The 'Power System Particulars' clause defines the specific technical and operational details of the power system relevant to the contract. It typically outlines parameters such as voltage, frequency, capacity, and configuration of the power system components to be supplied or operated. By clearly specifying these particulars, the clause ensures that both parties have a mutual understanding of the system requirements, reducing the risk of disputes or misunderstandings regarding performance expectations.
Power System Particulars;. The plant and materials supplied shall be suitable in all respect for continuous operation in the existing system having the following data: Normal Voltage 415V 11KV 33KV Maximum Voltage 500V 12 KV 36KV No. Of phases 3 3 3 System frequency (Hz) 50 50 50 No. of wires 5 3 3 Fault level (MVA) 25 350 1500 Fault Current / Duration * * 25 kA / 3s Earth Fault Current / Duration * 3 kA / 3 s 3 kA / 3 s Neutral point Earthing Solid Resistance Resistance Conductor arrangement Vertical Horizontal Horizontal
Power System Particulars;. The plant and materials supplied shall be suitable in all respect for continuous operation in the existing system having the following data: 1 Normal Voltage 415V 11KV 33KV 2 Maximum Voltage 500V 12KV 36KV
Power System Particulars;. The plant and materials supplied shall be suitable in all respect for continuous operation in the existing system having the following data: 1 Normal Voltage 415V 11KV 33KV 2 Maximum Voltage 500V 12KV 36KV 3 No. Of phases 3 3 3 4 System frequency (Hz) 50 50 50 5 No. of wires 5 3 3 6 Fault level (MVA) 25 350 1500 7 Fault Current / Duration * * 25 kA / 3s 8 Earth Fault Current / Duration * 3 kA / 3s 3 kA / 3s 9 Neutral point Earthing Solid Resistance Resistance 10 Conductor arrangement Vertical Horizontal Horizontal
Power System Particulars;. The plant and materials supplied shall be suitable in all respect for continuous operation in the existing system having the following data: All low voltage equipment must be capable of operating within range of +10% to –15% of the rated voltage, tripping devices shall be capable of operating within the range +10% to –25% of the rated voltage.
Power System Particulars;. The plant and materials supplied shall be suitable in all respect for continuous operation in the existing system having the following data: 1 Normal Voltage 415V 11KV 33KV 2 Maximum Voltage 500V 12KV 36KV 3 No. Of phases 3 3 3 4 System frequency (Hz) 50 50 50 5 No. of wires 5 3 3 6 Fault level (MVA) 25 350 1500 7 Fault Current / Duration 120KA/3S * 25 kA / 3s 8 Earth Fault Current / Duration * 3 kA / 3s 3 kA / 3s 9 Neutral point Earthing Solid Resistance Resistance 10 Conductor arrangement Vertical Horizontal Horizontal ⮚ Technical Specifications for Item no.1: Rated 36 KV, Single Core Cable, Aluminum Conductor of 400 mm2, XLPE Insulated, Copper Wire Screened, Aluminum Wire Armored, And PVC Sheath. ◼ As per the details a) Depth of laying 1.4m b) Ground temperature 25 Co at 1.2 m c) Solid thermal resistively 1, 75 Co m/ w d) Spacing between circuits 0.55 m