Fuel Oil System Sample Clauses

Fuel Oil System. 1. Provide a system of fuel oil storage and distribution for the emergency generator plant. Provide two (2) buried fiberglass fuel oil storage tanks of 25,000 gallons capacity each. Fuel oil storage will provide for two days operation at full load based on ultimate generator plant capacity of six (6) engines running at 1,400 kw. each (8,400 kw. total).
Fuel Oil System. A2.1.1 Gas oil (GO) Fuel System (for black start sets and back-up) Piping, pumps and valves GO fuel 1 1 system (lot) (from GO storage/treatment tank to common treatment module) Treated GO service tank 1 1 GO pump and filters 1 1
Fuel Oil System. 1. Generator An above slab steel (20,000 gallon) fuel oil tank located in the lowest cellar will be provided to service the boilers and building generator. The system will include fuel oil fill and vent lines, fuel oil tank, duplex fuel oil transfer pumps, fuel oil transfer piping (supply and return). Horizontal piping within the building shall be pipe within a pipe construction with an additional 2-hour fire rated enclosure system and vertical piping shall be enclosed in 2-hour fire rated masonry construction. The fuel oil tank will be sized to accommodate minimum code requirements. Generator(s) will be located on the Roof Mechanical Equipment Room. Fill box and containment design shall be as per EPA and NYC requirements. A 275-gallon day tank will be provided for fuel-oil feed on the Roof Mechanical Equipment Room. Space for a future Tenant generators and risers are available. All equipment and associated material is by Tenant.