Exhibit 10.3.23
Execution Copy
PLANT CONNECTION AGREEMENT
FOR THE
HEBER GEOTHERMAL PLANT NO. 1
BETWEEN
IMPERIAL IRRIGATION DISTRICT
AND
HEBER GEOTHERMAL COMPANY
Execution Copy
TABLE OF CONTENTS
SECTION TITLE PAGE
------- ----- ----
1 PARTIES ......................................................... 1
2 RECITALS ........................................................ 1
3 AGREEMENT ....................................................... 3
4 DEFINITIONS ..................................................... 3
5 EFFECTIVE DATE AND TERM ......................................... 4
6 CONNECTION OF PLANT ............................................. 4
7 ELECTRIC SERVICE TO HEBER GEOTHERMAL ............................ 4
8 METERING OF ENERGY DELIVERIES ................................... 4
9 HEBER GEOTHERMAL DELIVERY AND IID ACCEPTANCE OF
ENERGY FROM PLANT ............................................... 5
10 HEBER GEOTHERMAL'S GENERAL OBLIGATIONS .......................... 6
11 IID'S GENERAL OBLIGATIONS ....................................... 6
12 BILLING ......................................................... 7
13 AUTHORIZED REPRESENTATIVES ...................................... 7
14 METERS .......................................................... 8
15 CONTINUITY OF SERVICE ........................................... 9
16 LIABILITY ....................................................... 10
17 UNCONTROLLABLE FORCE ............................................ 10
18 INTEGRATION AND AMENDMENTS ...................................... 11
19 NON-WAIVER ...................................................... 11
20 NO DEDICATION OF FACILITIES ..................................... 11
21 SUCCESSORS AND ASSIGNS .......................................... 11
i
22 EFFECT OF SECTION HEADINGS ....................................... 12
23 GOVERNING LAW .................................................... 12
24 ARBITRATION ...................................................... 13
25 ENTIRE AGREEMENT ................................................. 14
26 NOTICES .......................................................... 15
27 SEVERAL OBLIGATIONS .............................................. 15
28 SIGNATURE CLAUSE ................................................. 16
ATTACHMENTS
EXHIBIT "A" ...................................................... 17
EXHIBIT "B" ...................................................... 19
ii
1. PARTIES
The parties to this Agreement are IMPERIAL IRRIGATION DISTRICT (IID),
an irrigation district organized and operating under the laws of the State of
California and HEBER GEOTHERMAL COMPANY (Heber Geothermal), a California
Partnership (hereinafter individually Party, collectively Parties).
2. RECITALS
2.1 Heber Geothermal leases and operates a geothermal generating
facility with a maximum 49.9 megawatt net output at the Heber known Geothermal
Resource Area (KGRA) and sells the Electric Output From the Plant to Southern
California Edison Company (SCE).
2.1.1 Heber Geothermal intends to construct the Plant, and
upon completion of such construction, sell the Plant to United States
Trust Company of New York, a New York corporation, not in its
individual capacity (except as expressly provided in the
Participation Agreement and the Trust Agreement) but solely as Owner
Trustee under the Trust Agreement, and its successors and assigns as
such Owner Trustee (the "Owner Trustee") and lease back the Plant
from the Owner Trustee pursuant to the Lease Agreement, dated the
Lease Closing Date, between the Owner Trustee, as Lessor, and Heber
Geothermal, as Lessee (the "Lease"). To finance construction of the
Plant, Heber Geothermal proposes to borrow money from General
Electric Credit Corporation, a New York corporation ("GECC"),
pursuant to a loan agreement. Such borrowing will be secured in
accordance with the Construction Deed of Trust, Assignment of Rents,
Security Agreement and Fixture Filing, dated as of December 1, 1983,
among Heber Geothermal, the deed trustee and GECC, and as it may be
amended, modified and supplemented from time to time in accordance
with the terms thereof (the "Mortgage")
by a first mortgage on the Plant and by an assignment (for security
purposes only) of certain contractual rights of Heber Geothermal.
