Operation Agreement for
Qualifying Facilities with Generating Capacity
Greater Than 5 MW
THIS AGREEMENT (the "Agreement") is made and entered into this 1st day of
January, 2003 (the "Effective Date"), by and between Green Power Kenansville LLC
which is located at 0000 Xxxxxxxx Xxxx, Xxxxxxxxxx, XX 00000, sometimes
hereinafter referred to as "Seller", and Carolina Power & Light Company (CP&L"),
a subsidiary of Progress Energy Inc., a corporation organized and existing under
the laws of the State of North Carolina , sometimes hereinafter referred to as
"Company". Seller and Company each may be referred to as a "Party," or
collectively as the "Parties."
WITNESSETH:
WHEREAS, Seller owns and operates a 35 MW electric generating facility
located near Kenansville, NC (the "Facility"); and
WHEREAS, the Facility is located adjacent to and physically interconnected
with the transmission facilities of Company;
WHEREAS, Seller has agreed to sell energy or capacity or both to Company as
a Qualifying Facility under the Public Utility Regulatory Policies Act of 1978
(PURPA) pursuant to (1) the Company's form of Application for Standard Contract
by a Qualifying Cogenerator or Small Power Producer when signed by Seller and
accepted by Company, (2) Schedule CSP-20B and any applicable Riders, and (3) the
Terms and Conditions for the Purchase of Electric Power for Qualifying
Facilities with Generating Capacity Greater than 5 MW (hereinafter referred to
as "Terms and Conditions"),and
WHEREAS, Seller has requested, and Company has agreed to enter into, an
operation and interconnection agreement with Seller to govern the terms of
interconnection of the Facility with the Company Transmission System (hereafter
defined);
NOW, THEREFORE, in consideration of and subject to the mutual covenants
contained herein, it is agreed:
1.0 DEFINITIONS
(a) "Company Transmission System" shall mean all the facilities owned or
controlled by Company on Company's side of the Points of Interconnection.
(b) "Emergency" shall mean an imminent or occurring condition on the Company
Transmission System, on the system of a neighboring utility, or in the
Facility, that is likely to impair system reliability, cause an
unacceptable change in system or facility voltage or frequency, or
otherwise result in significant disruption of service or damage to any of
the foregoing, or is likely to endanger life, property or the environment;
provided, however, that the inability of Company to meet its load
requirements because of insufficient generation shall not constitute an
Emergency.
Page 1
(c) "Facility" shall mean Seller's electric generating facility identified in
the APPLICATION FOR STANDARD CONTRACT BY A QUALIFYING COGENERATOR OR SMALL
POWER PRODUCER together with the other property, facilities, and equipment
owned and/or controlled by Seller on Seller's side of the Point of
Interconnection.
(d) "Facility Operator" shall mean the entity that operates the Facility.
(e) "Good Utility Practice" shall mean any of the practices, methods and acts
engaged in or approved by a significant portion of the electric utility
industry during the relevant time period, or any of the practices, methods
and acts which, in the exercise of reasonable judgment in light of the
facts known at the time the decision was made, could have been expected to
accomplish the desired result at a reasonable cost consistent with good
business practices, reliability, safety and expedition. Good Utility
Practice is not intended to be limited to the optimum practice, method, or
act to the exclusion of all others, but rather to be acceptable practices,
methods, or acts generally accepted in the region.
(f) "Joint Use Facilities" shall mean facilities and equipment which are
identified as Joint Use Facilities in 9.4.1, as it may be amended from time
to time, which are owned by either Company or Seller and are or may be
operated jointly by Company and Seller.
(g) "Modification(s)" shall mean any alteration, augmentation, removal,
upgrade, replacement, including any changes in design, configuration or
change in maximum facility output.
(h) "NERC" shall mean the North American Electric Reliability Council, or its
successor.
(i) "RTO" shall mean a Regional Transmission Organization pursuant to FERC
Order 2000.
(j) "SERC" shall mean the Southeastern Electric Reliability Council, or its
successor.
(k) "VACAR" shall mean the Virginia Carolinas Reliability Agreements.
2.0 CONDITIONS OF SERVICE
2.1 Company is not obligated to purchase electricity from Seller unless and
until: (1) Company's form of Application for Standard Contract by a Qualifying
Cogenerator or Small Power Producer is executed by Seller and accepted by
Company; (2) in cases where it is necessary to cross private property to accept
delivery of electricity from Seller, Seller conveys or causes to be conveyed to
Page 2
Company, without cost to Company, a right-of-way easement, satisfactory to
Company, across such private property which will provide for the construction,
maintenance, and operation of Company's lines and facilities, necessary to
receive electricity from Seller; provided, however, in the absence of a formal
conveyance, Company nevertheless, shall be vested with an easement over Seller's
premises authorizing it to do all things necessary including the construction,
maintenance, and operation of its lines and facilities for such purpose; and (3)
any inspection certificates or permits that may be required by law in the local
area are furnished to Company. Where not required by law, an inspection by a
Company-approved inspector shall be made at Seller's expense. In the event
Seller is unable to secure such necessary rights-of-way, Seller shall reimburse
Company for all costs Company may incur for the securing of such rights-of-way.
2.2 Seller's interconnection facilities shall be designed to accepted
engineering standards and Seller shall submit a facility description, including
equipment specifications, to Company for review prior to the connection of said
facility and equipment to Company's system. Company's review shall not be
construed as confirming nor endorsing Seller's design nor as any warranty as to
the safety, durability, or reliability of Seller's facility or equipment.
Company shall not, by reason of its review or failure to review, be responsible
for strength, details of design, adequacy, or capacity of Seller's facility or
equipment, nor shall Company's acceptance be deemed to be an endorsement of any
facility or equipment.
2.3 If electricity is received through lines which cross the lands of the United
States of America, a state, or any agency or subdivision of the United States of
America or of a state, Company shall have the right, upon 30 days' written
notice, to discontinue receiving electricity from any Seller or Sellers
interconnected to such lines, if and when (1) Company is required by
governmental authority to incur expense in the relocation or the reconstruction
underground of any portion of said lines, unless Company is reimbursed for such
expense by Sellers or customers connected thereto, or (2) the right of Company
to maintain and operate said lines shall be terminated, revoked, or denied by
governmental authority for any reason.
2.4 The Company and the Seller have an existing Facility Interconnection and
Operating Agreement dated January 18, 2002 on file with the Federal Energy
Regulatory Commission, Docket No. ER02-1569-000 (the "FERC Interconnection
Agreement"). This Agreement, and not the FERC Interconnection Agreement, shall
govern as long as the Seller is operating the facility solely as a Qualifying
Facility under PURPA and selling either capacity or energy or both to Company.
3.0 OPERATIONS
3.1 General. Company and Seller agree that their respective performances of this
Agreement shall comply with the then-existing (or amended) manuals, standards,
and policies of NERC, SERC, VACAR or RTO or any successor agency assuming or
charged with similar responsibilities related to the operation and reliability
Page 3
of the North American electric interconnected transmission grid. To the extent
that this Agreement does not specifically address or provide the mechanisms
necessary to comply with such NERC, SERC, VACAR or RTO manuals, standards or
policies, Company and Seller hereby agree that both Parties shall provide to the
other Party all such information as may reasonably be required to comply with
such manuals, standards or guidelines and shall operate, or cause to be
operated, their respective facilities in accordance with such manuals, standards
or policies.
3.2 Company Obligations. Company shall operate and control the Company
Transmission System and other Company facilities (1) in a safe and reliable
manner; (2) in accordance with Good Utility Practice; (3) in accordance with
NERC, SERC, VACAR or RTO manuals, standards or policies; and (4) in accordance
with the provisions of this Agreement.
3.3 Seller Obligations. Seller shall operate and control the Facility (1) in a
safe and reliable manner; (2) in accordance with Good Utility Practice; (3) in
accordance with NERC, SERC, VACAR or RTO manuals, standards or policies; and (4)
in accordance with the provisions of this Agreement, including the
Interconnection Operating Requirements set forth in Appendix A.
3.4 Switching and Tagging Rules. The Parties shall abide by the Company's
Switching and Tagging Rules for obtaining clearances for work or for switching
operations on equipment as set forth in Appendix A. With regard to Joint Use
Facilities, the Parties will follow the Switching and Tagging Rules in order to
obtain clearances for work on equipment requiring switching of both Parties'
facilities.
3.5 Joint Use Facilities. In accordance with mutually-agreed upon procedures,
Company and Seller shall jointly operate the Joint Use Facilities in accordance
with Good Utility Practice, including, but not limited to: (1) closing breakers
to accomplish interconnection, but not synchronization, of the Facility to the
Company Transmission System; (2) opening breakers to remove the Facility from
service; (3) operating disconnect and ground switches as required; (4)
in-service relay testing; and (5) battery system testing and maintenance.
3.5.1 Joint Use Facilities consist of the joint operation of the Company
owned 115 kV circuit breaker included in the Company's Interconnection
Facilities with operation in accordance with the Interconnection Operating
Requirements in Appendix A.
Page 4
3.6 Voltage Control and Reactive Power.
3.6.1 Operating Requirements. The Facility will supply reactive power to,
and absorb reactive power from, the Company Transmission System during
periods of time that its Facility is connected to and operating in parallel
with the Company Transmission System. Seller shall respond to requests from
Company to increase or decrease the Facility's reactive power output in a
manner consistent with Seller's obligation to operate the Facility: (1) in
a safe and reliable manner; (2) in accordance with Good Utility Practice;
(3) in accordance with NERC, SERC, VACAR or RTO manuals, standards or
policies; and (4) in accordance with the provisions of this Agreement. The
Facility shall generate such reactive power in accordance with the voltage
schedule, reactive schedule or power factor schedule, whichever is
applicable, prescribed by Company, but not in excess of the amount
available from the Facility's equipment in operation at the time. In the
event that the schedule prescribed by Company cannot or is not maintained,
Company may direct the Facility to be operated at its maximum available
reactive capability. In addition, Seller shall promptly take other steps as
necessary to allow the Facility to maintain its schedule. The excitation
system shall normally be operated in the automatic mode. Operation in the
manual mode for extended periods is permitted only with prior approval of
Company. Seller shall have a maintenance and testing program for excitation
systems in compliance with applicable NERC, SERC, VACAR or RTO manuals,
standards or policies and Good Utility Practice. Seller shall have a
testing program to verify the gross and net reactive power capability of
the Facility. Such program shall be in compliance with NERC, SERC, VACAR or
RTO manuals, standards or policies and results of such tests shall be
provided to Company upon request.
