Backup Generator. 1. Emergency backup power will be supplied by a permanently installed generator capable of providing adequate power to the well. The generator will be capable of producing 400KV. The generator will have a fuel tank capable of a run duration of 24hrs. Generator will be installed upon a steel re−enforced concrete base and anchored securely. Installation will include 3” Steel fuel lines run under ground between a 2000−gallon fuel tank and the generator. Concrete filled steel bollards will be installed around the fuel tank to assist in preventing vehicle or equipment impact. 2. A single 2000−gallon tank will be furnished and installed to accommodate the 400KV generator. The tank will be fabricated to the latest ASME code, Section VIII, Division 1. The tank will be equipped with liquid withdrawal and vapor withdrawal port. This tank is also equipped with safety relief valving. 3. A steel reinforced concrete pad will be installed approx. 50’ from any other structure per regulatory specifications to accommodate the tank. The pad will be approximately 25’ x 6’x 6” and be formed and poured with 4500PSI pea gravel pump mix concrete.