Upon completion of such construction, Xxxxx Geothermal intends to
assign all of its rights under certain contracts outright to the
Owner Trustee pursuant to the Xxxx of Sale and Assignment, dated the
Lease Closing Date, from Heber Geothermal in favor of the Owner
Trustee (the "Xxxx of Sale") in connection with the sale of the Plant
to the Owner Trustee. Contemporaneously with such assignment and
sale, Heber Geothermal intends to enter into the Lease pursuant to
which all of the Owner Trustee's rights under such contracts will be
assigned to Heber Geothermal during the term of the Lease and
thereafter if Heber Geothermal purchases the Plant pursuant to the
terms of the Lease. After giving effect to the aforesaid sale and
leaseback, Heber Geothermal will be fully obligated to perform all of
its obligations with respect to such contracts.
2.2 SCE has entered into the Power Purchase Agreement dated August 26,
1983, (Purchase Agreement) with Heber Geothermal to purchase all the Electric
Output From the Plant.
2.3 SCE and Heber Geothermal agree that the terms and conditions
regarding transmission of the Electric Output From the Plant to an IID/SCE point
of interconnection shall be pursuant to an agreement to be entered between IID
and SCE.
2.4 Since the Plant has been built in the IID service territory, it
will be convenient to connect the Plant to the IID electric system.
Heber Geothermal hereby grants the IID the right to enter the Plant
site for any reasonable purposes connected with this Agreement, by previous
arrangements with the Plant manager. Those reasonable purposes included
maintenance and
repairs to IID equipment in Heber Geothermal facilities, observing tests of said
facilities, reading of kilowatt-hour meters, and the like.
2.5 Heber Geothermal desires to purchase and IID desires to sell the
electrical energy necessary to satisfy all of the corporation and maintenance
power consumption requirements of the Plant for the life of the Plant that is
not normally generated by the Plant itself, or portable generating equipment.
2.6 The Parties desire, by means of this Agreement, to interconnect the
Plant to the IID electrical system and to establish the terms, conditions and
obligations of the Parties relating to such interconnection.
3. AGREEMENT
The Parties agree as follows:
4. DEFINITIONS
4.1 Authorized Representative: The representative of a Party designated
in accordance with Section 13.
4.2 Energy: Electric energy in excess of Heber Geothermal's electric
energy requirements, expressed in kilowatt-hours, generated by the Plant and
measured and delivered to the Point of Delivery.
4.3 Operation Date: The day on which the Plant Energy is accepted by
IID for SCE's account.
4.4 Plant: A maximum of 49.9 MW net output geothermal generating
facility owned by Heber Geothermal including all associated equipment and
improvements necessary for generating electric energy and transmitting it to the
high voltage side of the power transformer.
4.5 Point of Delivery: The point on the high voltage side of Heber
Geothermal's switchyard where IID's metering equipment measures the delivery of
Energy to the IID system as shown on Exhibit "B".
4.6 System Emergency: A condition on IID's system which is likely to
result in imminent significant disruption of service to customers or is
imminently likely to endanger life or property.
4.7 Electric Output From the Plant: For the purposes of this agreement,
the Electric Output From the Plant shall be defined as the net metered output of
the Plant plus the net metered usage of electric power by chevron, as shown on
in Exhibit B.
4.8 Consumption of Energy From IID's Resources: For the purposes of
this agreement, Consumption of Energy From IID's Resources shall be defined as
the metered energy delivered to Heber Geothermal, less that metered energy
consumed by Chevron during deliveries from IID. Demand charges will be computed
in the same manner.
5. EFFECTIVE DATE AND TERM
This Agreement shall become effective when signed by the Parties and
shall terminate at the earlier of (i) midnight December 31, 2015, or (ii)
twenty-four (24) months from the date the plant has ceased to operate at the
option of the IID or (iii) the date agreed to by the Authorized Representatives.
6. CONNECTION OF PLANT
6.1 Heber Geothermal may electrically connect its Plant, in accordance
with the provisions of this Agreement, so that it can operate in parallel with
the IID electric system.
6.2 Notwithstanding the provision that Heber Geothermal has furnished
the high voltage switchyard complete, including the high voltage oil circuit
breakers and disconnect
switches, the control of the high voltage oil circuit breakers and disconnect
switches shall be under the control of the IID dispatcher.
