STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS STATYBOS ADRESAS D. POŠKOS G. 7, ŠILALĖ STATINIO GRUPĖ GYVENAMOSIOS PASKIRTIES (TRIJŲ IR DAUGIAU BUTŲ) (DAUGIABUČIAI) PASTATAI...
STATINIO PROJEKTO PAVADINIMAS | DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | |
STATYBOS ADRESAS | D. POŠKOS G. 7, ŠILALĖ | |
STATINIO GRUPĖ | GYVENAMOSIOS PASKIRTIES (TRIJŲ IR DAUGIAU BUTŲ) (DAUGIABUČIAI) PASTATAI | |
STATINIO STATYBOS RŪŠIS | STATINIO ATNAUJINIMAS (MODERNIZAVIMAS) | |
STATINIO KATEGORIJA | YPATINGAS STATINYS | |
ETAPAS | TECHNINIS DARBO PROJEKTAS (TDP) | |
BYLA | VI | |
LAIDA | 0 | |
BYLOS IŠLEIDIMO DATA | 2021 | |
STATINIO PROJEKTO DALIS | ŠILDYMO IR VĖDINIMO DALIS (ŠV) | |
ŽYMUO | 1014-1A5p-PA(PM)-TDP-2110-ŠV | |
UŽSAKOVAS/STATYTOJAS | UAB „ŠILALĖS ŠILUMOS TINKLAI“, MAIRONIO G. 20B, LT- 75136, ŠILALĖ, ĮM. K. 176502533 | |
PROJEKTUOTOJAS | UAB ,,POLISTATYBA“ Atestato Nr. 4983 ĮMONĖS KODAS: 3006300009 ĮMONĖ ATESTUOTA: 2007.09.28 Nr.4983 APLINKOS MINISTERIJOJE | |
PROJEKTO VADOVAS | (parašas) | Xxxxx Xxxxxxxxxx 27833 ( vardas, xxxxxxx, kval. Atestato Nr.) |
PROJEKTO DALIES VADOVAS | (ŠV) (parašas) | Xxxxxxxx Xxxxxx 33244 ( vardas, xxxxxxx, kval. Atestato Nr.) |
STATINIO PROJEKTO DALIES BYLOS DOKUMENTŲ SUDĖTIES ŽINIARAŠTIS
Dokumento žymuo | Lapų sk. | Laida | Dokumento pavadinimas | Pastabos |
Tekstiniai dokumentai: | ||||
1014-1A5p-PA(PM)-TDP-2110-ŠV.T-BSŽ | 1 | 0 | Bylos sudėties žiniaraštis | |
1014-1A5p-PA(PM)-TDP-2110-ŠV.T-AR | 3 | 0 | Aiškinamasis raštas | |
1014-1A5p-PA(PM)-TDP-2110-ŠV.T-TS | 8 | 0 | Techninės specifikacijos | |
1014-1A5p-PA(PM)-TDP-2110-ŠV.T-SKŽ | 2 | 0 | Sąnaudų kiekių žiniaraštis | |
Grafiniai dokumentai: | ||||
1014-1A5p-PA(PM)-TDP-2110-ŠV.B-01 | 1 | 0 | Rūsio planas su šildymo sistema, M 1:100 | |
1014-1A5p-PA(PM)-TDP-2110-ŠV.B-02 | 1 | 0 | 1 aukšto planas su šildymo sistema, M 1:100 | |
1014-1A5p-PA(PM)-TDP-2110-ŠV.B-03 | 1 | 0 | 2 aukšto planas su šildymo sistema, M 1:100 | |
1014-1A5p-PA(PM)-TDP-2110-ŠV.B-04 | 1 | 0 | 3 aukšto planas su šildymo sistema, M 1:100 | |
1014-1A5p-PA(PM)-TDP-2110-ŠV.B-05 | 1 | 0 | 4 aukšto planas su šildymo sistema, M 1:100 | |
1014-1A5p-PA(PM)-TDP-2110-ŠV.B-06 | 1 | 0 | 5 aukšto planas su šildymo sistema, M 1:100 | |
1014-1A5p-PA(PM)-TDP-2110-ŠV.B-07 | 1 | 0 | Šildymo sistemos aksonometrinės schemos |
0 | 2021 | STATYBOS LEIDIMUI, (KONKURSUI) IR STATYBAI. | ||||
LAIDA | IŠLEIDIMO DATA | LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA) | ||||
KVAL. PATV. DOK. NR. | UAB „POLISTATYBA“ | STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | ||||
STATINIO NUMERIS IR PAVADINIMAS PASTATAS – DAUGIABUTIS GYVENAMASIS NAMAS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014) | ||||||
27833 | PV | X. XXXXXXXXXX | ||||
33244 | PDV | X. XXXXXX | ||||
DOKUMENTO PAVADINIMAS BYLOS DOKUMENTŲ SUDĖTIES ŽINIARAŠTIS | LAIDA | |||||
0 | ||||||
LT | STATYTOJAS IR (ARBA) UŽSAKOVAS UAB „ŠILALĖS ŠILUMOS TINKLAI“, MAIRONIO G. 20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 | DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-BSŽ | LAPAS | LAPŲ | ||
1 | 1 |
AIŠKINAMASIS RAŠTAS
1. Bendri duomenys
Daugiabučiam 5 aukštų gyvenamajam pastatui, esančiam Šilalėje, D. Xxxxxx x. 0, šildymo ir vėdinimo sistemos techninis darbo projektas atliktas vadovaujantis užduotimi projektavimui, statybiniais – architektūriniais brėžiniais, statybos normatyviniai dokumentais.
Normatyviniai, kiti dokumentai ir duomenys, kuriais vadovaujantis parengtas projektas:
- STR 2.09.02:2005 „Šildymas, vėdinimas ir oro kondicionavimas“;
- STR 2.01.01(3):1999 „Esminiai statinio reikalavimai. Higiena, sveikata, aplinkos apsauga“;
- STR 2.01.01(5):2008 „Esminis statinio reikalavimas. Apsauga nuo triukšmo“;
- STR 2.01.01(6):2008 „Energijos taupymas ir šilumos išsaugojimas“;
- STR 2.01.02:2016 „Pastatų energinio naudingumo projektavimas ir sertifikavimas“;
- STR 1.04.04:2017 „Statinio projektavimas, projekto ekspertizė“;
- STR 2.02.01:2004 „Gyvenameji pastatai“;
- RSN 156-94 „Statybinė klimatologija“;
- HN 42:2009 „Gyvenamųjų ir viešojo naudojimo pastatų mikroklimatas“;
- HN 33:2011 „Triukšmo ribiniai dydžiai gyvenamuosiuose ir visuomeninės paskirties pastatuose bei jų aplinkoje“;
- LST EN 12828:2012+A1:2014 „Pastatų šildymo sistemos. Vandeninių šildymo sistemų projektavimas“;
- LST EN 14336 „Pastatų šildymo sistemos. Vandeninių šildymo sistemų įrengimas ir priėmimas eksploatuoti“;
- LST EN 16798-1:2019 „Pastatų energinis naudingumas. Pastatų vėdinimas. 1 dalis. Pastatų energinio naudingumo projektavimo ir vertinimo vidaus aplinkos įvesties parametrai, susiję su patalpų oro kokybe, šilumine aplinka, apšvietimu ir akustika. M1-6 modulis“;
- Lietuvos Respublikos statybos įstatymas;
- Statybos produktų reglamentas - Europos Parlamento ir Tarybos Reglamentas (ES) Nr.305/2011;
- Šilumos tinklų ir šilumos vartojimo įrenginių priežiūros (eksploatacijos) taisyklės;
- Gaisrinės saugos pagrindiniai reikalavimai;
- Statybinių atliekų tvarkymo taisyklės;
- Biocidinių produktų autorizacijos taisyklės 2016m. vasario 24d. SAM ministro įsakymas Nr. V-289;
- Europos komisijos reglamentas (ES) Nr. 1254/2014;
- Gyvenamųjų pastatų gaisrinės saugos taisyklės.
Ši projekto dalis atitinka galiojančius projekto rengimo dokumentus ir esminius statinio reikalavimus.
Projektas parengtas naudojant Autodesk Autocad, Microsoft Excel, Microsoft Word, HySelect, Upoquick ir kitomis programomis.