3.6.2 Emergency Reactive Power Requirements. When Company declares an
Emergency Condition on the Transmission System or on an adjacent
transmission system, Company shall have the authority to direct Seller to
increase or decrease real power production (measured in MW) and/or reactive
power production (measured in MVAR), within the design and operational
limitations of the Facility equipment in operation at the time, in order to
maintain Transmission System security. In the event of a declaration of an
Emergency Condition, a determination: i) that the Transmission System
security is in jeopardy, and ii) that there is a need to increase or
decrease reactive power production, even if real power production is
adversely affected, will be made solely by Company. The Facility Operator
will honor Company's orders and directives concerning Facility real power
and/or reactive power output within the design limitations of the
Facility's equipment in operation at the time, such that the security of
the Transmission System is maintained. Company shall restore Transmission
System conditions to normal as quickly as possible to alleviate any such
Page 5
Emergency Condition. Company will take all reasonable steps to allocate
among all generating units and other reactive power supply resources the
responsibility to provide reactive power support to the Transmission
System.
3.6.3 Seller shall operate to maintain the schedule provided under Section
3.6.1 within the following limits.
3.6.3.1 For reactive schedules, Seller shall operate between +/- 10 %
of the reactive schedule provided to them by the Company.
3.6.3.2 For voltage schedules, Seller shall operate within +/- 1.5 %
of the voltage schedule provided to them by the Company.
3.7 Seller's Operating Expenses. Seller shall be responsible for all expenses
associated with operating its own property, equipment, facilities, and
appurtenances on Seller's side of the Points of Interconnection.
3.8 Protection and Power Quality. Seller shall, at its expense, install,
maintain, and operate System Protection Facilities, including such protective
and regulating devices as are identified by order, rule or regulation of any
duly constituted regulatory authority having jurisdiction, or as are otherwise
necessary to protect personnel and equipment and to minimize deleterious effects
to Company's electric service operation arising from the Facility. Any such
protective or regulating devices that may be required on Company's facilities in
connection with the operation of the Facility shall be installed by Company at
Seller's expense.
3.8.1 Requirements for Protection. Seller shall provide, install, own, and
maintain relays, circuit breakers, and all other devices necessary to
promptly remove any fault contribution of the Facility to any short circuit
occurring on the Company Transmission System not otherwise isolated by
Company equipment. Such protective equipment shall include, without
limitation, a disconnecting device or switch with load interrupting
capability to be located between the Facility and the Company Transmission
System at an accessible, protected, and satisfactory site selected upon
mutual agreement of the Parties. Seller shall be responsible for protection
of the Facility and Seller's other equipment from such conditions as
negative sequence currents, over- or under-frequency, sudden load
rejection, over- or under-voltage, and generator loss-of-field. Seller
shall be solely responsible for provisions to disconnect the Facility and
Seller's other equipment when any of the above-described disturbances occur
on the Company Transmission System.
Page 6
3.8.2 Power Quality. Seller's Facilities shall be required to not cause
excessive voltage excursions nor cause the voltage to drop below or rise
above the range normally maintained by Company. Seller's Facilities shall
be required to not cause excessive voltage flicker nor introduce excessive
distortion to the sinusoidal voltage or current waves as defined by ANSI
Standard C84.1-1989, IEEE- 519, or any applicable superseding electric
industry standard.
3.8.3 Inspection. Company shall have the right, but shall have no
obligation or responsibility to: i) observe Seller's tests and/or
inspection of any of Seller's protective equipment; ii) review the settings
of Seller's protective equipment; and iii) review Seller's maintenance
records relative to the Facility and/or Seller's protective equipment. The
foregoing rights may be exercised by Company from time to time as deemed
necessary by Company upon reasonable notice to Seller. However, the
exercise or non-exercise by Company of any of the foregoing rights of
observation, review or inspection shall be construed neither as an
endorsement or confirmation of any aspect, feature, element, or condition
of the Facility or Seller's protective equipment or the operation thereof,
nor as a warranty as to the fitness, safety, desirability, or reliability
of same.
3.8.4 Underfrequency Relaying. Seller's generator underfrequency relaying
and/or underfrequency tripping procedures shall be coordinated with and
approved by Company. Facility generator underfrequency tripping shall be
coordinated with the regional underfrequency load shedding program to
insure that the Facility remains connected to the Company Transmission
System during frequency declines.
3.9 Continuity of Service. Notwithstanding any other provision of this
Agreement, Company shall not be obligated to accept, and Company may require
Seller to curtail, interrupt or reduce, deliveries of energy if such delivery of
energy impairs Company's ability to construct, install, repair, replace or
remove any of its equipment or any part of its system or if Company determines
that curtailment, interruption or reduction is necessary because of Emergencies,
forced outages, operating conditions on its system, or any reason otherwise
permitted by applicable rules or regulations promulgated by a regulatory agency
having jurisdiction over such matters. Except in case of Emergency, Company
shall give Seller reasonable prior notice of any curtailment, interruption or
reduction, the reason for its occurrence, and its probable duration. Seller
reserves all rights under the Federal Power Act and applicable other federal and
state laws and regulations to commence a complaint proceeding or other action
with respect to any action taken by the Company pursuant to this Section 3.9.
3.10 Governor Speed and Frequency Control. Seller shall maintain a speed
governor system on all generators. The speed governor system must respond to
system frequency changes to help maintain the stability of the power system. At
no time shall a speed governor be blocked with out first obtaining permission
from Company. The speed governor system shall have a droop characteristic
settable between three and seven percent and typically set to five (5%) percent.
Page 7
4.0 MAINTENANCE
4.1 Coordination. The Parties agree to coordinate the planning and scheduling of
maintenance of the Seller's Facility and the Company's Interconnection
Facilities. Each Party shall conduct maintenance activities as planned and
scheduled in accordance with this section. Seller shall provide Company with an
on-going five (5) year maintenance outage schedule of three (3) or more days
duration by January 1 of each year. Throughout the year, Seller will provide
reasonable advance notice to Company of any modifications to the maintenance
schedule.
4.2 Unplanned Outage. In the event of an unplanned outage of (i) the Company
Interconnection Facilities that adversely affects the Seller or the Facility or
(ii) a component of the Facility that adversely affects reliability of the
Company Transmission System, the Party causing the adverse affect in (i) or (ii)
above, as applicable, will use commercially reasonable efforts to promptly
restore the necessary equipment to service in accordance with Good Utility
Practice.
4.3 Planned Outage. In the event of a planned outage of (i) the Company
Interconnection Facilities that adversely affects Seller or (ii) a component of
the Facility that adversely affects reliability of the Company Transmission
System, the Party causing the adverse affect in (i) or (ii) above, as
applicable, will use commercially reasonable efforts to restore that equipment
to service in accordance with Good Utility Practice and in accordance with the
schedule for work that necessitated the planned outage.
4.4 Outage Authority and Coordination. In accordance with Good Utility Practice,
Company may remove its Interconnection Facilities from service that may impact
Seller's Facilities as necessary to perform maintenance or testing or to install
or replace equipment. Absent the existence or imminence of an Emergency, Company
scheduling a removal of equipment from service will use best efforts to schedule
such removal on a date mutually acceptable to both Parties, in accordance with
Good Utility Practice.
5.0 INSPECTION AND ACCESS TO FACILITIES
5.1 The Parties grant to each other, from the Effective Date of this Agreement,
the rights necessary to perform the functions contemplated by this Agreement,
including but not limited to the right, upon reasonable notice, to inspect and
monitor the construction and operations of the Facility and the Interconnection
Facilities, along with adequate and continuing access rights. Such access shall
be provided in a manner so as not to unreasonably interfere with the ongoing
business operations, rights and obligations of either Party. Each Party shall
execute or cause to be executed such other licenses, grants, deeds or documents
as may be required to enable the other Party to record such rights-of-way and
easements.
5.2 Access to Premises: The duly authorized agents of Company shall have the
right of ingress and egress to the premises of Seller at all reasonable hours
Page 8
for the purpose of reading meters, inspecting Company's wiring and apparatus,
changing, exchanging, or repairing Company's property on the premises of Seller,
or removing such property at the time of or at any time after suspension of
purchases or termination of this Agreement.
5.3 Protection: Seller shall protect Company's wiring and apparatus on Seller's
premises and shall permit no one but Company's agents to handle same except as
provided in 3.0. In the event of any loss of or damage to such property of
Company caused by or arising out of carelessness, neglect, or misuse by Seller,
Seller's employees or agents, the cost of making good such loss or repairing
such damage shall be paid by Seller. In cases where Company's service facilities
on Seller's premises require abnormal maintenance due to Seller's operation,
Seller shall reimburse Company for such abnormal maintenance.
6.0 EMERGENCY
6.1 Obligations. Each Party agrees to comply with NERC, SERC, VACAR or RTO
Emergency procedures and Company and Seller Emergency procedures, as applicable,
with respect to an Emergency.
6.2 Notice. Company shall provide Seller with notification that is prompt under
the circumstances of an Emergency that may reasonably be expected to affect
Seller's operation of the Facility, to the extent Company is aware of the
Emergency. Seller shall provide Company with notification that is prompt under
the circumstances of an Emergency, which may reasonably be expected to affect
Company's Transmission System, to the extent Seller is aware of the Emergency.
To the extent the Party becoming aware of an Emergency is aware of the facts of
the Emergency, such notification shall describe the Emergency, the extent of the
damage or deficiency, its anticipated duration, and the corrective action taken
and/or to be taken, and shall be followed as soon as practicable with written
notice.
6.3 Immediate Action. In the event of an Emergency, the Party becoming aware of
the Emergency may, in accordance with Good Utility Practice and using its
reasonable judgment, take such action as is reasonable and necessary to prevent,
avoid, or mitigate injury, danger, and loss. In the event Seller has identified
an Emergency involving Company's Transmission System, Seller shall obtain the
consent of Company personnel prior to manually performing any switching
operations unless, in Seller's reasonable judgment, immediate action is
required.
6.4 Company Authority. Company may, consistent with Good Utility Practice, take
whatever actions or inactions with regard to the Company Transmission System it
deems necessary during an Emergency in order to: i) preserve public health and
safety; ii) preserve the reliability of the Company Transmission System; iii)
limit or prevent damage; and iv) expedite restoration of service. Company shall
use reasonable efforts to minimize the effect of such actions or inactions on
the Facility, and shall use its best efforts to cancel the Emergency as soon as
practicable.
Page 9
6.4.1 Facility may be called upon by Company during a potential or actual
Emergency to mitigate such Emergency by, but not limited to, requesting the
Facility to start up, shut down, increase or decrease the output of the
Facility.
6.4.2 Company shall reimburse Seller for any reasonable costs incurred by
Seller in response to a request by Company to start up or increase the
output of the Facility to mitigate an Emergency.
6.5 Seller Authority. Seller may, consistent with Good Utility Practice, take
whatever actions or inactions with regard to the Facility it deems necessary
during an Emergency in order to: i) preserve public health and safety; ii)
preserve the reliability of the Facility; iii) limit or prevent damage; and iv)
expedite restoration of service. Seller shall use reasonable efforts to minimize
the effect of such actions or inactions on the Company Transmission System.