7. ELECTRIC SERVICE TO HEBER GEOTHERMAL
IID shall provide electric service to Heber Geothermal pursuant to
Section 12.
8. METERING OF ENERGY DELIVERIES
Metering for electric service to Heber Geothermal and for energy
deliveries by Heber Geothermal to IID for SCE's account shall be at the Point of
Delivery as shown on Exhibit "B". Four meters shall be installed which shall
measure and record flows in each direction as shown on Exhibit "3".
9. HEBER GEOTHERMAL DELIVERY AND IID ACCEPTANCE OF ENERGY FROM PLANT
Whenever Electric Output From the Plant exceeds Heber Geothermal 's
power requirements, Heber Geothermal shall deliver all such excess output to IID
for the account of SCE and IID shall accept such output for the account of SCE
and deliver such output to SCE pursuant to transmission service agreement to be
entered into between Southern California Edison Company and Imperial Irrigation
District.
10. HEBER GEOTHERMAL'S GENERAL OBLIGATIONS
Heber Geothermal shall:
10.1 Operate the Plant in a manner consistent with applicable electric
utility industry standards, good engineering practice, and without degradation
of quality or reliability of the IID system.
10.2 Deliver the Electric Output From the Plant to IID for the account
of SCE at the Point of Delivery.
10.3 Each Party shall provide the reactive kilovolt ampere (KVA)
requirements of its own system so that there will be no interchange of reactive
KVA between systems. The Parties shall cooperate to control the flow of reactive
KVA to prevent the introduction of objectionable operating conditions on the
system of either Party.
10.4 Coordinate, to the greatest extent practicable, major overhaul and
inspection outages of the Plant with IID.
10.5 Give IID a written schedule on or before June 1, and December 1,
each year of the estimated amounts and rates of delivery of energy to be
delivered to IID for the account of SCE at the Point of Delivery during each
month of the succeeding twelve-month (12) period commencing July 1, and January
1.
10.6 Give IID a written schedule on or before the fifteenth (15th) day
of each month of the estimated amounts and rates of delivery of energy to be
delivered to IID for the account of SCE at the Point of Delivery during each day
of the succeeding calendar month.
10.7 Give IID a schedule on or before 12:01 p.m. on Tuesday of each
seven-day (7) period of the estimated amounts and rates of delivery of energy to
be delivered to IID for the account of SCE at the Point of Delivery during each
hour of the succeeding seven-day (7) period commencing at 12:01 a.m. on the
following Monday; provided, however, that if any changes in the hourly
deliveries so scheduled become necessary, Heber Geothermal shall notify IID of
such changes as far in advance as possible.
10.8 Provide IID any reasonable rights-of-way and access required for
testing and reading of meters by previous arrangement with the Plant manager.
10.9 When IID determines that it is necessary to utilize the
transmission capability being utilized by Heber Geothermal to meet IID's load
requirements,
a) pay its pro-rata share of the total costs associated with
extensions or upgrades of IID's existing system and/or a new system
required for delivery of Heber Geothermal's power, or
b) arrange for transmission capability exclusive of IID.
In any event, IID will give Heber Geothermal 60 months written notice of such
determination.
11. IID'S GENERAL OBLIGATIONS
11.1 Accept the Electric Output From the Plant for the account of SCE
at the Point of Delivery and concurrently deliver an equal amount of electric
energy to the SCE system at IID/SCE point(s) of interconnection.
11.2 Coordinate, to the greatest extent practicable, major overhaul and
inspection outages of IID transmission facilities with Heber Geothermal and
notify Heber Geothermal of any changes as far in advance as possible.
11.3 Carry out the directions of the Authorized Representative with
respect to the matters set forth in this Agreement.
12. BILLING
12.1 IID shall read the meters monthly according to its regular meter
reading schedule beginning no more than thirty (30) days after the date that
electric energy is first supplied to Heber Geothermal. IID monthly shall send
Heber Geothermal within ten (10) working days after the meter is read a xxxx for
electric service. Heber Geothermal shall pay IID the total amount billed within
thirty (30) days of receipt of the xxxx.