1.1. Skaičiuoti lauko oro parametrai (RSN 156-94, 4.6 lentelė, parametrai B Šilalėje)
- Žiemą T=-21 °C, entalpija -19.6 kJ/kg (-4.7 kcal/kg);
- Šildymo sezono vidutinė lauko oro temperatūra – 0.5 °C;
- Šildymo sezono trukmė 203 paros;
1.2. Projektiniai vidaus oro parametrai
- Gyvenamosiose patalpose T= 20 °C (skaičiavimuose priimta +20 °C);
- San. mazguose T= 24 °C (skaičiavimuose priimta +24 °C);
- Koridoriuose, laiptinėse T= 16 °C (skaičiavimuose priimta +16 °C).
1.3. Atitvarų šilumos perdavimo koeficientai
- Sienos U=0.2∙κ, [W/(m2∙K)];
- Stogai, perdangos besiribojančios su išore U=0.16∙κ, [W/(m2∙K)];
- Grindys į rūsį U=0.50∙κ, [W/(m2∙K)];
- Durys U=1.6∙κ, [W/(m2∙K)];
- Langai ir kitos skaidrios atitvaros U=1.6∙κ, [W/(m2∙K)].
0 | 2021 | STATYBOS LEIDIMUI, (KONKURSUI) IR STATYBAI. | ||||
LAIDA | IŠLEIDIMO DATA | LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA) | ||||
KVAL. PATV. DOK. NR. | UAB „POLISTATYBA“ | STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | ||||
STATINIO NUMERIS IR PAVADINIMAS PASTATAS – DAUGIABUTIS GYVENAMASIS NAMAS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014) | ||||||
27833 | PV | X. XXXXXXXXXX | ||||
33244 | PDV | X. XXXXXX | ||||
DOKUMENTO PAVADINIMAS AIŠKINAMASIS RAŠTAS | LAIDA | |||||
0 | ||||||
LT | STATYTOJAS IR (ARBA) UŽSAKOVAS UAB „ŠILALĖS ŠILUMOS TINKLAI“, MAIRONIO G. 20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 | DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-AR | LAPAS | LAPŲ | ||
1 | 3 |
1.4. Duomenys apie šilumos nešėją
- Skaičiuojamoji temperatūra šildymo sistemoje 65/45 °C;
- Slėgio nuostoliai šildymo sistemoje 44.3 kPa;
- Darbinis slėgis 2.5 bar;
- Didžiausias eksploatacinis slėgis (Pmaks.) 3 bar;
- Darbinė temperatūra 65 °C;
- Didžiausia eksploatacinė temperatūra (Tmaks.) 75 °C;
- Šildymo sistemos tūris 1430 ltr;
- Šildymo sistemos cirkuliacinis debitas 6.45 m³/h.
1.5. Pagrindiniai rodikliai
- Šilumos poreikis prieš pastato modernizavimą 190.00 kW;
- Šilumos poreikis po pastato modernizavimo 147.19 kW;
- Projektinis metinis šilumos poreikis pastatui šildyti 334.50 MWh/metus.
2. Šildymas
Gyvenamojo pastato esami šildymo sistemos vamzdynai susidėvėję, surūdiję, viduje užkalkėję. Vamzdynų izoliacija susidėvėjusi, kai kur jos išvis nėra, dideli šilumos nuostoliai nuo vamzdynų į aplinką. Esama šildymo sistemos būklė neatitinka šiuo metu galiojančių norminių reglamentų, todėl ją nuspręsta keisti nauja. Esamų vamzdynų panaudoti nėra galimybės, todėl jie demontuojami kartu su susidėvėjusia izoliacija. Šildymo prietaisai – radiatoriai keičiami naujais (šoninio pajungimo).
Pastato pirmame aukšte, bute Nr. 32, yra įrengtos komercinės paskirties patalpos. Vadovaujantis šių patalpų savininko prašymu, Nr. 32-9 patalpoje radiatoriai numatyti prie sienų esančiose dekoratyvinėse dėžutėse.
Parengti patalpų šilumos nuostolių ir šildymo sistemų hidraulinio pasipriešinimo skaičiavimai, pagal kuriuos parinkti tinkamo dydžio šildymo prietaisai ir vamzdynai. Slėgio nuostoliai šildymo, šilumos tiekimo sistemos vamzdynuose neviršija 150 Pa/m. Pastato patalpų šilumos nuostoliai ir projektinės temperatūros pateiktos projekto planuose (nuostoliai ir temperatūros pateiktos tik toms patalpoms, kurios turi išorines atitvaras, nes vidinės patalpos neturi šilumos nuostolių).
Esama šildymo sistema keičiama į naują dvivamzdę šakotinę sistemą.
Šilumos šaltinis – modernizuojamas šilumos punktas (žr. ŠT projekto dalį). Pagrindinės magistralės iš šilumos punkto uždaromoji ir išleidimo armatūra pateikta šilumos tiekimo projekto dalyje.
Prie kiekvieno radiatoriaus montuojami termostatiniai vožtuvai srautams sureguliuoti. Prie radiatorių taip pat montuojami šilumos kiekio nuskaitymo davikliai-indikatoriai bei įrengiama reikalinga techninė ir programinė įranga duomenų nuskaitymui nuotoliniu būdu. Visų daliklių duomenys iš butų turi būti nuskaitomi vienu metu ir perduodami į šilumos punkte esančią duomenų sistemą ENCO ir interneto pagalba perduodami į duomenų centrą – skaičiavimui.
Šildymo sistemai sureguliuoti ant stovų rūsyje montuojami slėgio skirtumo reguliatoriai TA STAP kartu su balansiniais ventiliais TA STAD, kurie tarpusavyje sujungti impulsiniais vamzdeliais. STAD montuojami ant tiekiamo šilumnešio vamzdyno, STAP – ant grįžtamo.
Rūsyje, žemiausiose vamzdyno vietose montuojami vandens išleidimo ventiliai.
Visi šildymo sistemos vamzdynai - iš plieninių presuojamų vamzdžių. Magistraliniai vamzdynai ir stovai iki rūsio perdangos izoliuojami akmens vatos izoliacija. Šildymo sistemos magistraliniai vamzdynai vedžiojami rūsio aukšte, palubėje. Stovuose įrengiama uždaromoji, vandens išleidimo armatūra bei automatiniai balansiniai ventiliai.
Dalis šildymo stovų su uždaromąja armatūra yra rūsyje, individualiuose sandėliukuose. Pastato šildymo sistemą prižiūrinčios tarnybos atstovui laisvai patekti į šiuos sandėliukus nebus galimybės. Todėl patekimas turi būti organizuojamas iš anksto, suderinus su namo pirmininku ir gyventojais.
Po remonto darbų visa šildymo sistema (vamzdynai ir radiatoriai) turi būti praplaunama, atliekamas hidraulinis bei šiluminis bandymas, sureguliuojamas cirkuliacinio siurblio šilumos punkte darbo rėžimas.
Po pastato rekonstrukcijos bus pasiekta B energetinio naudingumo klasė.
Patalpų vidaus aplinkos kokybės kategorija IEQII.
3. Vėdinimas
Esama ventiliacijos būklė bloga: natūralaus vėdinimo kanalai užakę, vėdinimo grotelės kai kur sulūžusios, ventiliacijos sistema neatlieka savo funkcijos. Pertvarkomos esamos pastato vėdinimo sistemos: dezinfekuojami, išvalomi ir sandarinami esami natūralios ventiliacijos kanalai, keičiamos oro ištraukimo grotelės butuose, remontuojami vėdinimo kanalai virš stogo.
Gyvenamojo pastato buto patalpų oro kiekiai (STR 2.02.01:2004 "Gyvenamieji pastatai").