6.6 Audit Rights. Each Party shall keep and maintain records of actions taken
during an Emergency that may reasonably be expected to impact the other Party's
facilities and make such records available for third party independent audit
upon the request and expense of the party affected by such action. Any such
request for an audit will be no later than twenty-four (24) months following the
action taken.
7.0 SAFETY
7.1 General. Company and Seller agree that all work performed by either Party
that may reasonably be expected to affect the other Party shall be performed in
accordance with Good Utility Practice and all applicable laws, regulations, and
other requirements pertaining to the safety of persons or property. A Party
performing work within the boundaries of the other Party's facilities must abide
by the safety rules applicable to the site.
7.2 Environmental Releases. Each Party shall notify the other Party, first
orally and then in writing, of the release of any Hazardous Substances, any
asbestos or lead abatement activities, or any type of remediation activities,
each of which may reasonably be expected to affect the other Party, as soon as
possible but not later than twenty-four (24) hours after the Party becomes aware
of the occurrence, and shall promptly furnish to the other Party copies of any
reports filed with any governmental agencies addressing such events.
8.0 MODIFICATIONS
8.1 Seller Construction Responsibility. Seller shall be responsible to design,
engineer, construct and own the Facility. Seller may make Modifications during
the term of this Agreement subject to the requirements of the Company's
interconnection procedures.
8.2 Need to Maintain the Integrity of the Company Transmission System. The
Facility and any subsequent Modifications shall be designed, constructed and
operated in accordance with this Agreement and Good Utility Practice, so as to
maintain the integrity of the transmission and communications capabilities of
the Company Transmission System. Company will have the right to review all
engineering plans and specifications of the Facility Modifications in order to
assure compliance with this Section 8.2.
Page 10
8.3 Company Right to Review and Inspect Facility Construction. Company may
inspect the Facility or any subsequent Modification prior to Substation
Energization and at its interconnection to the Company Transmission System
pursuant to Section 5 of this Agreement. If, after an inspection, Company
determines that the Facility or any subsequent Modification does comply with
Section 3.2, Company shall notify Seller in writing within five (5) working
days.
8.4 Facility Non-Compliance with Section 8.2. If, after an inspection pursuant
to Section 8.3, Company determines that the Facility or any subsequent
Modification does not comply with Section 8.2, Company shall notify Seller in
writing within five (5) working days of the reasons why the Facility or any
subsequent Modification is in non-compliance with Section 8.2. Seller shall take
appropriate corrective action and obtain Company's written acknowledgement that
the Facility or Modification is in compliance with Section 8.2. Such
acknowledgement by Company will not be unreasonably delayed, withheld or
conditioned.
8.4.1 In the event that the Facility is found by Company to be in
non-compliance with Section 8.2 during a pre-energization inspection,
Company may deny the interconnection of the Facility or any subsequent
Modification to the Company Transmission System until such non-compliance
is corrected by Seller and Seller obtains written acknowledgement of
compliance with Section 8.2 from Company. In the event that the Facility is
found by Company to be in non-compliance with Section 8.2 during
energization testing, Company may disconnect the Facility or any subsequent
Modification from the Company Transmission System until such non-compliance
is corrected by Seller and Seller obtains written acknowledgement of
compliance with Section 8.2 from Company.
8.5 Company Construction Responsibility. Company shall be responsible to design,
engineer, construct and own the facilities of the Company Transmission System
including all Interconnection Facilities on Company's side of the Point of
Interconnection.
8.6 Notice to Company for Modifications. Seller shall provide Company with at
least ninety (90) days' advance notice of any Modification to the Facility that
might reasonably be expected to have an impact on system frequency, system
voltage, system loading, system stability, system power quality and the safe
operation of the Company Transmission System. The notice shall be written and
include all design and engineering specifications of the proposed Modification.
Within thirty (30) days after receipt of such notice, Company shall by written
response approve or reject the proposed specifications; provided, however, that
Company may only reject the proposed specifications if they are inconsistent
with Good Utility Practice or are otherwise contrary to standards set forth in
this Agreement.
Page 11
8.7 Payment to Company for Subsequent Modifications. Seller shall pay Company
for all reasonable costs, including any tax cost, associated with Modifications
to the Company Transmission System which result from Modifications to Seller's
Facilities.
8.8 Modifications to Interconnection Facilities. Company shall make such
Modifications to its Interconnection Facilities as required by law, regulation,
rule or Good Utility Practice to enable Company to provide Interconnection
Service in compliance with this Agreement.
8.9 Seller Modifications Resulting from Company Modifications. If Company is
required by law, regulation, rule or Good Utility Practice to make Modifications
to its facilities and the Modifications require Seller to make Modifications to
its Facilities, Seller shall be responsible for the costs associated with the
Modification to its Facilities, unless such Modifications provide benefits to
Company or Company's other customers, in which event Seller can pursue any
remedies it may have at the North Carolina Utilities Commission or any other
forum.
8.10 Drawings. Subject to the requirements of Article 17, upon completion of any
construction or Modification to the Facilities that takes place after the
effective date of the Agreement, Seller shall deliver "as Built" drawings to
Company.
8.11 Payments for Interconnection Facilities. Seller shall pay a Monthly
Facility Charge as stated in Appendix B for the existing interconnection
facilities, communication equipment, and meter equipment necessary to provide
interconnection.
8.12 Changes in Operating Voltage. Company may change the operating voltage at
the Point of Interconnection. Company shall provide a minimum of two (2) years
written notice to Seller prior to any change in operating voltage. Within one
year of receipt of such notice, Seller shall notify Company that, by no later
than the notice effective date of the change in operating voltage, it will
either: (a) terminate the Point of Interconnection; or (b) provide any and all
equipment or facilities as may be necessary or required on Seller's side of the
Point of Interconnection in order to be able to accept the new voltage.
9.0 METERING
9.1 General. Company will be responsible for the installation, operation,
maintenance, repair and replacement of all Metering Equipment necessary to meet
Company's metering obligations under this Agreement. All Metering Equipment
shall conform to Good Utility Practice and the standards and practices of
Company in effect during the term of this Agreement. Subject to Section 9.3, the
meter readings provided by the Company Metering Equipment shall be used as the
official measurement of capacity and energy delivered from the Facility to the
Point of Interconnection. In addition to the Metering Equipment provided by
Company, Seller may, at its own expense, provide backup meters for its own use
provided it does not interfere with the performance of Company meters.
Page 12
9.2 Meter location. Unless otherwise agreed, electric capacity and energy
received by Company from Seller will be measured by meters installed and
maintained by Company at the Point(s) of Interconnection. When measurement is
made at any location other than the Point(s) of Interconnection, suitable
adjustment for losses between the point of measurement and the Point(s) of
Interconnection will be agreed upon in writing between the Parties hereto and
will be applied to all measurements so made. Metered receipts used in energy
accounting and applicable billing hereunder will in all cases include adjustment
for such losses. Company meters will be positioned at a location to properly
account for net Facility output.
9.3 Testing of Metering Equipment. Company shall inspect and test all
Company-owned Metering Equipment upon installation and at least once every 12
months thereafter. Company shall give reasonable notice of the time when any
scheduled inspection or test shall take place, and Seller may have
representatives present at the test or inspection. Upon prior reasonable written
notice to Company, Seller may request more frequent tests or inspections. If
such tests or inspections determine that the meter is defective or inaccurate,
Company shall pay for the test; otherwise, Seller shall pay for such tests and
inspections. If Metering Equipment is found to be inaccurate or defective, it
shall be adjusted, repaired or replaced in order to provide accurate metering.
If Metering Equipment fails to register, or if the measurement made by Metering
Equipment during a test varies by more than plus or minus two percent (2%) from
normal, adjustments shall be made correcting all measurements made by the
inaccurate meter for: a) the actual period during which inaccurate measurements
were made, if the period can be determined, or if not, b) the period immediately
preceding the test of the Metering Equipment equal to one-half the time from the
date of the last previous test of the Metering Equipment; provided that the
period covered by the correction shall not exceed six months.
9.4 Metering Data. Unless the Parties have not made other arrangements, if
hourly and/or daily energy readings are available and if such data are requested
by Company, Seller shall report same to Company's representatives as designated
pursuant to Article 10, by telephone or electronically or as the Parties
otherwise agree, on a schedule to be agreed upon.
9.4.1 Metering quantities, in analog and/or digital form, shall be provided
to Seller upon request and at Seller's expense.
9.4.2 At Seller's expense, Seller's metered data shall be telemetered to a
location designated by Company.
9.5 Communications. At Seller's expense, Seller shall maintain satisfactory
operating communications with Company's system dispatcher or representative, as
Page 13
designated by Company. Seller will provide a dedicated automatic ring-down
circuit at its Facility control room for direct communication with Company's
system dispatcher.
9.5.1 Seller will also provide the necessary data circuit (or circuits)
operating at a baud rate specified by Company. The data circuit(s) shall
extend from Seller's Facility to a location(s) specified by Company. Any
required maintenance of such communications equipment shall be performed at
Seller's expense, but may be performed by Seller or by Company. Operational
communications shall be activated and maintained under, but not be limited
to, the following events: system paralleling or separation, scheduled and
unscheduled shutdowns, equipment clearances, and hourly and daily load
data.
9.5.2 A Remote Terminal Unit ("RTU") or equivalent data collection and
transfer equipment acceptable to both Parties shall be installed by Company
at Seller's expense, at a location determined by Company, to gather
accumulated and instantaneous data to be telemetered to a location(s)
designated by Company through use of a dedicated point-to-point data
circuit(s) as indicated in Section 9.4.2. Data communicated will include
but is not limited to reactive output, voltage, generator output, and
generator breaker status. The communication protocol for this data
circuit(s) will be specified by Company. Instantaneous bi-directional
analog real power and reactive power flow information must be telemetered
directly to the location(s) specified by Company.
9.5.3 At Seller's expense, Seller shall provide a public telephone line at
a location specified by Company to connect to Company metering equipment
for meter maintenance and data collection.
9.6 For any period during which there is a loss of telemetering capability
between Company and Seller which results in the loss of generation information,
Seller shall provide reasonable estimates to the Company of projected generation
schedule information which has been lost. Such estimates shall be updated at
least hourly and more frequently if possible. Such estimates of hourly
scheduling will be used for record purposes unless actual data is retrieved from
the meter records.