12.2 IID shall xxxx Xxxxx Geothermal for Heber Geothermal's Consumption
of Energy From IID's Resources in accordance with Rate Schedule A2, as it may be
revised from time to time. Copy of current Rate Schedule A2 is attached as
Exhibit "A".
12.3 If Heber Geothermal disputes a xxxx, payment shall be made as if
no dispute existed pending resolution of the dispute by the Authorized
Representatives. If the xxxx is determined to be in error, the disputed amount
shall be refunded by IID including interest at the rate of one and one half
percent (1-1/2%) per month, compounded monthly, from the date of payment to the
date the refund check or adjusted xxxx is mailed.
13. AUTHORIZED REPRESENTATIVES
13.1 Within thirty (30) days after the date this Agreement is signed,
each Party shall designate, by written notice to the other Party, an Authorized
Representative who is authorized to act in its behalf in the implementation of
this Agreement and with respect to those matters contained herein which are the
functions and responsibilities for the Authorized Representatives. Either Party
may, at any time, change the designation of its Authorized Representative by
written notice to the other Party.
13.2 IID's Authorized Representative shall develop detailed written
procedures necessary and convenient to administer this Agreement within six (6)
months after the date signed. Such procedures shall be submitted to Heber
Geothermal's Authorized Representative for review, comment, discussion and
concurrence before they are put into effect. Such procedures shall include,
without limitation: (i) communication between Heber Geothermal and IID's
electric system dispatcher with regard to daily operating matters, (ii) billing
and payments, (iii) specified equipment tests, and (iv) operating matters which
affect or may affect quality and reliability of service to electric customers
and continuity of deliveries to SCE.
13.3 The Authorized Representative shall have no authority to modify
any of the provisions of this Agreement.
14. METERS
14.1 All meters shall be sealed and the seal shall be broken only upon
occasions when the meters are to be inspected, tested or adjusted.
14.2 IID shall inspect and test all meters upon their installation and
at least once every year thereafter. If requested to do so by Heber Geothermal,
IID shall inspect or test a meter more frequently than every year, but the
expense of such inspection or test shall be paid by Heber Geothermal unless the
meter is found to register inaccurately by more than two percent (2%) from the
measurement made by a standard meter. Each Party shall give reasonable notice to
the other party of the time when any inspection or test shall take place and
that Party may have representatives present at the test or inspection. If a
meter is found to be inaccurate or defective, it shall be adjusted, repaired or
replaced in order to provide accurate metering. All adjustments due to
inaccurate meters shall be limited to the preceding six (6) months.
14.3 If a meter fails to register, or if the measurement made by a
meter during a test varies by more than two percent (2%) from the measurement
made by the standard meter used in the test, adjustment shall be made correcting
all measurements made by the inaccurate meter for:
(i) the actual period during which inaccurate measurements
were made, if the period can be determined, or if not,
(ii) the period immediately preceding the test of the meter
equal the one-half (1/2) the time from the date of the last previous
test of the meter; provided, however, that the period covered by the
correction shall not exceed six (6) months.
14.4 Heber Geothermal shall telemeter information to IID's new dispatch
center regarding the kilowatts, kilowatt-hours, kilovars and kilovar-hours
delivered to or received from IID at the Point of Delivery, as well as voltage
and breaker status over phone line leased by
Heber Geothermal. IID shall purchase, own, and shall design, install, operate,
maintain, or cause to be designed, installed, operated, and maintained,
equipment to automatically transmit from the Plant to IID's new dispatch center
continuous values of Plant output expressed as megawatts, megavars and
megawatt-hours. IID may thereupon xxxx and Xxxxx Geothermal shall promptly pay
IID's cost of design, purchase and installation of said equipment. Heber
Geothermal shall have the right to audit IID's records and accounts to verify
the cost of said equipment.
15. CONTINUITY OF SERVICE
IID shall not be obligated to accept and IID may require Heber
Geothermal to temporarily curtail, interrupt or reduce deliveries of energy upon
advance notice to Heber Geothermal, when such curtailment, interruption or
reduction is required in order for IID to construct, install, maintain, repair,
replace, remove, investigate or inspect any of its equipment or any part of its
system or if IID determines that such curtailment, interruption or reduction is
necessary because of a System Emergency, forced outages or abnormal operating
conditions on its system which IID in its sole judgment deems to jeopardize its
system integrity. IID shall exercise due diligence to minimize the frequency and
duration of such curtailments, interruptions or reductions.