Lentelė 2. Gyvenamojo pastato buto patalpų oro kiekiai (STR 2.02.01:2004 „Gyvenamieji pastatai“)
Šalinamo oro kiekis, mt/h patalpai | Tiekiamo lauko oro kiekis, l/s 1 m2 grindų ploto | ||
Virtuvė | Vonia | WC | Gyvenamosios patalpos |
36 | 54 | 36 | 0.35 |
Lentelė 3. Oro apykaitos butuose
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-AR | LAPAS | LAPŲ | LAIDA |
2 | 3 | 0 |
Buto Nr. | Apykaita |
1,3,4,6,7,9,10,12,13,15,16,17,19,20,22,23,25,26,28,29 | 0.96 kart./val. |
2,5,8,11,14 | 1.47 kart./val. |
18,21,24,27,30 | 0.77 kart./val. |
31,33,35,37,39 | 0.79 kart./val. |
34,36,38,40 | 0.66 kart./val. |
32 | 0.59 kart./val. |
Į pastatą pritekančio oro minimalus kiekis – 5040 m³/h. Šilumos kiekis, reikalingas jam sušildyti – 71.3 kW.
Ištraukiamo oro norma yra didesnė nei tiekiamo oro. Priimama, kad iš kiekvieno buto WC traukiama 36 m³/h oro, vonios – 54 m³/h, virtuvės – 36 m³/h. Kompensacinis oras priteka per virtuvės ir kambarių langų orlaides (patalpų šilumos nuostoliai skaičiuoti, įvertinant skaičiuotinus ištraukiamo iš patalpos oro kiekius prie skaičiuotinos lauko oro temperatūros -21 °C) – jos turi būti sumontuotos atliekant renovaciją.
Būtina įvertinti esamą pastato rūsio vėdinimo būklę, turinčią atitikti reikalavimus nurodytus RSN 37-90 „Požeminių inžinerinių tinklų įvadų į pastatus ir įgilintų patalpų vėdinimo taisyklėse“ p.9.2.5. (dėl viso rūsio ir rūsyje įrengtų patalpų (sandėliukų) vėdinimo).
Pastato laikančiųjų konstrukcijų, inžinerinių sistemų tyrimų, matavimų, jų techninės būklės įvertinimo dokumentai, pastato
energinio audito ataskaita pateikiami projekto bendrojoje dalyje.
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-AR | LAPAS | LAPŲ | LAIDA |
3 | 3 | 0 |
TECHNINĖS SPECIFIKACIJOS
1. Šildymas
1.1. Armatūra
1.1.1. Vamzdynų uždaromoji armatūra
Sklendė, rutulinis čiaupas vandeniui, plieninis, bronzinis, prijungimas - movinis.
Turi atitikti šiuos standartus: LSTEN 12288:2010 „Pramoninės sklendės. Vario lydinio sklendės“, LSTEN 12266-1:2012
„Pramoninės sklendės. Metalinių sklendžių bandymai. 1 dalis. Slėginiai bandymai, bandymo procedūros ir priėmimo kriterijai.
Privalomieji reikalavimai“, LSTEN 13547:2014 „Pramoninės sklendės. Vario lydinio rutulinės sklendės“, LSTEN 13709:2010
„Pramoninės sklendės. Plieninės vožtuvinės ir uždaromosios bei atbulinės vožtuvinės sklendės“, LSTEN 1983:2013
„Pramoninės sklendės. Plieninės rutulinės sklendės“, LSTEN ISO 228-1:2003 „Neslėginio sandarumo vamzdžių jungčių sriegiai. 1 dalis. Matmenys, tolerancijos ir žymėjimas“, LSTEN 16722:2016 „Pramoninės sklendės. Sklendžių su srieginiais galais atstumai tarp galų ir tarp centro ir galo“, LSTEN 10226-2:2005 „Vamzdžių sriegiai, užtikrinantys sandūrų sandarumą. 2 dalis. Išoriniai ir vidiniai kūginiai sriegiai. Matmenys, leidžiamosios nuokrypos ir žymėjimas“.
Pmaks. – 3 bar, Tmaks. – 75 °C, DN15-50.
1.1.2. Automatiniai balansiniai ventiliai STAP (DN15-DN50) techninis aprašymas Naudojimas: šildymo sistemose.
Paskirtis: slėgio perkričio reguliavimas, slėgio perkričio nustatymas, matavimas, vandens nuleidimas (pagal pageidavimą), uždarymas.
Maksimalus slėgio perkritis: 250 kPa. Darbinė temperatūra: nuo -20 °C iki +75 °C.
Reguliavimo intervalas: 5-25 kPa (DN15-DN20).
Medžiagos:
- Vožtuvo korpusas ir vidinė dalis AMETAL (patentuotas žalvario lydinys, atsparus cinko korozijai).
- Sandarinimo žiedai: guma EPDM.
- Diafragma: guma EPDM.
- Spyruoklė: nerūdijantis plienas.
- Rankenėlė: poliamidas.
Matavimo antgaliai: vienas savaime užsisandarinantis matavimo antgalis.
Pmaks. – 3 bar, Tmaks. – 75 °C.
Kvs = 1.4 (DN15), Kvs = 3.1 (DN20)
Nustatomas slėgio perkrytis – 17 kPa.
STAD techninis aprašymas
Naudojimas: šildymo, šaldymo, vandens tiekimo sistemos.
Paskirtis: uždarymas, hidraulikos balansavimas, derinimas, vandens nuleidimas, debito reguliavimas, debito, slėgio kritimo, temperatūros matavimas.
Darbinė temperatūra: nuo -20 °C iki 75 °C.
Medžiagos:
- Vožtuvai pagaminti iš AMETAL (patentuotas žalvario lydinys, atsparaus cinko korozijai).
- Rankenėlė iš raudono nailono su apsauginiu gaubteliu. Matavimo antgaliai: du savaime užsisandarinantys matavimo antgaliai.
Vandens nuleidimas: vožtuvai su vandens nuleidimu prijungiami prie ½” arba ¾” žarnos.
Pmaks. – 3 bar, Tmaks. – 75 °C.
Kvs = 2.52 (DN15), Kvs = 5.70 (DN20).
0 | 2021 | STATYBOS LEIDIMUI, (KONKURSUI) IR STATYBAI. | ||||
LAIDA | IŠLEIDIMO DATA | LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA) | ||||
KVAL. PATV. DOK. NR. | UAB „POLISTATYBA“ | STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | ||||
STATINIO NUMERIS IR PAVADINIMAS PASTATAS – DAUGIABUTIS GYVENAMASIS NAMAS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014) | ||||||
27833 | PV | X. XXXXXXXXXX | ||||
33244 | PDV | X. XXXXXX | ||||
DOKUMENTO PAVADINIMAS TECHNINĖS SPECIFIKACIJOS | LAIDA | |||||
0 | ||||||
LT | STATYTOJAS IR (ARBA) UŽSAKOVAS UAB „ŠILALĖS ŠILUMOS TINKLAI“, MAIRONIO G. 20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 | DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-TS | LAPAS | LAPŲ | ||
1 | 9 |
1.1.3. Automatiniai nuorinimo vožtuvai
Statomi aukščiausiose vietose oro išleidimui iš vamzdynų. 3/4" srieginis prijungimas.
Pmaks. – 3 bar, Tmaks. – 75 °C, DN15.
1.1.4. Termostatinis ventilis ir termostatinė galva
Termostatinė galva TA K.
Skysčiu užpildytas termostatas.
Spaudimo jėga iki 1 bar.
Du išoriniai energijos ribotuvai ir du papildomi vidiniai energijos ribotuvai temperatūrų ribojimui.
Nustatymo ribos nuo 16 °C iki 28 °C. Nustatymo skalė nuo 1 iki 5 arba temperatūrinė, su pagrindiniais simboliais patogiai
eksploatacijai.
Histerezė 0,2 K. Slėgio skirtumo įtaka 0,3 K. Apsaugos nuo užšalimo funkcija.
Balta spalva RAL 9016. Pajungimo sriegis M30x1,5.
Termostatinis ventilis pagal LST EN 215:2019 „Termostatinės radiatorių sklendės. Reikalvimai ir bandymo metodai.“.
Termostatinis vožtuvas TA V-exact II
Termostatinis vožtuvas su 8 padėčių išankstiniais nustatymais srautų sureguliavimui. Vožtuvo padėčių nustatymai atliekami specialaus rakto pagalba.
Nustatymų skalė nuo 1 iki 8. Tiksliam srautų sureguliavimui galimi išankstiniai nustatymai tarpinėse padėtyse (viso 15 pozicijų).
Minimali darbinė temperatura: -10°C.