10.0 NOTICES
10.1 Any notice, demand or request required or permitted to be given by either
Party to the other and any instrument required or permitted to be tendered or
delivered by either Party to the other may be so given, tendered or delivered,
as the case may be, by depositing the same in any United States Post Office with
postage prepaid, for transmission by certified or registered mail, addressed to
the Party, or personally delivered to the Party, at the address set out below:
Page 14
To Company:
CP&L
0000 Xxxxxxxxxxxx Xxxxxx
Xxxxxxx, XX 00000
Attention: Director Power System Operations Carolinas
To Seller:
Green Power Kenansville LLC
0000 Xxxxxxxx Xxxx
Xxxxxxxxxx, XX 00000
Attn: Xxxxx Xxxxxxxxx
11.0 FORCE MAJEURE
11.1 Damages Resulting from Factors Outside a Party's Control. Neither Party
shall be considered in default under this Agreement or responsible to the other
Party in tort, strict liability, contract or other legal theory for damages of
any description for any interruption or failure of service or deficiency in the
quality or quantity of service or any other failure to perform any of its
obligations hereunder to the extent such failure occurs without fault or
negligence on the part of that Party and is caused by factors beyond that
Party's reasonable control, which by the exercise of reasonable diligence that
Party is unable to prevent, avoid, mitigate or overcome, including without
limitation storm, flood, hurricane, lightning, earthquake, explosion, equipment
failure, civil disturbance, labor dispute, act of God or the public enemy,
action or inaction of a court or Governmental Authority, unscheduled withdrawal
of either Parties' facilities from operation for maintenance or repair, or any
other cause of similar nature beyond the reasonable control of that Party (any
such event, "Force Majeure"). Economic hardship of either Party shall not
constitute Force Majeure under this Agreement, nor shall anything contained in
this Article 11 or elsewhere in this Agreement excuse Seller or Company from
strict compliance with the obligation of the Parties to comply with the terms of
this Agreement relating to timely payments.
11.2 Requirement to Operate with Good Utility Practice. Each Party shall have
the obligation to operate in accordance with Good Utility Practice at all times
and to use due diligence to overcome and remove any cause of failure to perform.
11.3 Notification and Efforts to Mitigate an Event. If a Party relies on the
occurrence of an event or condition described above as a basis for being excused
from performance of its obligation under this Agreement, then the Party relying
on the event or condition shall: (a) provide prompt written notice of such Force
Majeure event to the other Party, giving an estimate of its expected duration
and the probable impact on the performance of its obligations hereunder; (b)
exercise all reasonable efforts to continue to perform its obligations under
this Agreement; (c) expeditiously take action to correct or cure the event or
Page 15
condition excusing performance; provided, however, that settlement of strikes or
other labor disputes will be completely within the sole discretion of the Party
affected by such strike or labor dispute; (d) exercise all reasonable efforts to
mitigate or limit damages to the other Party; and (e) provide prompt notice to
the other Party of the cessation of the event or condition giving rise to its
excuse from performance. All performance obligations hereunder shall be extended
by a period equal to the term of the resultant delay.
11.4 Costs Incurred to Mitigate an Event. If a Party responding to a Force
Majeure event has the ability to obtain, for additional expenditures, expedited
material deliveries or labor production which would allow a response to the
event in a manner that is above and beyond Good Utility Practice, such a
response could shorten the duration of the event, and a shorter duration of the
event could lessen the economic hardship of the other Party, the Party
responding to the event may, at its discretion, present the other Party with the
option of funding the expenditures for expediting material deliveries or labor
production in an effort to reduce the duration of the event and economic
hardship. Each such opportunity will be negotiated on a case-by-case basis by
the Parties.
12.0 INSURANCE
12.1 Seller shall maintain, at their own cost and expense or self insurance,
insurance coverage in the amounts set forth as follows. Seller may self insure
provided that Company is satisfied that the Seller has sufficient financial
resources to maintain self insurance for the coverage and amounts set forth
below. Seller shall, annually, provide Company with its certified financial
reports when self-insuring.
12.2 Company shall maintain insurance or self insurance in accordance with the
requirements set forth below.
12.3 Company's Insurance. During the term of this Agreement, Company shall
maintain the following coverage:
12.3.1 Workers' Compensation and any other statutory insurance required by
Law with respect to work-related injuries or disease of employees of
Company applicable to Company's employees in such form(s) and
amount(s) as required by all applicable Laws. Such policy(ies) of
insurance shall be endorsed to provide a waiver of subrogation in
favor of Owner.
12.3.2 Commercial General Liability ("CGL") insurance, in broad form
including coverage for liability assumed under contract, providing
coverage for bodily injury and property damage with a combined single
limit of not less than Ten Million Dollars ($10,000,000) cumulative
total of underlying and excess coverages.
Page 16
12.3.3 The foregoing insurance policies shall provide that the policy shall
not be canceled without thirty (30) days' advance written notice to Seller
of such cancellation or change.
12.3.4 Prior to commencement of any work under this Agreement, and not less
than annually thereafter, if requested in writing, during the term of this
Agreement, Company shall deliver to Seller certificate(s) of insurance
showing that the foregoing insurance is in full force and effect.
12.3.5 Auto Liability with combined single limit of $1 million per
occurrence shall be maintained with financially sound and reputable
insurance companies covering bodily injury and property damage for all
owned , non-owned, leased and hired vehicles. Each such policy shall also
provide that if such insurance is canceled or lapses for any reason,
including nonpayment of premium, or if any material change is made that
adversely affects coverage, insurers will provide written notice to the
Company 30 days prior to such cancellation, lapse or change.
12.4 Seller's Insurance. During the term of this Agreement, Seller shall
maintain the following insurance coverage:
12.4.1 Workers' Compensation and any other statutory insurance required by
law with respect to work-related injuries or disease of employees of Seller
applicable to Seller's employees in such form(s) and amount(s) as required
by all applicable laws. Such policy(ies) of insurance shall be endorsed to
provide a waiver of subrogation in favor of Company and its Affiliates.
12.4.2 Commercial General Liability ("CGL") insurance, in broad form
including coverage for liability assumed under contract, providing coverage
for bodily injury and property damage with a combined single limit of not
less than Ten Million Dollars ($10,000,000) cumulative total of underlying
and excess coverages or such lesser combined single limits as may from time
to time be obtainable under conditions then prevailing in the insurance
market for independent power generation facilities.
12.4.3 The foregoing insurance policies shall provide that the policy shall
not be canceled without thirty (30) days' advance written notice to Company
of such cancellation or change.
12.4.4 Prior to commencement of any work under this Agreement, and not less
than annually thereafter, if requested in writing, during the term of this
Agreement, Seller shall deliver to Company a certificate(s) of insurance
showing that the foregoing insurance is in full force and effect.
Page 17
12.4.5 Auto Liability with combined single limit of $1 million per
occurrence shall be maintained with financially sound and reputable
insurance companies covering bodily injury and property damage for all
owned , non-owned, leased and hired vehicles. Each such policy shall also
provide that if such insurance is canceled or lapses for any reason,
including nonpayment of premium, or if any material change is made that
adversely affects coverage, insurers will provide written notice to the
Company 30 days prior to such cancellation, lapse or change.
13.0 INDEMNITY AND LIABILITY
13.1 Seller Indemnity. Seller agrees to fully indemnify and hold Company, its
shareholders, directors, partners, stakeholders, officers, managers, employees,
agents, representatives, servants, its Affiliates, their respective
shareholders, directors, partners, stakeholders, officers, managers, employees,
agents, representatives, servants, and/or their assigns (collectively "Company
Indemnified Persons"), harmless from and against any and all claims, demands,
liability, losses, damage, costs or expenses (including attorneys' fees and
other costs of defense), of any nature or kind whatsoever, including, but not
limited to, claims, demands and/or liability for personal injury to (including
death of) any person whomever (including payments and awards made to Seller's
employees or other under any workers' compensation law or under any plan for
employees' disability and death benefits) and for damage to any property
whatsoever (including Seller's Facilities and the Company Transmission System)
arising out of or otherwise resulting from the use, ownership, maintenance, or
operation of the Facility or regardless of whether such claims, demands or
liability are alleged to have been caused by negligence or to have arisen out of
Company's status as the owner or operator of facilities involved; provided,
however, that the provisions of this Section 13.1. shall not apply if any such
claim is caused by the negligence or intentional wrongdoing of Company, its
agents or any other Company Indemnified Person.
13.2 Company Indemnity. Company agrees to fully indemnify and hold Seller, its
shareholders, directors, partners, stakeholders, officers, managers, employees,
agents, representatives, servants, its Affiliates, their respective
shareholders, directors, partners, stakeholders, officers, managers, employees,
agents, representatives, servants, and/or their assigns (collectively "Seller
Indemnified Persons"), harmless from and against any and all claims, demands,
liability, losses, damage, costs or expenses (including attorneys' fees and
other costs of defense), of any nature or kind whatsoever, including, but not
limited to, claims, demands and/or liability for personal injury to (including
death of) any person whomever (including payments and awards made to Company's
employees or other under any workers' compensation law or under any plan for
employees' disability and death benefits) and for damage to any property
Page 18
whatsoever (including Facilities and the Company Transmission System) arising
out of or otherwise resulting from the use, ownership, maintenance, or operation
of Company's Transmission System, regardless of whether such claims, demands or
liability are alleged to have been caused by negligence or to have arisen out of
Seller's status as the owner or operator of facilities involved; provided,
however, that the provisions of this Section 13.2 shall not apply if any such
claim is caused by the negligence or intentional wrongdoing of Seller, its
agents or any other Seller Indemnified Person.
13.3 Limitation on Liability. Neither Party shall be liable in statute,
contract, in tort (including negligence), strict liability, or otherwise to the
other Party, its agents, representatives, its affiliated and associated
companies, and/or its assigns, for any incidental or consequential loss or
damage whatsoever, including, but not limited to, loss of profits or revenue on
work not performed, for loss of use of or under-utilization of the other Party's
facilities, or loss of use of revenues or loss of anticipated profits, resulting
from either Party's performance or non-performance of an obligation imposed on
it by this Agreement.
14.0 ASSIGNMENT
14.1 Neither Party shall assign, pledge, delegate or otherwise transfer this
Operation and Interconnection Agreement or any rights, duties or obligations
hereunder without first obtaining the other Party's written consent, which
consent shall not be unreasonably withheld, except that a Party shall be
permitted to assign, pledge or otherwise transfer this Facility Interconnection
and Operating Agreement or its rights hereunder, or to delegate its duties and
obligations hereunder, in whole or in part, by operation of law or otherwise,
without the other Party's consent, to: (i) any entity that assumes control over,
in the case of Company, all or part of the Company Transmission System to which
the Facility is connected or in the case of Seller, all or part of the Facility,
(ii) any successor to or transferee of the direct or indirect ownership or
operation of all or part of, in the case of Company, the Company Transmission
System to which the Facility is connected or in the case of Seller, the
Facilities, or (iii) any Affiliate. In addition and notwithstanding the
foregoing, either Party may assign this Agreement to the persons, entities or
institutions providing financing or refinancing for the development, design,
construction or operation of its assets or facilities (a "Lender") , and if
Seller provides notice thereof to Company, shall provide notice and reasonable
opportunity for such Lender(s) to cure any Breach of this Agreement, pursuant to
the terms of Section 15.4 below.