16. LIABILITY
16.1 Neither Party shall hold the other Party, its officers, agents or
employees liable for any loss, damage, claim, cost, or expense for less of or
damage to property, or injury or death of persons, which arises out of the first
Party's ownership, operation or maintenance of facilities on its own side of the
Point of Delivery.
16.2 Each Party agrees to defend, indemnify and save harmless the other
Party, its officers, agents, or employees against all losses, claims, demands,
costs or expenses for loss of or
damage to property, or injury or death of persons, which directly or indirectly
arise out of the indemnifying Party's performance pursuant to this Agreement;
provided, however, that a Party shall be solely responsible for any such losses,
claims, demands, costs or expenses which result from its sole negligence or
willful misconduct.
17. UNCONTROLLABLE FORCE
Neither Party shall be considered to be in default with respect to any
obligation hereunder, other than the obligations to pay money, if prevented from
fulfilling such obligation by reason of an uncontrollable force. The term
"uncontrollable force" means any cause beyond the control of the Party affected,
including, but not limited to, failure or threat of imminent failure of
facilities, flood, earthquake, storm, lightning, fire, epidemic, war, riot,
civil disturbance, sabotage and restraint by court or public authority, which by
exercise of due diligence and foresight could not reasonably have been avoided.
Whichever Party is rendered unable to fulfill any obligation by reason of
uncontrollable forces shall give prompt written notice of such fact to the other
Party and shall exercise due diligence to remove such inability with all
reasonable dispatch. Nothing in this Agreement shall require a Party to settle
any strike or labor dispute in which it is involved.
18. INTEGRATION AND AMENDMENTS
This Agreement constitutes the entire agreement between the Parties
relating to the interconnection of Heber Geothermal's Plant to IID's electric
system, the acceptance of energy by IID from Heber Geothermal and the providing
of electric service by IID. No oral agreement or prior written agreement between
the Parties shall be of any effect whatsoever; provided, however, that any
arrangements agreed upon by the Authorized Representatives within the limits
of their authority, and consistent with this Agreement shall be binding upon the
Parties. All changes to this Agreement shall be in writing and shall be signed
by an officer of each Party.
19. NON-WAIVER
None of the provisions of this Agreement shall be considered waived by
either Party except when such waiver is given in writing. The failure of either
Party to insist in any one or more instances upon strict performance of any of
the provisions of this Agreement or to take advantage of any of its rights
hereunder shall not be construed as a waiver of any such provisions or the
relinquishment of any such rights for the future; but the same shall continue
and remain in full force and effect.
20. NO DEDICATION OF FACILITIES
Any undertaking by one Party to the other Party under any provision of
this Agreement shall not constitute the dedication of the system or any portion
thereof by the Party to the public or to the other Party, and it is understood
and agreed that any such undertaking under any provision of this Agreement by a
Party shall cease upon the termination of its obligations hereunder.
21. SUCCESSORS AND ASSIGNS
21.1 This Agreement shall be binding upon and inure to the benefit of
the respective successors and assigns of the Parties.
21.2 IID hereby consents to the assignment of this Agreement:
(i) by Heber Geothermal to GECC, as security, pursuant to
the Mortgage;
(ii) by Heber Geothermal to the Owner Trustee pursuant to
the Xxxx of Sale;
(iii) by the Owner Trustee to Heber Geothermal pursuant to
the Lease or otherwise to Heber Geothermal in connection with the
transactions contemplated by the Participation Agreement;
(iv) by any assignee permitted by this Section 21.2
(including any assignee permitted by this clause (iv) to any Person
if such Person is, or has a binding contract for the operation of the
Plant by, an experienced and prudent power plant operator and has a
net worth (determined in accordance with generally accepted
accounting principles) of at least $100,000,000;
(v) by any assignee permitted by this Section 21.2
(including any assignee permitted by this clause (v) to any Person,
unless IID shall have reasonably objected to such Person in writing
within 30 days of notice to IID of the proposed assignment, which
notice shall name the proposed assignee and the proposed operator of
the Plant, such objection to be because such assignee either (a) is
not a financially responsible entity, (b) is not, and does not have a
contract for the operation of the Plant by, an experienced and
prudent operating entity or (c) cannot obtain the rights, title and
interest necessary to perform the assigned obligations.
