The 'Newfoundland Power' clause typically defines the rights, obligations, or specific considerations related to the utility company Newfoundland Power within a contract. This clause may outline responsibilities for providing electrical service, payment terms, or procedures for addressing outages or service interruptions as they pertain to Newfoundland Power. Its core function is to clarify the relationship and expectations between the contracting parties and Newfoundland Power, ensuring that all parties understand their roles and responsibilities regarding electrical utility services.
Newfoundland Power. When specified, the transformer shall have two 2-’4% taps above rated voltage and two 2-V2% taps below rated voltage on the high voltage winding. Units for Maritime Electric shall be equipped with taps as indicated above.
Newfoundland Power. Transformer shall be painted equipment green ▇▇▇▇▇▇▇ 9 GY 1.5/2.6. ▇▇▇▇▇▇▇ ▇▇▇▇ shall also be provided if specified in the tender document.
Newfoundland Power. The low voltage terminals shall be unplated aluminum spade type and the X2 to X3 jumper strap, where required, shall be one-piece unplated aluminum. All material is to be extruded aluminum alloy type 6061 with galvanized hardware.
Newfoundland Power. All fastening hardware used to secure the cover and external connections is to be stainless steel or silicon bronze. September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work Preference is for non-cover band designs. However, if supplied, cover bands are to be 316L stainless steel secured with stainless steel hardware (Silicon Bronze Nut). Cover clamp designs must have a protective barrier between the clamp and cover to protect the paint finish.
Newfoundland Power. Each transformer shall be shipped on a pallet as a completely assembled unit. Each transformer shall be suitably packed so as to insure delivery in good condition. Each transformer shall be shipped in an open-top carrier so as to allow easy removal with a crane. September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work NOTE: Four lifting bosses and bolts to be supplied and positioned such that balance is maintained when lifted. September 1, 2006 Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work
Newfoundland Power. Edges of the transformer cover and outer edge of the upper mounting bracket shall have sharp edges removed.
Newfoundland Power. Terminals for all sizes of transformers shall be bronze or copper tin plated bar type. Low voltage terminals for transformer sizes up to, and including, 167 kVA shall be in accordance with. Figure 9(a) of DTWG-02.
Newfoundland Power. Minimum impedances shall be per DTWG-02 (99) Clauses 4.10 and 11.1(n) as follows: 50kVa 1.5% 75 kVA 2.0% 100-167 kVA 2.5% September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work
Newfoundland Power. Each transformer shall be shipped on a pallet as a completely assembled unit and suitably packed so as to insure delivery in good condition. Each transformer shall be shipped in an open-top carrier so as to allow easy removal with a crane. September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule B – Statement of Work September 1, 2006 Distribution Transformers Newfoundland Power Inc. Schedule C – Payment for Work
Newfoundland Power. Transformers with high voltage loop feed shall have the loop feed feature internally connected and capable of carrying 200 Amperes (continuous) and 10,000 Amperes (Symmetrical) for 0.17 seconds, minimum X/R = 6.