14.2 Upon the assumption by any permitted assignee, pledge or other transferee
described above of a Party's rights, duties and obligations hereunder, that
Party shall be released and discharged therefrom to the extent provided in the
assignment, pledge or other transfer agreement. Except as specifically provided
for in this Article 14, any assignment, pledge or transfer of this Agreement or
any rights, duties or interests hereunder by either Party without the express
written consent of the other Party shall be void and without force or effect.
Page 19
15.0 BREACH, CURE AND DEFAULT
15.1 General. A breach of this Agreement ("Breach") shall occur upon the failure
by a Party to perform or observe any material term or condition of this
Agreement. A default of this Agreement ("Default") shall occur upon the failure
of a Party in Breach of this Agreement to cure such Breach in accordance with
the provisions of Section 15.4.
15.2 Events of Breach. In addition to the circumstances that give rise to a
Breach that are set forth in Section 15.1 above, a Breach of this Agreement
shall also occur under the following circumstances:
(a) A Party shall fails to pay any amount when due;
(b) A Party shall: (1) become insolvent; (2) file a voluntary petition in
bankruptcy under any provision of any federal or state bankruptcy law
or shall consent to the filing of any bankruptcy or reorganization
petition against it under any similar law; (3) make a general
assignment for the benefit of its creditors; or (4) consent to the
appointment of a receiver, trustee or liquidator;
(c) A Party attempts to assign this Agreement in a manner inconsistent
with the terms of Article 14; or
(d) A Party fails to provide the other Party or its agents access rights
in accordance with Article 5.
15.3 Continued Operation. If a Breach or Default occurs, the Parties shall
nevertheless continue to be obligated operate and maintain, as applicable, such
DC power systems, protection and Metering Equipment, telemetering equipment,
SCADA equipment, transformers, secondary systems, communications equipment,
building facilities, software, documentation, structural components, and other
facilities and appurtenances that are reasonably necessary for Company to
operate and maintain the Company Transmission System, or for Seller to operate
and maintain the Facility, in a safe and reliable manner.
15.4 Cure and Default. Upon the occurrence of a Breach, the Party not in Breach
(hereinafter the "Non-Breaching Party") shall, upon becoming aware of the
Breach, give written notice to the Party in Breach (the "Breaching Party") and
(when applicable) the Breaching Party's Lender pursuant to Article 14. Such
notice shall set forth, in reasonable detail, the nature of the Breach, and
where known and applicable, the steps necessary to cure such Breach. Upon
receiving written notice of the Breach hereunder, the Breaching Party shall have
thirty (30) days to cure such Breach. If the Breach is such that it cannot be
cured within thirty (30) days, the Breaching Party must commence in good faith
all steps as are reasonable and appropriate to cure the Breach within such
thirty (30) day time period and thereafter diligently pursue such action to
completion. In the event the Breaching Party fails to cure the Breach, or to
commence reasonable and appropriate steps to cure the Breach, within thirty (30)
days of becoming aware of the Breach, the Breaching Party will be in Default of
this Agreement.
Page 20
15.5 Right to Compel Performance. Notwithstanding the foregoing, upon the
occurrence of an event of Default, the non-Defaulting Party shall be entitled
to: (1) commence an action to require the Defaulting Party to remedy such
Default and specifically perform its duties and obligations hereunder in
accordance with the terms and conditions hereof, and (2) exercise such other
rights and remedies as it may have in equity or at law.
16.0 SUBCONTRACTOR
16.1 General. Nothing in this Agreement shall prevent a Party from utilizing the
services of such subcontractors as is deems appropriate to perform its
obligations under this Agreement; provided, however, that each Party shall
require its subcontractors to comply with all applicable terms and conditions of
this Agreement in providing such services and each Party shall remain primarily
liable to the other Party for the performance of such subcontractor.
16.2 Responsibility of Principal. The creation of any subcontract relationship
shall not relieve the hiring Party of any of its obligations under this
Agreement. Each Party shall be fully responsible to the other Party for the acts
or omissions of any subcontractor it hires as if no subcontract had been made.
Any applicable obligation imposed by this Agreement upon a Party shall be
equally binding upon, and shall be construed as having application to, any
subcontractor of such Party.
16.3 No Third Party Beneficiary. Except as may be specifically set forth to the
contrary herein, no subcontractor or any other party is (other than a Lender as
defined under Section 14.1) intended to be, nor will it be deemed to be, a
third-party beneficiary of this Agreement.
16.4 No Limitation by Insurance. The obligations under this Article 16 will not
be limited in any way by any limitation of subcontractor's insurance.
17.0 CONFIDENTIALITY
17.1 Certain information provided by each Party (the "Disclosing Party") to the
other Party (the "Receiving Party") pursuant to the provisions of this Agreement
may be designated by the Disclosing Party as confidential and/or proprietary
("Confidential Information"). The Receiving Party shall use such Confidential
Information solely for the purpose for which it was intended and for no other
purpose. The Receiving Party may disclose Confidential Information only when
required by applicable law, regulation; provided that, prior to doing so, the
Receiving Party shall provide the Disclosing Party with as much advance notice
as is reasonably practicable under the circumstances.
18.0 AUDIT RIGHTS
18.1 Subject to the requirements of confidentiality under Article 17 of this
Agreement, either Party shall have the right, during normal business hours, and
upon prior reasonable notice to the other Party, to audit each other's accounts
and records pertaining to either Party's performance and/or satisfaction of
Page 21
obligations arising under this Agreement. Said audit shall be performed at the
offices where such accounts and records are maintained and shall be limited to
those portions of such accounts and records that relate to obligations under
this Agreement.
19.0 COORDINATION
19.1 Appointment of Representatives. Company and Seller shall each appoint one
representative to serve on an operating committee ("Operating Committee") to act
for each respective Party in all matters pertaining to or relating to this
Agreement. The members of the Operating Committee shall communicate with each
other on a regular basis. The Operating Committee shall meet in person as soon
as practicable subsequent to the request of either Operating Committee member.
19.2 Designation of Substitutes. Each representative on the Operating Committee
may at any time designate a substitute to act for him or her with respect to any
matter or matters specified in such notice. All decisions made or directions
given by the Operating Committee shall be unanimous.
19.3 Responsibilities. The Operating Committee shall be responsible for the
establishment, from time to time, of the operating practices and procedures for
the interconnected operation of the Facility. These practices and procedures
shall be consistent with the provisions of this Agreement.
19.4 Data Reporting: Seller shall provide Company with all information required
to operate the transmission grid including but not limited to the requirements
of NERC, SERC and/or VACAR. Seller shall comply with the requirements of the
NERC Compliance Program which includes but is not limited to provisions for data
reporting to the transmission provider.
19.5 Notice. Each Party shall notify the other Party in writing of the personnel
that it appoints to the Operating Committee.
Page 22
IN WITNESS WHEREOF, the Parties hereto have caused this Agreement to be duly
executed by their duly authorized officers on the day and year indicated below.
SELLER
By: _____________________________
Name: ___________________________
Title: __________________________
Date: ___________________________
CP&L
By: ____________________________
Name: ___________________________
Title: __________________________
Date: ___________________________
Page 23
APPENDIX A
INTERCONNECTION OPERATING REQUIREMENTS
This Appendix A is a part of the Interconnection and Operation Agreement
between Seller and Company.
I. PURPOSE:
These requirements will contribute to a safer working environment for those
persons authorized by Seller and Company to operate and maintain their
respective equipment; also to minimize customer inconvenience by promoting
improved coordination between Seller and Company.
II. APPLICABILITY:
These requirements apply to all operations that can affect the Company
Transmission System via the 115 kV interconnection with Seller located in
Kornegay, North Carolina identified in Attachment Exhibit I.
III. DESCRIPTION OF:
Attached Exhibit I to this document contains a written description of the
Company and Seller facilities these requirements are directed to. This
description contains the following information:
A. Location of the Company-owned station and Seller-owned substation.
B. Identification of equipment connected to the Company Transmission
System.
C. Description of the opening point that will separate Seller's equipment
from the Company's Switching Station.
IV. COORDINATION CONTACTS:
Attached Exhibit II to this document contains the following coordination
contacts information:
A. A listing of the appropriate Company operations contacts and their
telephone numbers.
B. Information received from Seller designating the names and telephone
numbers of individuals who are authorized to operate Seller's
equipment and coordinate operations with the Company power system
operator.
V. REVISIONS:
This document is subject to be revised, amended, or otherwise changed.
Exhibits I and II may be revised from time to time to keep telephone
numbers, contacts, and delivery locations current. Any other such revisal,
amendment, or change shall be in writing and signed by the parties. Seller
will notify Company in writing, at the following address, of any changes
that affect information in this Appendix A or Exhibits I and/or II. Company
will revise and redistribute this Appendix A with its exhibits as
necessary.
Page 24
To Company:
CP&L
0000 Xxxxxxxxxxxx Xxxxxx
Xxxxxxx, XX 00000
Attention: Director Power System Operations Carolinas
VI. GENERAL INFORMATION:
A. Main Equipment
1. Seller maintains and operates all facilities on the Seller's side
of the high-voltage bushing connections of the Seller-owned three
phase 115/13.2 kV transformer bank.
2. Seller maintains and operates all facilities on the Seller's side
of the high-voltage bushing connection of the Seller-owned three
phase115/13.2 kV transformer bank.
B. Relay Protection
1. Seller has the following relay protection schemes:
a. Seller has overcurrent and differential relay protection on
the transformer bank. For transformer trouble, the bank
lockout relay operates, tripping the total bank breaker and
the Company's 115 kV circuit breaker. When this lockout
relay operation occurs, Seller's personnel will not be able
to close the Company's 115 kV circuit breaker.
2. Company has the following relay protection schemes:
a. Non-directional total overcurrent relays that back up the
Seller's bank overcurrent relays and trip the Company's 115
kV circuit breaker.
b. Directional voltage-sensitive overcurrent relays that trip
the Company's 115 kV circuit breaker.
c. Under- and over-frequency relays that trip the Company's 115
kV circuit breaker except as defined in Section VII. below
(Bypass Switching).
d. A transfer-tripping scheme that trips the Company's 115 kV
circuit breaker (or if bypassed trips the Seller's total
bank breaker) for a fault on the Company's Xxx Sub-Xxxxxxx
115 kV Line.
If the Company's total overcurrent relays operate, the Seller
will not be able to close the Company's 115 kV circuit breaker.
Company will have to send someone to the switching station to
close the 115 kV breaker.
Page 25
C. Alarms
1. The following alarms are transmitted to Company's Energy Control
Center (ECC) in Raleigh, N.C.
o Company's station battery low voltage
o Company's 115 kV circuit breaker operation
o Company's 115 kV circuit breaker mechanism trouble
o Transfer-trip channel trouble (loss of guard)
2. When receiving an alarm, the Company power system operator at the
ECC will send personnel to investigate the reason for the alarm.
VII. OPERATING PRACTICES
Company personnel will operate all Company-owned substation facilities, and
Seller will operate all Seller-owned substation facilities, except as
specified under Section VII. Part B.
