Configuring The Transceiver For Internal Network Sample Clauses

Configuring The Transceiver For Internal Network. The Transceiver needs to be assigned an Identifier Address for device internal use. To enter the Transceiver Unit ID into the Configuration File, click on the Menu Comm > Unit Identifier. • Click on the drop-down menu arrow and select the Transceiver Unit Default ID of “1” from the drop-down menu and click “OK”. • Click on Menu - Comm > Serial Transport to activate the Serial Comm Port dialog box. • Use the Serial Comm Port configuration dialog box to select the appropriate internal communication parameters (Connect Speed, Connect Preferences, and Transport Mode) for the Transceiver. • The MOD9200LON requires internal communication parameters to be set as follows: Maximum Speed = 38400 BPS (This communication speed is set for internal use by the MOD9200LON Transceiver and it will not change the external LonWorks communication speed of 78 KBPS) Data Bits = 8 Parity = none Stop Bit = 1 Modbus Transport = RTU The MOD9200LON Transceiver transmission mode and serial port parameters need to be exactly the same as shown above. • To Save the configuration file click on File > Save. It is recommended that the .ini file be saved in the Trs folder already setup. i.e. C:\trs\config