Dvigubas reguliavimo ašies sandarinimas.
Speciali konstrukcija užtikrinanti tylų veikimą (prie 30kPa apie 25dB(A)). Vožtuvo korpusas pagamintas liejimo būdu iš raudonosios bronzos.
Turi atitikti LST EN ISO 228-1:2003 „Neslėginio sandarumo vamzdžių jungčių sriegiai. 1 dalis. Matmenys, tolerancijos ir žymėjimas“
Pmaks. – 3 bar, Tmaks. – 75 °C.
1.1.5. Šilumos skaitiklis
Šilumos skaitiklis skirtas matuoti sunaudotam šiluminės energijos kiekiui. Šilumos skaitikliai numatomi kartu su filtru ir uždaromaisiais ventiliais.
Funkcijos:
- Šilumos energijos sunaudojimo registravimas remiantis pratekėjimo debito ir temperatūrų skirtumo matavimais;
- Suminių reikšmių saugojimas pasirinktai atskaitos dienai;
- Sunaudojimo dydžių rodymas;
- Pagrindinių vartojimo parametrų rodymas;
- Savikontrolė su gedimų atpažinimu;
- Duomenų perdavimas į pastato įvado šilumos punkto centrinę duomenų surinkimo sistemą per nuotolinį radio ryšį. Šilumos skaitiklis susideda iš:
- Šilumos skaičiuotuvo;
- Temperatūros jutiklių;
- Debitomačio.
Reikalavimai šilumos skaitikliams:
- Temperatūros matavimo riba 0 °C ÷ +120°C;
- Temperatūros paklaida parodymuose ±0.3 °C;
- Skaitiklis ir jungiamosios detalės turi išlaikyti 10 bar slėgį;
- Maitinamas ličio baterija;
- Šilumos skaitikliai turi būti įrengiami paduodamoje šildymo sistemos linijoje;
- Prieš skaitiklį turi būti įrengtas filtras;
- Prieš ir po skaitiklio turi būti įrengti uždaromieji ventiliai;
- Pagal gamintojo reikalavimus turi būti išlaikyti mažiausi tiesių ruožų ilgiai prieš ir po srauto jutiklio;
- Šilumos skaitikliai privalo turėti galiojantį matavimo priemonės tipo tvirtinimo Lietuvoje ar vienoje iš Europos Sąjungos šalių pažymėjimą (sertifikatą);
- Šilumos skaitikliai turi atitikti 2 tikslumo klasei keliamus reikalavimus pagal LST EN 1434;
- Visi vamzdynai iki ir už skaitiklio turi būti padengti šilumine izoliacija. Pmaks. – 3 bar, Tmaks. – 75 °C.
Turi atitikti: LST EN 1434-1:2016 „Šilumos skaitikliai. 1 dalis. Bendrieji reikalavimai“, LST EN 1434-3:2016 „Šilumos skaitikliai. 3 dalis. Duomenų mainai ir sąsajos“, LST EN 1434-2:2016 „Šilumos skaitikliai. 2 dalis. Konstrukcijos reikalavimai“.
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-TS | LAPAS | LAPŲ | LAIDA |
2 | 9 | 0 |
1.2. Įrenginiai
1.2.1. Plieninis radiatorius (šoninio pajungimo)
Radiatoriai turi būti pagaminti iš šaltai valcuoto lakštinio plieno gamykloje, kurios technologija ir produkcija yra sertifikuotos pagal LST EN 442-1 „Radiatoriai ir konvektoriai. 1 dalis. Techninės charakteristikos ir reikalavimai“ kokybės reikalavimus. Radiatorių paviršiaus šilumos kiekis turi būti atestuotas pagal galiojančių normų reikalavimus. Radiatorių paviršius turi būti padengtas ir nudažytas. Jie gali būti padengti pagal užsakovo pageidavimą (tikslinti pas užsakovą) spalva. Švariose patalpose montuojami lygiais paviršiais, lengvai valomi, higieninio išpildymo radiatoriai. Radiatoriai turi būti įvynioti į polietilenines plėveles ir supakuoti į kartonines dėžes, papildomai apsaugant kampus ir groteles pakrovimo bei iškrovimo operacijų metu.Radiatoriai turi būti sukomplektuoti kartu su tvirtinamosiomis detalėmis ir laikikliais. Radiatoriai tvirtinami dviejų kronšteinų pagalba prie sienos arba specialiai komplektuojamų detalių (kojų) pagalba statomi ant grindų. Radiatoriai komplektuojami su termostatiniu ventiliu, nuorinimo vožtuvu ir drenažiniu ventiliu. Iš apačios jungiami radiatoriai turi būti su dvivamzdės šildymo sistemos pajungiamaisiais atvamzdžiais. Radiatoriai turi būti montuojami vadovaujantis gamintojo instrukcijomis. Prie sienų tvirtinami sieniniais laikikliais. Prie įstiklinimų iki žemės montuojami ant tvirtinamųjų stovų. Prie politerminių vamzdžių jungiami su jungiamosiomis tarpinėmis detalėmis ir adapteriais.
tw=65/45/20 ºC – kambariams; tw=65/45/16 ºC – laiptinėms. Pmaks. – 3 bar, Tmaks. – 75 °C.
1.2.2. Šilumos daliklis
Elektroninis šilumos daliklis naudojamas mokesčių už šildymą apskaičiavimui netiesioginio energijos matavimo principu.
Funkcijos:
- Eksploatacijos pradžios datos registravimas;
- Duomenu registracija kas mėnesi išsaugant paskutinius 18 mėnesiu duomenis;
- Programuojamas displėjaus persijungimo tvarka;
- Data ir laikas;
- Suvartotos šilumos vertė santykiniais vienetais;
- Parametrizavimo koeficientu reikšmės;
- Radiatoriaus ir aplinkos temperatura;
- Maksimali suvartotos šilumos vertė;
- Klaidu kodai;
- Manipuliavimo (uždengimo izoliuojant nuo aplinkos) fiksavimas – paskutinė manipuliavimo data ir bendras laikas;
- Baterijos veikimo laikas ne mažiau 10m;
- Radio dažnis 433.82 MHz.
Turi atitikti LST EN 834:2013 „Šilumos sąnaudų skirstytuvai patalpų šildymo radiatorių sunaudotai šilumai nustatyti.
Elektra maitinami prietaisai“.
1.2.3. Radijo duomenų kaupiklis
Prietaisas skirtas nuotoliniam duomenų nuskaitymui iš skaitiklių su radijo ryšio sąsaja.
Duomenų koncentratorius Supercom 646 yra nuotolinės duomenų nuskaitymos sistemos komponentas, nuolatinai irengtas pastate, radio prietaisu atmintyje saugomu duomenų nuskaitymui.
Koncentratorius aprūpintas 433 MHz radio plokšte ir vidine antena. Atmintyje saugomi konfiguraciniai parametrai, nuskaitomų prietaisų sąrašas, paskutinio nuskaitymo duomenys. Po kiekvieno nuskaitymo seni duomenys pakeičiami naujais. Jei nuskaitant iškilo problemų, seni duomenys neištrinami. Atmintyje visada yra paskutinio korektiško nuskaitymo duomenys. Koncentratorius gali nuskaityti ir saugoti iki 1000 prietaisų rodmenų. Nuskaityti galima užprogramuotu iš anksto laiku arba bet kada jei reikia patikrinti aktualius parodymus. Nuskaitymas gali buti atliktas priklausomai nuo pasirinktos koncentratoriaus konfiguracijos GSM/GPRS, MBus, USB, RS-232 interfeisais. Duomenys išsaugomi xml arba xls formatu ir yra paruošti apskaitai. Veikimo spindulys – ~30 m (3-5 aukštai).
Turi atitikti LST EN 135757-4:2013 “Skaitiklių ryšio ir jų nuotolinio nuskaitymo sistemos. 4 dalis. Belaidis skaitiklių rodmenų skaitymas (skaitiklių rodmenų skaitymas artimojo nuotolio įtaisu SRD juostoje)”; LST EN 60950-1:2006/A2:2013 “Informacijos technologijos įranga. Sauga. 1 dalis. Bendrieji reikalavimai”; LST EN 300 220-1 V1.3.1, EN 300 220-3 V1.1.1 – “Elektromagnetinio suderinamumo ir radijo dažnio spektro dalykai. Mažojo nuotolio įranga. Radijo ryšių įranga, kuri naudojama nuo 432 MHz iki 870 MHz dažnių juostoje ir kurios galia neviršija 500mW. 3 dalis”.