A. Company's Xxxxxxxx Cogentrix 115 kV Switching Station Equipment
Operated by Company:
1. Company personnel will operate all Company owned equipment.
B. Company's Xxxxxxxx Cogentrix 115 kV Switching Station Equipment
Operated by Seller
1. Remote Operation of Company's Equipment
a. Authorized Seller personnel will be allowed remote operation
(trip and close) of the Company's 115 kV circuit breaker.
The 115 kV circuit breaker can be closed remotely only if
the following conditions are met:
i. Permission for closing the Company's 115 kV circuit
breaker is granted by the Company's Power System
Operator.
ii. The LOCAL/REMOTE switch is in the REMOTE position.
iii. The Company's Xxx Sub-Xxxxxxx 115 kV Line is energized.
iv. No bank relay has operated.
v. Seller's total bank breaker is open.
b. After the Company's 115 kV circuit breaker is closed, the
Seller should be able to synchronize with the total bank
breaker. The Seller has the ability to synchronize the
Seller's generator with either the Seller's total bank
breaker or the Seller's generator breaker.
Page 26
c. Seller will report all operations of the Company's 115 kV
circuit breaker immediately after each operation. If the 115
kV circuit breaker is to be opened, it should be coordinated
ahead of time with the Company's Power System Operator
unless conditions occur which endanger human life or
equipment and require immediate action.
2. Bypass Switching
a. If the bypass switch on the Company's 115 kV circuit breaker
at the Company Xxxxxxxx Cogentrix 115 kV Switching Station
is to be closed for breaker maintenance or other necessary
reasons, Seller will be notified, when possible, at least 10
days prior to closing the bypass switch. Seller will also be
notified immediately before the bypass switch is closed.
b. Just prior to closing the bypass switch, Company will change
the LOCAL/REMOTE switch to LOCAL and place the switch
labeled NORMAL/BYPASS in the BYPASS position. This transfers
the transfer-trip, under/over frequency relaying to trip
only the Seller's total bank breaker while the Company's 115
kV circuit breaker is bypassed.
c. If the bypass switch on the 115 kV circuit breaker at the
Xxxxxxxx Cogentrix 115 kV Switching Station is closed, the
Company's Power System Operator will not issue a stop test
for the Xxx Sub-Xxxxxxx 115 kV Line. Automatic reclosing
equipment may be placed in MANUAL position, however,
permission will not be given for personnel to work on the
transmission line while the bypass switch is closed.
C. Seller Guidelines for Planned Clearing of the Company Substation
1. Seller will notify Company fourteen (14) days in advance of the
need or desire to clear its facilities from the Company system.
2. The Company power system operator will arrange for the necessary
equipment to be cleared and tagged by Company operating
personnel.
3. Seller personnel may place their own clearance tags on
Company-owned disconnecting devices in accordance with its own
safety procedures.
Page 27
4. Upon completion of the work and proper authorization by Seller,
the Company power system operator will arrange for the Company
equipment to be returned to service.
D. Scheduled Maintenance on Seller's Generation
Seller will provide to the Company Manager of System Operations each
year in January a 12-month anticipated maintenance outage schedule of
three days or more duration. Throughout the year, Seller will provide
reasonable advance notice to Company of any modifications to the
maintenance schedule. Seller will make best effort to prevent
scheduled maintenance from exceeding 45 days per year.
E. Scheduled Outages/Maintenance on Company Facilities
1. When it is necessary for Company to place a Stop Test Order on
its equipment, Seller will be notified in advance. If the
insolating switching device opens while a Stop Test Order is in
effect, the devise will not be reclosed until the Company person
holding the Stop Test Order gives permission to the Company power
system operator. Only Company personnel are allowed to reclose
the Company-owned equipment.
2. Company equipment will be tested periodically. Prior to testing,
the time of the test will be coordinated with Seller's authorized
personnel by the Company power system operator.
3. The Company representative, or the Company power system operator
will notify Seller prior to a prearranged clearance the may
impact Seller's facilities.
F. Miscellaneous
1. Seller will contact the Company power system operator and request
permission to synchronize their generation with the Company
Transmission System. Under no condition shall Seller synchronize
generation with the Company Transmission System without prior
approval of the Company power system operator.
2. When Seller is not injecting power to the Company Transmission
System, the generation shall not be in parallel with the Company
Transmission System unless Seller has received permission from
the Company power system operator.
Page 28
3. Seller will communicate daily with the Company power system
operator to discuss their operating plans and capability.
4. For all planned Seller work or activities that affect the Company
Transmission System, and which do not require immediate
attention, Seller's personnel should contact the Outage
Coordinator as indicated in Exhibit II. All other day-to-day
operations will be coordinated through the Company power system
operator. Refer to Exhibit II for specific contact information.
5. Seller shall confirm kW and kWh meter readings daily with the
Company power system operator by telephone.
Page 29
APPENDIX A
EXHIBIT I
DESCRIPTION OF THE INTERCONNECTION
I. This facility is located near Kornegay, North Carolina.
II. Seller has a generating facility consisting of approximately 35 MW of
generation connected to a secondary bus via a Seller-owned generator
breaker. All of the Seller's auxiliary load is connected to the secondary.
A Seller-owned total bank circuit breaker connects the secondary bus to the
Seller-owned 115/13.8 kV transformer bank.
III. The Company-owned equipment at Company's Xxxxxxxx Cogentrix 115 kV
Switching Station consists of a 115 kV circuit breaker and metering
equipment, located on the high-voltage side of the Seller-owned 115/13.8 kV
transformer.
Page 30
APPENDIX A
EXHIBIT II
COORDINATION CONTACTS
I. COMPANY COORDINATION CONTACTS:
A. Outage Coordinator at the Energy Control Center in Raleigh, North
Carolina (ECC): Mgr-Power Sys Ops-Carolina-Xxxxxxx X. Xxxxx
Telephone: (000) 000-0000
B. Company power system operator in Raleigh, North Carolina.
Telephone: (919) 546--6527
C. The alternate contact in the event that the Company power system
operator cannot be reached is: Alternate: Director Power System
Operations Carolinas- Xxxxx X. Xxxxxxxxx
Telephone: (000) 000-0000
II. SELLER COORDINATION CONTACTS:
A. Primary Contact: Kenansville Plant Manager Xxxxx Xxxxxx
Telephone: (000) 000-0000
B. Alternate Contact:
Xxxxx Xxxxxxxxx
Telephone: (000) 000-0000
Page 00
XXXXXXXX X
INTERCONNECTION FACILITIES
Company shall install, own, operate, and maintain all lines and equipment
located on its side of the point of interconnection. It shall also install and
own the necessary metering equipment, and meter transformers, where necessary,
for measuring the electricity delivered to Company, though such meter may be
located on Seller's side of the point of interconnection. Interconnection
facilities, installed by either Company or Seller, solely for such purpose,
include, but are not limited to connection, line extension, transformation,
switching equipment, protective relaying, metering, telemetering,
communications, and appropriate safety equipment.
Point of Interconnection
------------------------
The Point of Interconnection will be the point where the Company's jumpers
connect to the high-side bushings of the Seller's three-phase 115/13.2 kv
generator step-up transformer. See Figure 1 titled, "Company / Customer (Seller)
Xxxxxxxx Facilities", which drawing is attached hereto and made a part hereof.
Transmission Interconnection Facilities to be Furnished by Company
------------------------------------------------------------------
Company shall own, operate, and maintain all Transmission Interconnection
Facilities. These facilities include real property associated with the
Transmission Interconnection Facilities, 2.29 miles of 115 kV line and the
Company's Xxxxxxxx Cogentrix 115 kV Switching Station and all associated
equipment. This tap line interconnects to the Company Transmission System at
structure #263 on the Company's Xxx- Xxxxxxx 115 kV line. (See Figure 1).
Seller Facilities to be Furnished by Seller
-------------------------------------------
Seller will own, operate, and maintain all facilities that connect Seller's
Facility to the Transmission Interconnection Facilities. These facilities
consist of a Seller-owned generator breaker that connects to the Facility's
secondary bus and a total bank circuit breaker that connects the secondary bus
to the Seller-owned 115/13.8 kV transformer bank. (See Figure 1).
Any interconnection facilities installed by Company necessary to receive power
from Seller shall be considered as additional facilities and shall be provided,
if Company finds it practicable, under the following conditions:
(1) The facilities will be of a kind and type normally used by or
acceptable to Company and will be installed at a place and in a manner
satisfactory to Company.
(2) Seller will pay to Company a Monthly Facilities Charge of $ 20,730
which is 2% of the original installed cost and rearrangement cost of
all facilities required to accept interconnection ($1,036,540).
Page 32
(3) If Company increases its investment, either by decision of the Company
or request of the Seller, other than replacement of existing equipment
with equipment of equal capacity and kind, in interconnection
facilities or other special facilities required by Seller (including
conversion of the Company's primary voltage to a higher voltage), the
monthly charge for providing the additional facilities will be
adjusted at that time. The new Monthly Facilities Charge will be 2% of
the total investment, which includes existing facilities and
additional investment. Conversely, if Company utilizes the tap line to
supply load or accept generation into its system other than that of
Seller, said total investment will be proportionately reduced.
(4) The Monthly Facilities Charge as determined in (2) and (3) above shall
continue for the term of the Agreement until terminated by Seller or
Company.
(5) Seller's wiring and appurtenant structures shall provide for the
location, connection, and installation of Company's standard metering
equipment or other equipment deemed necessary by Company for the
metering of Seller's electrical output. Company shall, at its expense,
be permitted to install, in Seller's wiring or equipment, any special
metering devices or equipment as deemed necessary for experimental or
monitoring purposes.
Page 33
TERMS AND CONDITIONS FOR THE PURCHASE OF ELECTRIC POWER
For Qualifying Facilities with Generating Capacity Greater than 5 XX
x. PURCHASE AGREEMENT
------------------
These "Terms and Conditions" provide a mechanism through which Carolina
Power and Light Company, hereafter called Company, will agree to purchase
energy or capacity or both from a "Qualifying Cogeneration or Small Power
Production Facility" (Seller) as defined in the Regulations of the Federal
Energy Regulatory Commission (FERC) or other governmental authority having
jurisdiction, and for Seller to supply to Company energy or capacity or
both as defined herein. This Purchase Agreement does not provide for the
sale of any electric service by Company to Seller. If Seller requires
supplementary, standby, or interruptible power from Company, Seller shall
enter into a separate Retail Service Agreement or amend an existing Retail
Service Agreement, as appropriate, in accordance with Company's applicable
electric service tariffs on file with and authorized by the state
regulatory agency having jurisdiction.
