Telecommunication Room's Power Clause Samples
Telecommunication Room's Power. A dedicated power panel shall be provided to serve the telephone and data systems within the Telecommunication room exclusively. This panel shall be surge and spike protected, unless power to the room is serviced from any Uninterruptable Power Supply (See Exhibit E). Distribution within the room may be via surface mounted raceways. Room power shall be provided for, but not limited to, the following:
1. Dedicated, isolated ground, 20 amp, 120 volt circuits fed from this panel shall service receptacles at the following locations:
a. At the Central Patch Panel (Item No. 17 in Exhibit "A") racks; one circuit terminating in power strip (Wiremold 200 Plugmold 20-IG-306) installed on the back of the vertical wire management system for each open relay rack.
b. At the telephone switch. (Power requirements shall be provided by the Allstate representative.)
c. At each telephone "phone mail" or similar device. (Power requirements and receptacle configuration shall be provided by the Allstate representative.)
d. At each controller, server, modem and/or CPU. (Power requirement and receptacle configurations shall be provided by the Allstate representative.) A minimum of one (1) receptacle for each two (2) controllers, each server and the security main console.
2. Power and telecommunication services shall be located for two workstations within the room to be utilized on a part-time basis.
3. A dedicated, 120V, 20 amp circuit terminated in two separated duplex receptacles intended for printers within the room.
4. Other services prearranged or specified by Allstate. (UPS is recommended for all equipment within the Telecommunication Room.) A copper grounding bar, 1/4" x 2-1/2" x 24" shall be provided on the wall near the open relay rack(s). A #6 AWG green colored insulated ground wire shall be installed from the bar to the derived power system ground terminal. Resistance at the bar shall not exceed 25 ohms. A #6 AWG ground wire shall be connected from each rack to the bar.