Battery Charging Area Clause Samples
Battery Charging Area. The battery charging area will be provided with a dedicated exhaust system designed to meet IFC 608 requirements. This exhaust system will be tied to a make-up air unit which will provide adequate fresh air the area to ensure hydrogen out-gassing is maintained below hazardous levels. Compressor and liquid waste rooms systems shall be in compliance with IFC 57 requirements including quantities and categories stored. Laundry rooms will be provided with cascaded Class 1 or 2 air for dryer makeup. No air will be returned from laundry rooms. Tamco Series 9000 BF dampers will be provided at all building air intake and discharge locations to ensure positive shutoff. Hoods will be provided over each louver to reduce entrainment of snow. Intake hoods will be provided with a basin and drain to evacuate any snowmelt within the duct. Outside air intake ductwork will be insulated to prevent frost buildup and protect the building thermal envelope. Where passive intake systems do not prevent snow and ice blockage, active heating systems may be required at air intake ductwork to remove entrained snow and ice.
Battery Charging Area. In battery charging area(s) (3), as shown on Exhibit 1-D, provide all requirements per all applicable codes, including eyewash stations, air ventilation, floor drain, and acid proof epoxy floor coatings. Provide caulking at windows, exterior doors, control joints, exterior and interior joints between exterior wall panels, etc. Slab control joint caulking will be provided only as per 3.5.1 above.