1.2.4 Duomenų transformatorius
Prietaisas skirtas nuotoliniam skaitiklių duomenų nuskaitymui, jų kaupimui atmintyje, analizei bei rezultatų perdavimui į sistemą. Vidiniame archyve kaupiami parametrai ir apskaitos prietaisų duomenys. Pranešimų generavimas avarijos atveju.
Turi atitikti LST EN 135757-4:2013 “Skaitiklių ryšio ir jų nuotolinio nuskaitymo sistemos. 4 dalis. Belaidis skaitiklių rodmenų skaitymas (skaitiklių rodmenų skaitymas artimojo nuotolio įtaisu SRD juostoje)”; LST EN 60950-1:2006/A2:2013 “Informacijos technologijos įranga. Sauga. 1 dalis. Bendrieji reikalavimai”; LSTEN 300 220-1 V1.3.1, EN 300 220-3 V1.1.1 – “Elektromagnetinio suderinamumo ir radijo dažnio spektro dalykai. Mažojo nuotolio įranga. Radijo ryšių įranga, kuri naudojama nuo 432 MHz iki 870 MHz dažnių juostoje ir kurios galia neviršija 500mW. 3 dalis”.
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-TS | LAPAS | LAPŲ | LAIDA |
3 | 9 | 0 |
1.3. Vamzdžiai
1.3.1. Plieniniai cinkuoti vamzdžiai
Prestabo naudojimas
Prestabo sistema skirta pramoninėms sistemoms ir šildymo sistemoms ir netinkama naudoti vandens tiekimui. Todėl vamzdžiai ir jungtys yra pažymėtos raudonu tašku „ne geriamo vandens sistemoms“. Prestabo elementus galima naudoti tik su tai sistemai numatytomis detalėmis. Presavimo fitingai turi SC-Contur apsaugą ir neužpresuoti yra nesandarūs.
Techniniai duomenys
Nelegiruotas plienas, medžiagos kodas 1.0308 pagal LST EN 10305-3 „Tikslieji plieniniai vamzdžiai. Techninės tiekimo sąlygos. 3 dalis. Šaltai kalibruoti suvirintieji vamzdžiai“, su išoriniu cinkavimu galvaniniu būdu.
Tiekiami vamzdžiai turi išorinį cinko sluoksnį nuo 8 iki 15 µm.
Vamzdžiai tiekiami 6 m štagomis, išbandyti gamykloje ir sumarkiruoti: 15/18/22/28/35/42/54/64/76.1/88.9/108.0.
Panaudojimas
- Saulės kolektorių sistemos;
- Kondicionavimo sistemos;
- Šildymo sistemos;
- Suspausto oro sistemos;
- Vakuuminės sistemos, technologinių dujų sistemos (pagal užklausimą).
Prestabo vamzdis | ||||
Skermuo ir sienelės storis, dxs | Vandens kiekis 1m vamzdžio (ltr/m) | 1m vamzdžio svoris (kg/m) | 6m vamzdžio svoris (kg) | Pozicijos nr. |
15 x 1,0 | 0,13 | 0,41 | 2,5 | 559441 |
18 x 1,2 | 0,19 | 0,50 | 3,0 | 559458 |
22 x 1,5 | 0,28 | 0,80 | 4,8 | 559465 |
28 x 1,5 | 0,49 | 1,00 | 6,0 | 559472 |
35 x 1,5 | 0,80 | 1,20 | 7,2 | 559496 |
42 x 1,5 | 1,19 | 1,50 | 9,0 | 559489 |
54 x 1,5 | 2,04 | 2,00 | 12,0 | 559502 |
64 x 2,0 | 2.83 | 3,06 | 18,0 | 598327 |
Tiekėjas privalo pateikti numatomų panaudoti vamzdžių technines sąlygas, kokybę liudijančius dokumentus, kuriuose turi būti atžymos apie atliktus bandymus ir rezultatus, techninės priežiūros vadovui patvirtinti. Vamzdžių galai turi būti nupjauti statmenai, nuo jų nuvalytos atplaišos ir uždengti aklėmis. Vamzdžiai turi būti žymimi, pagal susitarimą užsakyme, dažytu ar štampuotu ženklu. Fasoninės dalys, numatomos naudoti montavimui, turi būti pagamintos pramoniniu būdu iš tos pačios plieno markės kaip ir pagrindiniai vamzdžiai. Fasoninės dalys turi būti padengtos gruntuote.
1.3.2. Plieninių vamzdžių įvorės
Vamzdžių įvorės turi būti ten, kur vamzdžiai kerta sienas, pertvaras ar perdangas.
Įvorės turi būti pagamintos iš tos pačios medžiagos kaip ir vamzdis. Įvorės vidinis skersmuo turi būti ne mažiau kaip 15 mm didesnis už vamzdžio išorinį skersmenį, jeigu nenurodyta kitaip.
Kur vamzdžiai praeina pro konstrukcines grindis ir ugniasienes, turi būti naudojamos specialios ugnies nepraleidžiančios tarpinės, kurios užtikrintų dviejų valandų atsparumą ugniai.
Tarpelis tarp vamzdžio ir įvorės turi būti užsandarintas elastinga mastika.
Turi atitikti LST EN 1366-3:2009 „Inžinerinių tinklų įrenginių atsparumo ugniai bandymai. 3 dalis. Angų sandarinimo priemonės“, „Gaisrinės saugos pagrindiniai reikalavimai“ p. 58-59, 77.
1.3.3. Plieninių vamzdžių temperatūrinis pailgėjimas
Specialūs plėtimosi kompensatoriai nereikalingi, jeigu:
- Vamzdis atremtas ir pritvirtintas inkarinėmis tvirtinimo detalėmis ne rečiau kaip kas 6 m;
- Vamzdis pravestas apvalkale, kuriame yra pakankamas plėtimuisi tarpelis tarp vandens vamzdžio ir apvalkalo;
- Ilgi vamzdžiai pakloti ant lentynų.
Tačiau instaliacijose, kuriose leidžiamas šiluminis plėtimasis, o vamzdžiai turi išlikti tiesūs, reikia naudoti plėtimosi
kompensatorius.
Lankstus kronšteinas turi būti pakankamai ilgas, siekiant išvengti pažeidimų, atraminius laikiklius reikia išdėstyti pakankamai toli nuo sienos, kad jie galėtų plėstis išilgine kryptimi dėl šilumos poveikio. Formulės naudojamos lankstaus kronšteino minimalaus ilgio apskaičiavimui.
- Temperatūrinis pailgėjimas turi būti kompensuojamas natūraliais vamzdynų pasislinkimais ašine kryptimi;
- Vamzdynų plėtimuisi kompensuoti turi būti montuojami linziniai arba „U“ formos kompensatoriai;
- Vamzdynai turi būti tvirtinami ant nejudamų atramų su apkrovas išlaikančiomis apkabomis. Ašinio kompensatoriaus medžiaga – plienas AISI 321.
Pmaks. – 3 bar, Tmaks. – 75 °C. Ašinis poslinkis – 30 mm.
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-TS | LAPAS | LAPŲ | LAIDA |
4 | 9 | 0 |
1.3.4. Vamzdynų šiluminis izoliavimas
Šilumine izoliacija, kurios pagrindas akmens vatos kevalai, išorėje laminuoti aliuminio folija. Izoliacija skirta montavimui šildymo, karšto vandens, pramoninio išpildymo ir pan. sistemose.
Izoliuojami vamzdynai – rūsyje esančios šildymo sistemos magistralės, rūsyje esantys stovai iki rūsio perdangos. Pagrindinės techninės izoliacijos charakteristikos ir rodikliai pateikiama gamintojų Eksploatacinių Savybių Deklaracijose.
- Izoliuojamo vamzdžio skersmuo: nuo d15 iki d64.
- Darbinė temperatūra: iki +250 °C.
- Eksploatacinis parametras I – 0.705 (0.8*(55-5)*204*24*3600).