(a) Description - The Purchase Agreement (hereinafter sometimes termed
"Agreement") shall consist of (1) Company's form of Application for
Standard Contract by a Qualifying Cogenerator or Small Power Producer
(Application) when signed by Seller and accepted by Company, (2) the
applicable Schedule and Riders, (3) these Terms and Conditions for the
Purchase of Electric Power for Qualifying Facilities with Generating
Capacity Greater than 5 MW (hereinafter referred to as "Terms and
Conditions"), and (4) the Operation Agreement for Qualifying
Facilities with Generating Capacity Greater than 5 MW when signed by
Seller and accepted by Company, and all changes, revisions,
alterations therein, or substitutions therefor lawfully made.
(b) Applicability - This Purchase Agreement shall be applicable only if
Seller's facility is a "Qualifying Cogenerator or Small Power
Production Facility" under Section 201 of The Public Utilities
Regulatory Policies Act of 1978 (PURPA), and the rules set forth by
the FERC.
(c) Application of Terms and Conditions, Schedules, and Riders - All
Purchase Agreements in effect at the time of the approval hereof or
that may be entered into in the future, are made expressly subject to
these Terms and Conditions, and subject to all applicable Schedules
and Riders, and any changes therein, substitutions thereof, or
additions thereto lawfully made, provided no change may be made in
rates or in the terms and conditions of this contract except by mutual
agreement of the parties to this contract.
(d) Conflicts - In case of conflict between any provision of a Schedule or
Rider or Application, and of these Terms and Conditions, the provision
of the Schedule or Rider or Application shall prevail.
(e) Transfer of Agreement - A Purchase Agreement between Company and
Seller may be transferred and assigned by Seller to any person, firm,
or corporation purchasing or leasing and intending to continue the
operation of the plant or business which is interconnected under such
Agreement, subject to the written approval of Company. Company will
grant such approval upon being reasonably satisfied that the assignee
will fulfill the terms of the Agreement and if, at Company's option, a
satisfactory guarantee for the payment of any applicable bills is
furnished by assignee. In addition, Seller shall have the right to
enter into a collateral assignment of the Agreement and any revenues
and contract rights thereunder to one or more lenders in connection
with a financing of Seller's Facility, and Company agrees that it will
not unreasonably delay or withhold its consent to any such assignment,
provided that Seller shall remain liable for its performance under
this Agreement notwithstanding any such assignment under this
sentence.
(f) Suspension of Sales Under Agreement at Seller's Request - If Seller is
temporarily unable to produce the electricity contracted for due to
physical destruction of, or damage to, his premises, Company will,
upon written request of Seller, and for a period Company deems as
reasonably required to replace or repair such premises, suspend
billing under the Agreement, exclusive of any Monthly Facilities
Charges, effective with the beginning of the next billing period.
(g) Termination of Agreement at Seller's Request - If Seller desires to
terminate the Agreement, Company maintains the right but not
obligation to agree to such termination. Termination will not be
granted if Company is not satisfied that all bills for services
previously rendered to Seller have been paid.
(h) Company's Right to Terminate or Suspend Agreement - Company, in
addition to all other legal remedies, may either terminate the
Agreement or suspend purchases of electricity from Seller (l) for any
default or breach of Agreement by Seller as defined in Section 15.0 of
the Operation Agreement for Qualifying Facilities with Generating
Capacity Greater than 5 MW, (2) for fraudulent or unauthorized use of
Company's meter, (3) for failure to pay any applicable bills when due
and payable, (4) for a condition on Seller's side of the point of
delivery actually known by Company to be, or which Company reasonably
anticipates may be, dangerous to life or property, or (5) due to
Seller's inability to deliver to Company the quality of electricity
mutually agreed to in the Purchase Agreement, unless Seller's
inability to deliver the quality of electricity is due to force
majeure as specified in Section 11.0 of the Operation Agreement for
Qualifying Facilities with Generating Capacity Greater than 5 MW.
No such suspension, however, will be made by Company without written
notice delivered to Seller, personally or by mail, stating what in
particular in the Agreement has been violated, except that no notice
need to be given in instances set forth in 1.(h)(2) and 1.(h)(4)
above. Company may terminate Agreement if violation for suspension
continues for more than sixty (60) days after written notice has been
delivered.
Failure of Company to terminate the Agreement or to suspend the
purchase of electricity at any time after the occurrence of grounds
therefor, or to resort to any other legal remedy or to exercise any
one or more of such alternative remedies, shall not waive or in any
manner affect Company's right later to resort to any one or more of
such rights or remedies on account of any such ground then existing or
which may subsequently occur.
Any suspension of the purchase of electricity by Company or
termination of the Agreement upon any authorized grounds shall in no
way operate to relieve Seller of Seller's liability to compensate
Company for services and/or facilities supplied, nor shall it relieve
Seller of liability for the payment of minimum monthly charges during
the period of suspension
(i) Suspension of Purchases at Company's Request - If Seller has a
Contract Capacity of 5,000 kW or greater, Company will contract for a
maximum number of hours annually during which Company may suspend
purchases. Company will exercise reasonable and diligent effort to
notify Seller, and provide maximum prior notice, prior to a request
for suspension to allow for Seller's proper planning and coordination
of such suspension.
2. PURCHASES OF ELECTRICITY
------------------------
If Seller desires to purchase electricity from Company through the same
point of interconnection used by Seller in supplying power to Company, and
Company approves, then Seller shall execute a separate Agreement for such
purchases in accordance with Company's Rate Schedules, Riders, and Service
Regulations as filed with the regulatory authority having jurisdiction.
Company's purchases of electricity from Seller and sales to Seller shall be
separately metered.
3. CONTRACT CAPACITY
-----------------
(a) The Contract Capacity shall be the kW of capacity specified in the
Application for Standard Contract by a Qualifying Cogenerator or Small
Power Producer. In cases where any change is required in Company's
facilities due to the actual capacity delivered exceeding the Contract
Capacity or due to Seller requesting an increase in the capacity of
Company's facilities, Company may require Seller to execute a new
Agreement or amend an existing Agreement, thereby establishing a new
Contract Capacity. If Company's facilities cannot be upgraded to
accept such actual or requested increase, then upon written notice,
Seller will not exceed the existing Contract Capacity or such amount
in excess thereof as Company determine it is able to accept.
(b) If Seller increases his generating capacity without adequate notice to
Company, and without receiving Company's consent, and such
unauthorized increase causes loss of or damage to Company's
facilities, the cost of making good such loss or repairing such damage
shall be paid by Seller and shall not be considered consequential
damages.
(c) Company may require that a new Contract Capacity be determined when it
reasonably appears that the capacity of Seller's generating facility
will deviate from contracted or established levels for any reason,
including, but not limited to, a change in water flow, steam supply,
or fuel supply.
4. CONTRACT ENERGY
---------------
The Contract Energy shall be computed for on-peak and off-peak time periods
and shall be the resultant total annual kilowatt-hours registered or
computed by or from Company's metering facilities for each time period
during a continuous 12-month interval.
5. CONTRACT TERMINATION
--------------------
If Seller or Company terminates the Agreement, the Seller's facilities
charges will be applied as outlined in the existing Facility
Interconnection and Operating Agreement between Seller and Company, dated
January 18, 2002, on file with the Federal Energy Regulatory Commission.
6. QUALITY OF ENERGY RECEIVED
--------------------------
Seller has full responsibility for the routine maintenance of his
generating and protective equipment to insure that reliable, utility grade
electric energy is being delivered to Company. Failure of Seller to comply
will constitute grounds for Company to cease parallel operation with
Seller's generation equipment and constitute grounds for termination or
suspension of the Agreement as set forth under Item 1.(h) above.
7. BILLING
-------
(a) Company's meters will be read as nearly as practicable at regular
intervals of not less than 27 days and not more than 33 days.
(b) If Company is unable to read its purchase meter for any reason,
Seller's production may be estimated by Company on the basis of
Seller's production during the next preceding billing period for which
readings were obtained, unless some unusual condition is known to
exist. A xxxx or payment rendered on the basis of such estimate shall
be as valid as if made from actual meter readings.
(c) The term "Month" or "Monthly", as used in Company's Schedules and
Riders, refers to the interval transpiring between the previous meter
reading date and the current reading date and bills shall be rendered
accordingly, except that if the period covered by an initial or final
xxxx, or due to rerouting of the meter reading schedule, is more or
less than 27-33 days, the xxxx will be prorated based on a 30-day
billing month.
(d) Payments for capacity and/or energy will be made to Seller based on
the rate schedule stated in the Application for Standard Contract by a
qualifying Cogenerator or Small Power Producer.
8. METER STOPPAGE OR ERROR
-----------------------
In the event a meter fails to register accurately within the allowable
limits established by the state regulatory body having jurisdiction,
Company will adjust the measured energy for the period of time the meter
was shown to be in error, and shall, as provided in the rules and
regulations of the state regulatory body having jurisdiction, pay to
Seller, or Seller shall refund to Company, the difference between the
amount billed and the estimated amount which would have been billed had the
meter not exceeded the allowable limits. No part of any minimum service
charge shall be refunded.
9. POINT OF INTERCONNECTION
------------------------
The point of interconnection is the point where Company's conductors are,
or are to be, connected to Seller's conductors. Seller shall do all things
necessary to bring his conductors to such point of interconnection for
connection to Company's conductors, and shall maintain said conductors in
good order at all times. If Seller chooses to deliver power to Company
through a point of delivery where Seller presently receives power from
Company, then the point of interconnection shall be the same point as the
point of delivery.
10. CONTINUANCE OF PURCHASES AND LIABILITY THEREFOR
-----------------------------------------------
Company does not guarantee continuous purchases but shall use reasonable
diligence at all times to provide for acceptance of electricity and having
used reasonable diligence shall not be liable to Seller for damage, for
failure in, or for interruptions or suspensions of the same.
11. DISPATCHING OF SELLER'S GENERATION
----------------------------------
Company may desire to dispatch Seller's generation, from Company's central
dispatching facility, if the generation is firm capacity equal to or
greater than 5,000 kW. Firm capacity shall be considered to be a facility
which is fueled by a reliable fuel supply with adequate fuel storage and is
available to deliver power to Company's system as requested by Company's
system dispatcher during the system daily and seasonal peak periods.
Conditions affecting the ability of a facility to be classified as firm
capacity, and therefore to be eligible for dispatch by Company are:
(1) Seller's generation must be available upon the request of Company's
system dispatcher.
(2) Seller shall schedule maintenance of Seller's generator during periods
approved by Company, not to exceed 45 days per calendar year.
(3) Telemetering and communications, for automatic control of Seller's
generation by Company, will be required as a part of the
interconnection facilities for any dispatched facility.
(4) Other mutually agreeable considerations will be made a part of the
negotiated contract as necessary.
12. GOVERNMENTAL RESTRICTIONS
-------------------------
This Agreement is subject to the jurisdiction of those governmental
agencies having control over either party or over this Agreement. This
Agreement shall not become effective until all required governmental
authorizations are obtained. Certification of receipt of all permits and
authorizations shall be furnished by Seller to Company upon Company's
request. This Agreement shall not become effective unless it and all
provisions thereof are authorized and permitted by such governmental
agencies without change or conditions.