22. EFFECT OF SECTION HEADINGS
Section headings appearing in this Agreement are inserted for
convenience only, and shall not be construed as interpretations of text.
23. GOVERNING LAW
This Agreement shall be interpreted, governed and construed under the
laws of the State of California or the laws of the United States, as applicable.
24. ARBITRATION
24.1 Any dispute arising out of or relating to this Agreement, or the
breach thereof, which is not resolved by the Parties acting through their
Authorized Representatives shall be settled by arbitration to the extent
permitted by the laws applicable to the Parties; provided, however, that no
Party to the dispute shall be bound to any greater extent than any other Party
to the dispute. Arbitration shall not apply to any dispute or matter that is
within the jurisdiction of any regulatory agency.
24.2 Any demand for arbitration shall be made by written notice to the
other Party setting forth in adequate detail the nature of the dispute, the
issues to be arbitrated, the amount or amounts, if any, involved in the dispute,
and the remedy sought. Within twenty (20) days from the receipt of such notice,
the other Party may submit its own written statement of the dispute and may set
forth in adequate detail any additional related matters or issues to be
arbitrated.
24.3 Within thirty (30) days after delivery of the written notice
demanding arbitration, the Parties acting through their Authorized
Representatives shall meet for the purpose of selecting an arbitrator. The.
Parties may agree upon a single arbitrator, but in the event that they cannot
agree, three arbitrators shall be used. Each Party shall designate one
arbitrator, and the two arbitrators shall then select a third arbitrator. All
arbitrators shall be persons skilled and experienced in the field in which the
dispute has arisen and no person shall be eligible for appointment as an
arbitrator who is or has been an officer or employee of either of the Parties or
otherwise interested in the matter to be arbitrated. Should either party refuse
or neglect to appoint an arbitrator or to furnish the arbitrators with any
papers or information demanded, the arbitrators are empowered, by both Parties,
to proceed without the participation or assistance of that Party.
24.4 Except as otherwise provided in this Section, the arbitration
shall be governed by the rules and practices of the American Arbitration
Association, or a similar organization if the American Arbitration Association
should not at the time exist.
24.5 Arbitration proceedings shall be held in Imperial, California, at
a time and place to be selected by the arbitrators. The arbitrators shall hear
evidence submitted by the Parties and may call for additional information which
shall be furnished by the Party having such information. The arbitrators shall
have no authority to call for information not related to the issues included in
the dispute or to determine other issues not in dispute.
24.6 If there is only one arbitrator, his decision shall be binding and
conclusive on the Parties. If there are three arbitrators, the decision of any
two shall be binding and conclusive. The decision of the arbitrators shall
contain findings regarding the issues involved in the dispute, including the
merits of the positions of the Parties, the materiality of any default, and the
remedy or relief to which a Party shall be entitled. The arbitrators may not
grant any remedy or relief which is inconsistent with this Agreement, nor shall
the arbitrators make findings or decide issues not in dispute.
24.7 The fees and expenses of the arbitrators shall be shared equally
by the Parties, unless the decision of the arbitrators specifies some other
apportionment. All other expenses and costs of the arbitration shall be borne by
the Party incurring such expenses and costs.
24.8 Any decision or award granted by the arbitrators shall be final
and judgment may be entered on it in any court of competent jurisdiction. This
agreement to arbitrate shall be specifically enforceable.
25. ENTIRE AGREEMENT
The complete agreement of the Parties is set forth in this Agreement
and all prior
communications regarding subject interconnected operations whether oral or
written, are hereby abrogated and withdrawn.
