ any person for the purpose of cleaning the Premises or permit any person to enter the Building for such purpose other than Landlord's janitorial service, except with Landlord's prior written consent. Tenant will not necessitate, and will be liable for the cost of, any undue amount of janitorial labor by reason of Tenant's carelessness in or indifference to the preservation of good order and cleanliness in the Premises. Janitorial service will not be furnished to areas in the Premises on nights when such areas are occupied after 9:30 p.m., unless such service is extended by written agreement to a later hour in specifically designated areas of the Premises.

  • Administration of Equipment 24 6.4.1. Records and Schedules of Equipment...................................................................24 6.4.2. Dispositions of Equipment............................................................................24 6.5.

  • Utility Services Company agrees to pay the full cost and expense associated with its use of all utilities, including but not limited to water, sanitary sewer, electric, storm drainage, and telecommunication services.

  • Janitorial Service Landlord shall not be obligated to provide any janitorial services to the Premises or replace any light bulbs, lamps, starters and ballasts for lighting fixtures within the Premises. Tenant shall be solely responsible, at Tenant’s sole cost and expense, for (i) performing all janitorial services, trash removal and other cleaning of the Premises, and (ii) replacement of all light bulbs, lamps, starters and ballasts for lighting fixtures within the Premises, all as appropriate to maintain the Premises in a first-class manner consistent with the first-class nature of the Building and Project. Such services to be provided by Tenant shall be performed by contractors and pursuant to service contracts approved by Landlord. Tenant shall deposit trash as reasonably required in the area designated by Landlord from time to time. All trash containers must be covered and stored in a manner to prevent the emanation of odors into the Premises or the Project. Landlord shall have the right to inspect the Premises upon reasonable notice to Tenant and to require Tenant to provide additional cleaning, if necessary. In the event Tenant shall fail to provide any of the services described in this Section 6.6 to be performed by Tenant within five (5) days after notice from Landlord, which notice shall not be required in the event of an emergency, Landlord shall have the right to provide such services and any charge or cost incurred by Landlord in connection therewith shall be deemed Additional Rent due and payable by Tenant upon receipt by Tenant of a written statement of cost from Landlord.

  • ELECTRICAL SERVICES A. Landlord shall provide electric power for a combined load of 3.0 xxxxx per square foot of useable area for lighting and for office machines through standard receptacles for the typical office space.

  • Telecommunications Services The offering of telecommunications for a fee directly to the public, or to such classes of users as to be effectively available directly to the public, regardless of the facilities used.

  • Equipment, Etc Each Grantor shall, (i) within ten (10) days after a written request by the Administrative Agent, in the case of Equipment now owned, and (ii) following a request by the Administrative Agent pursuant to subclause (i) above, within ten (10) days after acquiring any other Equipment, deliver to the Administrative Agent, any and all certificates of title, and applications therefor, if any, of such Equipment and shall cause the Administrative Agent to be named as lienholder on any such certificate of title and applications. No Grantor shall permit any such items to become a fixture to real estate or an accession to other personal property unless such real estate or personal property is the subject of a fixture filing (as defined in the UCC) creating a first priority perfected Lien in favor of the Administrative Agent.

  • Personal Services 1. Subject to the provisions of Articles 14, 16 and 17, salaries, wages and other similar remuneration or income derived by a resident of a Contracting State in respect of personal (including professional) services shall be taxable only in that State unless the services are rendered in the other Contracting State. If the services are so rendered, such remuneration or income as is derived therefrom may be taxed in that other State.

  • Additional Equipment Additional Equipment may from time to time be added as the subject matter of this Agreement as agreed on by the parties. Any additional property will be added in an amendment describing the property, the monthly rental, security deposit, and stipulated loss value of the additional Equipment. All amendments must be in writing and signed by both parties. Other than by this amendment procedure, this Agreement may not be amended, modified, or altered in any manner except in writing signed by both parties.

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!