Cooling Availability Clause Samples

Cooling Availability. Target ambient room temperature will be 22 Degrees Celcius in the server area of the Data Centre. Ambient room temperature will not vary by more than +/- 1 degree. BT shall guarantee that the Cooling Availability on the Heating Ventilation and Air Conditioning (HVAC) facilities within the BT Suite upto 99.99% in a calendar month based on the following formulae. TotalAvailableTime − TotalOutage Cooling Availability (%) = .
Cooling Availability. The Air-conditioning Availability shall be 99.99% on a monthly basis in accordance with the following specifications: (i) deviations of no more than 2 deg C on a daily basis under 100% Equipment load condition; and (ii) Equipment load condition.