Common use of Technical Requirements for Substations Clause in Contracts

Technical Requirements for Substations. The reactors must be supplied with current transformers incorporated in bushings, two 5P20 protection cores, in the three phases and neutral terminal, in addition to the corresponding core for thermal image protection. The reactance, power and definitive characteristics of the equipment shall be determined by the Concessionaire in accordance with what is defined, substantiated and approved in the Preoperative Study.

Appears in 2 contracts

Samples: Concession Agreement, Concession Agreement

AutoNDA by SimpleDocs

Technical Requirements for Substations. The reactors must shall be supplied provided with current transformers incorporated in built into insulating bushings, phase side and neutral side, of two cores with 5P20 protection coresprotection, apart from the current transformers in the three phases and neutral terminal, in addition to of the corresponding core for thermal image protectionthree-phase assembly. The reactance, reactance and power values and definitive final characteristics of the equipment shall be determined by the Concessionaire in accordance with what is definedConcession Holder, substantiated as determined, supported and approved in the Preoperative Pre- Operability Study.

Appears in 2 contracts

Samples: SGT Concession Contract, SGT Concession Contract

AutoNDA by SimpleDocs
Time is Money Join Law Insider Premium to draft better contracts faster.