Temperature Controls. Discharge air temperature from the heating coils and reheat coils shall be independently controlled. Discharge air temperature sensors shall control the leaving air temperature from the HVAC unit heating coils. Zone thermostats shall control the discharge temperature from the reheat coils. Variations in temperature within each control zone, and between zones, shall not exceed 40F, with the temperature measured from a reference point 1’ inside of any exterior wall to the center of the building. The temperature variation from the floor to a height of 30” for any employee work station (either conventional desk or systems furnishings cubicle) shall not exceed 20F. Testing shall be made when the exterior temperature has reached a daily low of 200F or more for 2 days.