- Izoliacijos klasė – 4.
- Skaičiuotinas vamzdinės izoliacijos storis:
a) D15 vamzdžiui – 20 mm (projekte priimta 20 mm)
b) D18 vamzdžiui – 20 mm (projekte priimta 20 mm)
c) D22 vamzdžiui – 25 mm (projekte priimta 30 mm)
d) D28 vamzdžiui – 30 mm (projekte priimta 30 mm)
e) D35 vamzdžiui – 35 mm (projekte priimta 40 mm)
f) D42 vamzdžiui – 35 mm (projekte priimta 40 mm)
g) D54 vamzdžiui – 40 mm (projekte priimta 40 mm)
h) D64 vamzdžiui – 50 mm (projekte priimta 50 mm)
- Tankis: 80 - 100 kg/m3.
- Šilumos laidumo koeficientas λ40 ≤ 0.037 W/mK.
- Laidumas vandens garams: MV1.
- Reakcija į ugnį pagal LST EN 13501-1:2007+A1:2010/P:2012 “Statybos gaminių ir pastato elementų klasifikavimas pagal atsparumą ugniai. 1 dalis. Klasifikavimas pagal atsako į ugnį bandymų duomenis” – A2L-s1, d0.
Montuojant techninę izoliaciją vadovautis gamintojo pateikiamomis instrukcijomis ir reikalavimais
Montuojant izoliaciją privaloma naudoti visus tvirtinimui būtinus priedus (tvirtinančias detales, juostas, diržus, įvairius klijus, sandarinimo juostas ir t.t.).
Šiluminė izoliacija ir jos montavimas atsižvelgiant į „Įrenginių ir šilumos perdavimo tinklų šilumos izoliacijos įrengimo
taisykles“, LST EN 14336:2004, LR Statybos įstatymo 8 straipsnis. Normatyvinių statybos techninių dokumentų sistema.
1.3.5. Vamzdžių atramos ir kreipiamosios detalės
Atramų apkabos turi būti įtvirtintos tinkamu būdu, kad laikytų apkrovą. Visos atramos jokiu būdu negali pažeisti pastato konstrukcijų.
Nejudamos atramos parinktos prie T1-65 °C ir ΔT-40 K:
- NA 1 (d22) ašinės jėgos (F/H ne daugiau 500 N);
- NA 1 (d28) ašinės jėgos (F/H ne daugiau 600 N);
- NA 1 (d35) ašinės jėgos (F/H ne daugiau 700 N);
- NA 1 (d42) ašinės jėgos (F/H ne daugiau 800 N);
1.3.7. Stovų šiluminis izoliavimas
Šildymo sistemos stovai nuo rūsio perdangos izoliuojami 13 mm pūsto polietileno izoliacija.
Pagrindinės techninės izoliacijos charakteristikos ir rodikliai pateikiama gamintojų Eksploatacinių Savybių Deklaracijose.
- Izoliuojamo vamzdžio skersmuo: nuo d15 iki d54.
- Darbinė temperatūra: iki +65 °C.
- Vamzdinės izoliacijos storis – 13 mm.
- Tankis: 30 - 35 kg/m3.
- Šilumos laidumo koeficientas λ ≤ 0.039 W/mK.
- Vandens įsigėrimas 1.4 %.
Montuojant techninę izoliaciją vadovautis gamintojo pateikiamomis instrukcijomis ir reikalavimais
Montuojant izoliaciją privaloma naudoti visus tvirtinimui būtinus priedus (tvirtinančias detales, juostas, diržus, įvairius
xxxxxx, sandarinimo juostas ir t.t.).
1.4. Darbai
1.4.1. Šildymo sistemos montavimas
Visi horizontalūs vamzdynai tiesiami su minimaliu nuolydžiu 0.002 m/m. Šildymo sistemos atšakoms ir stovams reikia statyti uždaromąją ir reguliuojamąją armatūrą, kiek jos reikia sistemai paleisti, reguliuoti, patogiai ir saugiai eksploatuoti.
Vamzdynui kertant statybines konstrukcijas (sienas, pertvaras, perdenginius), jis montuojamas metaliniame futliare, kurio galai sutampa su konstrukcijos storiu. Futliaro vidinis skersmuo turi būti 10-20 mm didesnis už vamzdžio išorinį skersmenį, o tarpas tarp jų užtaisytas nedegia medžiaga, netrukdančia vamzdžio linijiniam plėtimuisi.
Armatūrai tvirtinimo atramos įrengiamos atskirai. Armatūra ant horizontalių vamzdžių įrengiama taip, kad suklys būtų nukreiptas vertikaliai į viršų arba nuožulniai vamzdžio viršutinio pusapskritimio ribose ant vertikalių vamzdynų. Prieš montavimą visa armatūra turi būti išbandyta papildomai.
Vamzdžiai jungiami ir posūkiai daromi naudojant fasonines dalis. Išardomieji vamzdynų sujungimai daromi jungimo su armatūra vietose ir tose vietose, kur būtina pagal montavimo ir eksploatavimo sąlygas. Statybinėse konstrukcijose vamzdynai neturi turėti išardomųjų sujungimų.
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-TS | LAPAS | LAPŲ | LAIDA |
5 | 9 | 0 |
Sistemų vertikalūs vamzdynai neturi nukrypti nuo vertikalės daugiau negu 2mm vienam vamzdžio metrui. Atstumai tarp vamzdžio ir sienos tokie:
- vamzdžiams iki 32 mm skersmens - 35 mm;
- 40 mm ir 50 mm skersmens - 50 mm su paklaida ±5 mm.
Srieginiai sujungimai išdėstomi tose vietose, kur yra priėjimas aptarnavimui. Tarpas tarp stovo armatūros bei magistralinio vamzdžio ne didesnis už 120 mm.
Šildymo prietaisai į objektą atvežami sukomplektuoti su armatūra, tvirtinimo detalėmis ir išbandyti hidrauliškai. Radiatoriai montuojami, išlaikant vertikalę ir horizontalę. Patalpos ribose prietaisai montuojami vienodame aukštyje, ne mažiau nei 60mm nuo grindų, 50 mm nuo palangės ir 25 mm nuo sienos.
Radiatoriai prie vamzdynų jungiami srieginiu sujungimu. Šildymo sistemas montuoti, vadovaujantis statybos normomis ir saugaus darbo norminiais dokumentais bei priešgaisrinėmis normomis.
1.4.2. Plieninių vamzdžių montavimas
Vamzdynai tvirtinami pakabinimo mazgų ir atramų pagalba. Galima naudoti specialios konstrukcijos grupinio pakabinimo mazgus. Jie turi būti tokio dydžio, kad atstumas tarp vamzdžių leistų juos izoliuoti. Šilumnešio vamzdynų atramos apriboja vamzdyno judėjimo galimybę tik ašine kryptimi. Horizontalūs vamzdynai turi būti tvirtinami reguliuojamų pakabų pagalba. Leistini atstumai tarp atramų:
- 2.0 m, kai nominalus diametras yra iki 32 mm;
- 2.5 m, kai nominalus diametras yra iki 40 mm;
- 3.0 m, kai nominalus diametras yra 50 mm;
- 4.0 m, kai nominalus diametras yra 65…100 mm;
- 4.5 m, kai nominalus diametras yra 100…150 mm;
- 4.5 m, kai nominalus diametras yra 150…250 mm.
Vamzdžiai prie visų įrenginių ir valdymo vožtuvų turi būti tvirtinami taip, kad būtų išvengta įtempimų ar iškraipymų pajungtoje įrangoje ir valdymo vožtuvuose. Vamzdžiai turi būti tvirtinami taip, kad įrangą, vožtuvus ir priedus būtų galima nuimti mažiausiai juos išardant ir, kad nuėmus minėtus prietaisus, nereikėtų papildomų atramų. Visi vertikalūs vamzdžiai turi būti tvirtinami taip, kad būtų užkirstas kelias išlinkimams arba svyravimams. Vertikalūs vamzdžiai turi turėti stiprius kaltos geležies arba plieno spaustukus, gerai užvertus ant vamzdžių, su prailginimais, įsiremiančiais į pastato konstrukcijas. Norint išvengti per didelio vamzdžių ir atšakų įtempimo, vamzdžiai turi būti įtvirtinti atsižvelgiant į linijinius pailgėjimus. Ankeriai turi būti visiškai atskirti nuo pakabinimo mazgų ir turi būti tvirtai kaltos ar suvirintos konstrukcijos.