This Agreement shall at all times be subject to changes by such
governmental agencies, and the parties shall be subject to conditions and
obligations, as such governmental agencies may, from time to time, direct
in the exercise of their jurisdiction, provided no change may be made in
rates or in essential terms and conditions of this contract except by
agreement of the parties to this contract. Both parties agree to exert
their best efforts to comply with all of the applicable rules and
regulations of all governmental agencies having control over either party
or this Agreement. The parties shall take all reasonable action necessary
to secure all required governmental approval of this Agreement in its
entirety and without change.
The delivery date, quantity, and type of electricity to be accepted for
purchase by Company, from Seller, are subject to changes, restrictions,
curtailments, or complete suspensions by Company as may be deemed by it to
be necessary or advisable (a) on account of any lawful order or regulation
of any municipal, State, or Federal government or agency thereof, or order
of any court of competent jurisdiction, or (b) on account of any emergency
due to war, or catastrophe, all without liability on the part of the
Company therefor.
13. GENERAL
-------
(a) Whenever the term "purchase" or "purchase of electricity" is used in
these Terms and Conditions or other portions of the Agreement, it
shall be construed to refer to the electricity supplied to Company by
Seller.
(b) The term "Company's conductors" shall mean Company's wires extending
from the point of connection with Company's existing electric system
to the point of interconnection.
(c) The term "Seller's conductors" shall mean Seller's wires extending
from the point of interconnection to the switch box or other point
where Seller's circuits connect for the purpose of supplying the
electricity produced by Seller.
(d) The term "'interconnection" shall mean the connection of Company's
conductors to Seller's conductors.
APPLICATION FOR STANDARD CONTRACT
BY A QUALIFYING COGENERATOR OR SMALL POWER PRODUCER
1. The undersigned, hereinafter called "Seller," hereby requests that Carolina
Power & Light Company, hereinafter called "Company," purchase the
electricity supplied to Company's system by Seller's "Qualifying
(Cogeneration/Small Power Production) Facility" located at or near
Kenansville, North Carolina, in accordance with the terms hereof, Company's
Schedule No. CSP-20B and any applicable Riders, and the Terms and
Conditions for the Purchase of Electric Power for Qualifying Facilities
with Generating Capacity Greater than 5 MW ("Terms and Conditions"), a copy
of each being attached and made a part of this Agreement.
2. Electricity supplied, by Seller, hereunder shall be in the form of 3 phase,
3 wires, alternating current of 60 cycles and sufficient power factor to
maintain system operating parameters as specified by Company, with a
maximum on-peak generation capacity of 32,000 kW and an annual on-peak
energy production of not more than 96,000,000 kWh. Upon the completion of
the installation, by Company, of its interconnection facilities at the
point of interconnection of Seller's and Company's conductors, Seller shall
become responsible for the payment to Company of any and all charges that
may apply, whether or not Seller actually delivers any electricity to
Company.
3. The point of interconnection for the acceptance of Seller's electricity
supplied hereunder will be where Seller's conductors meet Company's
conductors as defined in Appendix B of the Operation Agreement for
Qualifying Facilities with Generating Capacity Greater than 5 MW.
The Company agrees to furnish the following interconnection facilities: as
defined in Appendix B of the Operation Agreement for Qualifying Facilities
with Generating Capacity Greater than 5 MW.
4. Upon the acceptance hereof by the Company, evidenced by the signature of
its authorized representative in the block provided below, this Agreement
together with the attachments specified in Paragraph 1 of this Agreement
shall become an agreement for Seller to deliver and sell to Company and for
Company to receive and purchase from Seller the electricity generated and
declared by Seller from its above-described qualifying generating facility
at the rates, in the quantities, for the term, and upon the terms and
conditions set forth herein.
5. Payment for energy and/or capacity received by Company, or payment by
Seller, if any, as set forth in the rate schedule shall be due within 15
days from the date billed, and shall be administered through Company's
Raleigh office.
6. The initial term of this Agreement (Term) is from January 1, 2003 and
continuing until December 31, 2012. Seller will not deliver energy to any
third party during the Term of this Agreement.
7. The Seller hereby certifies that this facility is "new capacity," as
defined by the Federal Energy Regulatory Commission (FERC), and that
construction was commenced on or after November 9, 1978.
8. In emergency conditions, Company retains the right to request Seller to
generate. When Seller generates at Company's request, Company agrees to pay
Seller $1,250 for each startup at times that the turbine generator is
off-line for more than 16 hours, and the Variable Energy and Capacity
Credits as stated under CSP-20B, or its successor, for energy received
during the emergency period.
9. Company agrees not to seek dispatch of Seller's generation until such time
that Seller modifies facility and/or fuel source to accommodate dispatch of
Seller's generation. At that time, Company may request, and Supplier may
mutually agree to, dispatch rights pursuant to Section 11 of the Terms and
Conditions.
10. Seller shall pay Company a Monthly Facilities Charge of $20,730 consistent
with the provisions defined in Appendix B of the Operation Agreement for
Qualifying Facilities with Generating Capacity Greater than 5 MW.
11. Company agrees to purchase electricity supplied to Company's transmission
system by Seller's qualifying power production facility at the rates and
provisions established under Schedule CSP-20B and its successor(s) as
modified by Attachment 1 and made part of this agreement.
12. The parties agree that the Company will make no claims to any Credits
Related to Environmental Emissions or Discharges or any Credits Related to
Renewable Energy Resources under the present rates established and paid to
Seller under Schedule CSP-20B, as referred to in Paragraph 11 of this
agreement. If future rates established and paid to Seller under Schedule
CSP-20B or its successor(s), as referred to in Paragraph 11 of this
agreement, include the cost or value of any such Credits, then such Credits
shall accrue to Company or, if such Credits do not accrue to Company, the
rate paid to seller shall be reduced by the value as provided in avoided
cost calculations of such Credits. Company will not unduly withhold
Supplier's opportunity to sell Credits that are not owned by Company to a
third party. If separate calculations of costs or values of such Credits
are not available, Company agrees to provide access to its avoided cost
calculations for review by Seller; provided, however, that such access
shall be consistent with the Company's usual practice for providing access
to such documents, which contain proprietary, confidential and competitive
information within the scope of N.C. Gen. Stat. ss. 132-1.2. For the
purpose of this Paragraph 12, Credits Related to Environmental Emissions or
Discharges shall mean any credits, allowances or allocations related to
emissions (as that term is defined in the Clean Air Act, 42 U.S.C. xx.xx.
7401 et seq.) or discharges (as that term is defined in the Clean Water
Act, 33 U.S.C. xx.xx. 1251 et seq.), including but not limited to
"allowance" as defined in 42 U.S.C. ss. 7651a(3) and "allocation" as
defined in 40 C.F.R. ss. 96.2, and any credit, allowance or allocation
related to an emission or discharge that is authorized or created pursuant
to federal, state or local law or regulation or international treaty. For
the purpose of this Paragraph 12, Credits Related to Renewable Energy
Resources shall mean financial or economic credits related to the
production of electric power from renewable energy resources, including but
not limited to energy that is generated from solar, wind, biomass or
geothermal energy resources.
13. In accordance with Paragraph 2 of this Agreement and Articles 3.6.1 and
8.12 of the Operation Agreement, Company agrees to purchase electricity
supplied by Seller at the point of interconnection at a nominal voltage of
115,000 volts; however, at all times the actual voltage maintained shall
support the system voltage maintained in the area.
14. Seller shall reduce the output of the facility to a level of 7 (seven) MW
during off-peak periods of system low load conditions for periods not to
exceed 1,000 cumulative hours during each one-year term of the Agreement,
when requested to do so by the Company. Seller will receive no compensation
for any generation over 7 (seven) MW during this period. Company will
provide Seller as much notice as reasonably possible under the
circumstances of a reduction to allow for Seller's proper planning and
coordination of such reduction.
15. Seller will provide Company, by the 15th of each calendar month, a
statement of its fuel cost consumed for the production of electricity at
the facility for the prior calendar month. Such costs shall include
start-up, running and stand-by fuel. Company will use this fuel cost
information in regulatory fuel cost recovery proceedings and only divulge
such cost data in support thereof.
Witness as to Seller:
------------------------------ Green Power Kenansville LLC, Seller
------------------------------ By
---------------------------------
Title
------------------------------
This day of ,2002
------ -------------
ACCEPTED: Carolina Power & Light Company Payment/Xxxx wire transferred to:
By Green Power Kenansville LLC
---------------------------------- ---------------------------------
Title Vice President -
Regulated Commercial Operations 0000 Xxxxxxxx Xxxx
------------------------------- ---------------------------------
This day of ,2002 Xxxxxxxxxx, XX 00000
-------- --------------- ---------------------------------
Notices: Notices:
Progress Energy Green Power Kenansville LLC
000 X. Xxxxxxxxxx Xxxxxx, XXX 00X 0000 XX Route 11 and 903
Xxxxxxx, XX 00000 Xxxxxxxxxxx, XX 00000
Attn: Cogeneration Manager Attn: Power Plant Manager
Green Power Energy Holdings LLC
0000 Xxxxxxxx Xxxx
Xxxxxxxxxx, XX 00000
Attn: Xxxxx Xxxxxxxxx
Attachment 1
Energy and Capacity
Rates and Terms
1. Energy:
During the Term of the Agreement, Seller is eligible for Energy Payments as
follows:
a) On-peak Variable Energy Credit as specified in Schedule CSP-20B and
its successor(s) for facilities whose deliveries enter the Company's
transmission system.
b) Off-peak Variable Energy Credit as specified in Schedule CSP-20B and
its successor(s) for facilities whose deliveries enter the Company's
transmission system.
2. Capacity:
During the first 2 (two) years of Term of the Agreement, from January 1,
2003 through December 31, 2004, Seller is eligible for Capacity Payments
during the months as defined in Table A:
TABLE A
-------------- ---------------- -------------------------------
Season Month Capacity Credit ((cent)/kWh)
-------------- ---------------- -------------------------------
Non-Summer December 1.460
-------------- ---------------- -------------------------------
January 1.460
-------------- ---------------- -------------------------------
February 1.460
-------------- ---------------- -------------------------------
Summer June 3.197
-------------- ---------------- -------------------------------
July 3.197
-------------- ---------------- -------------------------------
August 3.197
-------------- ---------------- -------------------------------
a) Seller is eligible for Capacity Credit during on-peak production for
the hours as defined in CSP-20B or successor tariffs. Capacity Credits
are not available for off-peak power production.
b) Summer and Non-Summer months are as stated in Table A.
c) After the first 2 (two) years of the Agreement Term, Seller and
Company agree to negotiate eligible Capacity Payment in good faith
taking into consideration then current Federal, State and North
Carolina Utilities Commission rulings and Orders.