Line 7 Protection Packages. The existing Line 7 relays can be re-used and shall be reset to accommodate interconnection of the Small Generating Facility. Interconnection of the Small Generating Facility will require the addition of DTT transmit and receive to the Grissom Solar Collector Substation. A new GARD 8000 shall be installed for communication with the Grissom Solar Collector Substation. DTT will be sent to the Grissom Solar Collector Substation for a line relay operation or R7 breaker failure. DTT for breaker failure will be received from Grissom Solar Collector Substation. A SEL 351-6 relay will be added for DTT receive supervision and will be used to trip and drive reclosing to lockout. (Note: Due to the addition of the Small Generating Facility, an area coordination study will be completed during final engineering and may result in resetting of relays in the area. The Interconnection Customer shall be responsible for all costs associated with this.)