- Srieginės jungties sandarinimui naudojamos linų pakulos mirkytos surike arba kitos karščiui atsparios medžiagos;
- Flanšiniai sujungimai sandarinami karščiui atspariomis tarpinėmis. Gumines ir asbestcementines medžiagas naudoti draudžiama;
- Šilumos tiekimo vamzdynai turi būti montuojami su ne mažesniu kaip 0.002 m/m nuolydžiu, tvirtinant prie statybinių konstrukcijų. Įrengimai ir vamzdynai turi būti tvirtinami taip, kad nebūtų pažeista pastato konstrukcija;
- Montuojant vamzdynus šilumos punktuose turi būti įrengtos visos įdėtinės detalės termometrų, manometrų bei jutiklių pastatymui;
- Žemiausiose vamzdynų vietose turi būti įrengiami ištuštinimo atvamzdžiai, o aukščiausiose vietose oro pašalinimo atvamzdžiai. Atvamzdžiai įrengiami patogiame aptarnauti aukštyje;
- Prieš pradedant montuoti įrenginius (šilumos apskaitos prietaisus, siurblius, šilumokaičius ir pan.), vamzdynų sistema turi būti praplauta siekiant apsaugoti įrenginius nuo teršalų;
- Vamzdynams kertant statybines konstrukcijas, jose turi būti įrengtos įvorės;
- Baigus montavimo darbus, turi būti atliktas sistemų praplovimas ir hidraulinis išbandymas;
- Visi atlikti darbai turi būti įforminti atitinkamuose aktuose;
- Šilumos tiekimas sistemų montavimo metu neturi būti atliekamas.
1.4.3. Plieninių vamzdžių tvirtinimas
Vamzdynai tvirtinami pakabinimo mazgų ir atramų pagalba. Galima naudoti specialios konstrukcijos grupinio kabinimo mazgus. Jų dydis turi būti toks, kad vamzdžius galima būti izoliuoti.
Horizontalūs vamzdynai tvirtinami reguliuojamų pakabų pagalba. Pakabos turi būti tokio dydžio, kad vamzdynus galima
būtų izoliuoti.
Atstumai tarp vamzdžio ir sienos: - vamzdžiams iki 32 mm skersmens – 35 mm; - 40 ir 50 mm skersmens vamzdžiams – 50 mm su paklaida ± 5 mm; - srieginiai sujungimai išdėstyti tose vietose, kur yra priėjimas aptarnavimui.
Vamzdžiai prie visų įrenginių ir valdymo vožtuvų turi būti paremti, kad būtų išvengta įtempimų ar iškraipymų prijungtoje įrangoje, vožtuvuose ir valdymo vožtuvuose. Vamzdžiai turi būti paremti, kad įrangą, vožtuvus ir priedus galima būtų nuimti mažiausiai juos išardant, o nuėmus įrangą nereiktų papildomų atramų.
Visi vertikalūs vamzdžiai turi būti pritvirtinti taip, kad vamzdis neišlinktų nuo savo svorio ir nejudėtų nuo tekančio vandens srauto ar vibracijos.
1.4.4. Ženklinimas
Ant vamzdynų paviršiaus klijuojami lipdukai - skiriamieji spalviniai ženklai pagal vamzdynų paskirtį, rodyklės rodančios tekėjimo kryptį. Žymėjimas turi būti atliktas vadovaujantis Lietuvoje galiojančiomis normomis.
Visi balansiniai ventiliai ir pan. turi būti aiškiai pažymėti. Ši ženklinimo sistema bus taikoma techninio aptarnavimo instrukcijose, statybos brėžiniuose bei kituose priėmimui naudotinuose dokumentuose. Prieš pradedant ženklinimą, visų ženklinimo tipų pavyzdžiai turi būti suderinti su užsakovu.
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-TS | LAPAS | LAPŲ | LAIDA |
6 | 9 | 0 |
Visi žymėjimai atliekami lietuvių kalba. Vamzdynų izoliuotieji paviršiai turi būti nužymėti žiedinėmis juostelėmis bei šilumnešio tekėjimo krypties rodyklėmis:
- Kai vardinis vamzdžio skersmuo mažesnis nei DN150, žiedinio ženklo juostos plotis turi būti 50 mm; rodyklės ženklinimo juosta ne trumpesnė kaip 150 mm;
- Tiekiamas į šildymo, šilumos tiekimo sistemą šilumnešis vanduo ženklinamas geltona rodykle žaliame lauke su vienu geltonu žiedu;
- Grąžinamas iš šildymo, šilumos tiekimo sistemos šilumnešis vanduo ženklinamas rudos spalvos rodykle žaliame lauke su vienu rudu žiedu.
1.4.5. Hidraulinis praplovimas ir išbandymas
Vandeninės sistemos
Hidraulinis vamzdynų praplovimas ir išbandymas atliekamas atlikus visus suvirinimo darbus ir sumontavus tvirtinimo detales. Vanduo hidrauliniam sistemų praplovimui ir išbandymui turi būti imamas iš statybos aikštelėje esančių vandentiekio sistemų, po vandens kiekio apskaitos.
Bandymas atliekamas kiekvienai sistemai atskirai.
Xxxxxxx xxxxxx – 1.3 * Pdarbinis (3.9 bar). Kontrolinio slėgio paklaida – 0.2 bar.
Bandomasis slėgis palaikomas 2 val., kol bus patikrinta ar nėra nuotėkio arba vamzdyno deformacijų.
Sistema užpildoma ne didesniu nei statinis slėgis, nuorinama, tikrinama ar nėra pratekėjimų, o tik po to atliekmas
hidraulinis bandymas.
Hidraulinis bandymas turi būti atliekamas pagal LST EN 14336:2004 „Pastatų šildymo sistemos. Vandeninių šildymo sistemų įrengimas ir priėmimas eksploatuoti“ reikalavimus.
Šildymo sietemos išbandymas, esant teigiamai išorės temperatūrai, atliekamas tinklo vandeniu, kurio temperatūra ne žemesnė kaip 10 °C.
Bandymo metu reikia naudoti spyruoklinius manometrus, kurių tikslumo klasė ne mažesnė kaip 1,5, skersmuo ne mažesnis kaip 160 mm, padalos vertė 0,01 MPa ir bandomojo slėgio dydis būtų rodomas manometro skalės antrame trečdalyje.
1.4.6. Šildymo sistemų šiluminis išbandymas
Įjungiant sumontuotą, suremontuotą ar rekonstruotą šildymo sistemą, būtina atlikti šiluminį bandymą. Šiluminio bandymo metu šilumnešio temperatūra turi atitikti nustatytąją temperatūros grafike pagal lauko oro temperatūrą. Šiluminio bandymo metu sistema derinama ir reguliuojama teisės aktų nustatyta tvarka. Bandymo rezultatai įforminami aktu.
Jei šildymo sistemos šiluminio bandymo nėra galimybių atlikti nešildymo sezono metu, tai reikia atlikti prasidėjus šildymo
sezonui.
1.4.7. Paleidimo – derinimo darbai
Paleidimo – derinimo darbus atlieka rangovas. Šiuos darbus gali atlikti specialistai turintys reikiamą kvalifikaciją ir leidimą šios rūšies darbams atlikti. Paleidimo – derinimo darbams surašomas priėmimo aktas ir patvirtinamas techninės priežiūros vadovo.
1.4.8. Šildymo sistemos priėmimas eksploatuoti
Šildymo sistemos priimamos eksploatuoti pagal LST EN 14336:2004 „Pastatų šildymo sistemos. Vandeninių šildymo sistemų įrengimas ir priėmimas eksploatuoti“.
Tikslas – perduoti rašytines instrukcijas apie šildymo sistemos eksploataciją, priežiūrą ir naudojimą, duoti instrukcijas vartotojui/operatoriui ir patvirtinti eksploatacinių reikalavimų atitiktį.
Eksploatacijos, priežiūros ir naudojimo instrukcijos turi būti parengtos pagal specifinius šildymo sistemos reikalavimus.
