Common use of Supply Considerations Clause in Contracts

Supply Considerations. 1.1.1 A high-voltage interrupting device (HVI) shall provide a point of isolation for the Generator=s station from the transmission system. HVIs shall be provided with appropriate back-up protection. The HVI shall be a circuit breaker unless the Transmitter authorizes another device. 1.1.2 The HV side of the Generator=s transformer shall be protected by surge arresters. 1.1.3 All protection systems shall be redundant and be complete with separate trip auxiliary relays and separately fused DC supplies. 1.1.4 The standard transformer winding connection for large Generators is LV delta B HV wye. Any other winding connections shall require the approval of the Transmitter. The Transmitter shall give its approval if it is satisfied that the reliability of its transmission system is not affected. 1.1.5 The method of grounding the neutral of all power transformer primary windings shall require the approval of the Transmitter. The Transmitter shall give its approval if it is satisfied that the reliability of its transmission system is not affected.

Appears in 2 contracts

Samples: Connection Agreement, Connection Agreement

AutoNDA by SimpleDocs

Supply Considerations. 1.1.1 A high-voltage interrupting device (HVI) shall provide a point of isolation for the Generator=s ’s station from the transmission system. HVIs shall be provided with appropriate back-up protection. The HVI shall be a circuit breaker unless the Transmitter authorizes another device. 1.1.2 The HV side of the Generator=s ’s transformer shall be protected by surge arresters. 1.1.3 All protection systems shall be redundant and be complete with separate trip auxiliary relays and separately fused DC supplies. 1.1.4 The standard transformer winding connection for large Generators is LV delta B HV wye. Any other winding connections shall require the approval of the Transmitter. The Transmitter shall give its approval if it is satisfied that the reliability of its transmission system is not affected. 1.1.5 The method of grounding the neutral of all power transformer primary windings shall require the approval of the Transmitter. The Transmitter shall give its approval if it is satisfied that the reliability of its transmission system is not affected.

Appears in 2 contracts

Samples: Connection Agreement, Connection Agreement

AutoNDA by SimpleDocs
Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!