Actual Roundtrip Efficiency Clause Samples

Actual Roundtrip Efficiency. The Actual Roundtrip Efficiency shall be calculated and recorded to determine the amount of energy the Project can deliver relative to the amount of Energy injected into the system during the preceding charge. The Actual Roundtrip Efficiency of the Project for the billing Month shall be determined in accordance with the equation below from the recorded and measured data. Where: MWhdelivered = measured and recorded energy delivered from the storage system at the Delivery Point for the billing Month, all Station Service Energy will be excluded from MWhdelivered. MWhreceived = measured and recorded energy received during charging of the storage system at the Delivery Point for the billing Month, all Station Service Energy will be excluded from MWhreceived. Stored Energyend = available energy in the battery at the end of the efficiency measurement period. Stored Energystart = available energy in the battery at the start of the efficiency measurement period
Actual Roundtrip Efficiency. The Actual Roundtrip Efficiency shall be calculated and recorded to determine the amount of energy the Project can deliver relative to the amount of Energy injected into the system during the preceding charge. The Actual Roundtrip Efficiency of the Project shall be determined in accordance with the equation below from the recorded and measured data. 𝑅𝑜𝑢𝑛𝑑𝑡𝑟𝑖𝑝 𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = MWh delivered + Stored Energyend