26. NOTICES
Any formal communication or notice in connection with this Agreement
shall be in writing and shall be deemed properly given if delivered in person or
sent first class mail, postage prepaid to the person specified below:
Heber Geothermal Company
000 Xxxx Xxxxxx Xxxx
Xxxxx 000
Xxx Xxxx, Xxxxxxxxxx 00000
Imperial Irrigation District
c/o General Manager
X.X. Xxx 000
Xxxxxxxx, Xxxxxxxxxx 00000
27. SEVERAL OBLIGATIONS
Except where specifically stated in this Agreement to be otherwise, the
duties, obligations and liabilities of the Parties are intended to be several
and not joint or collective. Nothing contained in this Agreement shall ever be
construed to create an association, trust, partnership, or joint venture, or
impose a trust or partnership duty, obligation or liability on or with regard to
either Party. Each Party shall be individually and severally liable for its own
obligations under this Agreement.
28. SIGNATURE CLAUSE
The Parties have caused this Agreement to be executed in their
respective names, in duplicate, by their respective officers hereunto this 31st
day of July, 1985.
HEBER GEOTHERMAL COMPANY
By /s/ Xxxx X. Xxxxxxxx
------------------------------
Assistant General Manager
WITNESS:
By /s/ Xxxxxx X. Sindilar
------------------------------
IMPERIAL IRRIGATION DISTRICT
By /s/ X.X. Xxxxxx
------------------------------
President, Board of Directors
ATTEST:
By /s/ Xxxxx X. Xxxx
------------------------------
Secretary
IMPERIAL IRRIGATION DISTRICT EXHIBIT "A" Revised Sheet No. 166
Imperial, California ----------- Cancelling Sheet No. 139
SCHEDULE A-2
GENERAL WHOLESALE POWER SERVICE
APPLICABILITY
Applicable to general wholesale power service for industrial, commercial
and agricultural purposes, subject to special conditions hereinafter stated.
Applicable to standby or breakdown service where the entire electric power
requirements on the customer's premises are not regularly supplied by the
District.
MONTHLY RATE
The monthly rate shall be the sum of A, B, C and D.
A. Demand Charge ........... $2.52 per kilowatt of Billing Demand
B. Energy Charge ........... 5.60c per kwh.
C. Energy Cost Adjustment --
The amount computed in accordance with Schedule ECA.
D. Power Factor Adjustment --
A charge of $0.25 per kilovar of reactive demand as measured by the
incoming kilovar demand meter for each kilovar in excess of .60 times the
kilowatt demand measured and supplied by the District.
MINIMUM CHARGE
The minimum charge shall be the demand charge, but in no case shall the
minimum charge be less than the demand charge (A) multiplied by 75% of the
highest maximum demand established in the preceding 11 months.
SPECIAL CONDITIONS
(a) Voltage: This schedule applies to service rendered at a transmission
voltage of 34.5-kv or above. It shall be the responsibility of the
customer to furnish transformation to any other voltages required.
(b) Billing Demand: The billing demand shall be the kilowatts of measured
maximum demand but in no case less than 75 percent of the highest
maximum demand established in the preceding 11 months. The measured
maximum demand in any month will be the average kilowatt delivery
indicated or recorded by the District's demand meter in the 15-minute
interval in which such delivery is greater than any other 15-minute
interval. In case the load is intermittent or subject to violent
fluctuations, the District may base the demand upon a 5-minute
interval instead of a 15-minute interval.
(c) A minimum connected load of 5000 kw shall be required.
Board Resolution Date Effective
July 3, 1984 August 1, 1984
IMPERIAL IRRIGATION DISTRICT EXHIBIT "A" Revised Sheet No. 167
Imperial, California ----------- Cancelling Sheet No. 139
SCHEDULE A-2 (Continued)
GENERAL WHOLESALE POWER SERVICE
(d) Parallel Operation: A customer may operate its generating plant in
parallel with the District's system if such customer installs and
operates such control and protective equipment as required by the
District.
(e) Metering: The District will provide the normal metering equipment for
the size and type of load served. Additional metering which may be
required by the District shall be furnished by the customer and tested
in accordance with requirements of the District. Meters shall not
allow reverse registration.
(f) Regulations Governing Sale of Electric Energy: Service under this rate
schedule is subject to the District's Regulations Governing the Sale
of Electric Energy.
Board Resolution Date Effective
July 3, 1984 August 1, 1984
Exhibit B
[Graphic: Simplified Switch Connection Diagram of
Imperial Irrigation District to Heber Geothermal Plan]
7