Instrukcijos turi atitikti LST EN 12170:2003 „Pastatų šildymo sistemos. Eksploatavimo, techninės priežiūros ir naudojimo dokumentų rengimo procedūra. Šildymo sistemos, kurioms reikia kvalifikuoto operatoriaus“ ir LST EN 12171:2003 „Pastatų šildymo sistemos. Eksploatavimo, techninės priežiūros ir naudojimo dokumentų rengimo procedūra. Šildymo sistemos, kurioms nereikia kvalifikuoto operatoriaus“
Šildymo sistemos operatorius turi būti instruktuotas tinkamai eksploatuoti šildymo sistemą.
Šildymo sistemos perdavimo dokumentaciją turi sudaryti visa informacija, reikalinga sistemą tinkamai eksploatuoti ir prižiūrėti. Ją turi sudaryti tokie dokumentai:
- Šildymo sistemos eksploatacijos, priežiūros ir naudojimo instrukcijos;
- Valdymo ir elektrinės schemos, kurios turi atitikti LST EN 61082-1:2015 „Elektrotechnikoje naudojamų dokumentų rengimas. 1 dalis. Taisyklės“;
- Hidraulinio ir šiluminio išbandymų aktai;
- Balansavimo protokolai.
1.4.9. Dokumentacija
Xxxxxxxx užsakovui turi pateikti visą reikalingą dokumentaciją pagal Lietuvoje galiojančius normatyvinius aktus ir dokumentus. Visa dokumentacija, išskyrus brėžinius ir originalius įrangos gamintojo pasus, turi būti A4 formato ir įrišta į segtuvą. Egzempliorių skaičius paruošiamas pagal susitarimą su užsakovu.
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-TS | LAPAS | LAPŲ | LAIDA |
7 | 9 | 0 |
1.4.10. Demontavimas, statybinių atliekų tvarkymas ir utilizavimas
Susidėvėję šildymo sistemos vamzdynai rūsyje demontuojami kartu su visa izoliacija, nejudamomis atramomis, laikikliais.
Taip pat demontuojami trieigiai vožtuvai prie radiatorių. Vietoje jų dedami vamzdyno intarpai.
Rangovas privalo vesti susidariusių ir perduotų tvarkyti statybinių atliekų apskaitą, nurodyti jų kiekį, kurio kontroliuojamoje teritorijoje vykdoma statinio statyba, rekonstravimas, remontas ar griovimas. Taip pat rangovas turi vykdyti kitus reikalavimus, nurodytus „Statybinių atliekų tvarkymo taisyklėse“ patvirtintose 2006 12 29 LR aplinkos ministro įsakymu Nr.D1-637 bei vadovautis kitais atliekų tvarkymą reglamentuojančiais teisės aktais (pvz.: LR atliekų tvarkymo įstatymu).
Rangovas privalo pašalinti statybinį laužą.
2. Vėdinimas
2.1. Prietaisai
2.1.1. Grotelės
Grotelės turi būti gaminamos iš cinkuoto (arba nerūdinančio) plieno lakštų, atsparaus korozijai, arba plastiko, su horizontaliomis, profiliuotomis plokštelėmis. Grotelės turi būti tvirtai sumontuotos, neturi kelti triukšmo, neskleisti vibracijos. Oro greitis pralaidos plote neturi viršyti 2,5 m/s.
2.2. Darbai
2.2.1. Ventiliacijos kanalų valymas, dezinfekcija
Nuo ventiliacijos kanalų (šachtų) vidinių paviršių šalinamas susikaupusių teršalų kiekis. Valymas atliekamas sausu būdu nuo dulkių ir kt. susikaupusių nešvarumų. Valymą sudaro ventiliacijos kanalų vidinio paviršiaus gramdymas lankstaus veleno pagalba su įvairaus agresyvumo ir diametro šepečiais. Naudojami atitinkamai pagal šachtos diametrą: apvalūs šepečiai Ø100, Ø150, Ø200 ir Ø250 arba kvadratiniai šepečiai 100x100,150x150, 200x200 ir 250x250.
Jeigu šachtoje yra įstrigusios stambios ir sunkios atliekos, pavyzdžiui buteliai ar plytos, tokiu atveju šių daiktų pašalinimas sprendžiamas kiekvienu atveju individualiai. Gali būti, kad vienintelis būdas tokias atliekas pašalinti yra tik pro bute esančią vėdinimo angą.
Visiškai užtikrinti vėdinimo kanalų vidinio paviršiaus švarą, atliekama vėdinimo kanalų baigiamoji dezinfekcija, kuriai naudojamas žmonių sveikatai nekenksmingas, patentuotas dezinfekantas biocidas (turintis NVSC išduotą biocidinių produktų autorizacijos liudijimą). Ventiliacijos šachtų sienelės apdorojamos nuo kenksmingų žmogaus sveikatai mikroorganizmų (pelėsio, virusų, bakterijų, alergenų), jeigu reikia ir nuo parazitų (žmonių kirmėlinių ligų įvairių sukėlėjų - askaridžių, spalinių, mažojo kaspinuočio kiaušinėlių).
Esamos vėdinimo kanalų būklės (prieš valymą) apžiūrai ir valymo kokybei užtikrinti (po valymo) bei probleminių vietų nustatymui papildomai gali būti pateikiama vėdinimo kanalų video ataskaita, kurias perduodame įrašytas laikmenoje.
Atsargumo priemonės:
- Ypač svarbu, kad dezinfekciją atliekančios įmonės laikytųsi visų autorizacijos sąlygų – iš anksto įspėtų gyventojus apie būsimą dezinfekciją, taikytų kitas privalomas priemones dezinfekcijos metu ir po jos, nenaudotų neįteisintų (naeutorizuotų) dezinfekantų. Daugiabučių gyvenamųjų namų vėdinimo kanalus galima dezinfekuoti 2 produktų tipo biocidiniais produktais ir turinčiais NVSC išduotus biocidinių produktų autorizacijos liudijimus.
Vėdinimo kanalų dezinfekciją atliekanti įmonė privalo:
- Ne vėliau kaip prieš tris dienas iki vėdinimo kanalų dezinfekcijos pradžios namo gyventojai privalo būti informuoti apie numatomus atlikti darbus, jų pradžią ir pabaigą bei būtinumą sandariai uždengti vėdinimo kanalų angas butuose;
- Suteikti gyventojams sveikatos saugos informaciją apie dezinfekcijai naudojamą darbinį tirpalą;
- Informuoti gyventojus, kad, nors jei darbinis tirpalas nėra klasifikuojamas kaip pavojingas sveikatai, siekiant išvengti potencialaus poveikio sveikatai reikia vengti įkvėpti rūko/ aerozolio;
- Užtikrinti, kad gyventojų butuose būtų sandariai uždengtos vėdinimo kanalų angos;
- Įspėti gyventojus, kad vėdinimo kanalų angos gali būti atidengtos tik praėjus valandai po dezinfekcijos procedūros
pabaigos.
Dėmesio! Negalint užtikrinti, kad bute dezinfekcijos metu ir valandą po jos bus sandariai uždengtos vėdinimo kanalų angos, to buto vėdinimo kanalų dezinfekcija neatliekama.
Xxxxxxxx, atlikęs darbus, pateikia sekančią dokumentaciją:
- Naudojamų medžiagų Saugos Duomenų Lapus, atitinkančius ES reglamento 1907/2006/EB-REACH reikalavimus;
- Galiojantį biocido autorizacijos liudijimą;
- VSVP Licencijos kopiją;
- Licencijuotų juridinių asmenų, atliekančių dezinfekciją, atliktų darbų ataskaitą-deklaraciją (Lietuvos higienos
normos );
- Ataskaita-deklaracija pateikiama VSC Užkrečiamų Ligų ir AIDS Centro Epidemiologinės Priežiūros Skyriui ir užsakovui;
- Atliktų darbų aktai;
- Atliktų darbų sąmata;
- Užpildomas Statybų žurnalas.
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-TS | LAPAS | LAPŲ | LAIDA |
8 | 9 | 0 |
2.2.2. Vėdinimo sistemos pridavimas ir perdavimas eksploatacijai
Iki vėdinimo sistemų priėmimo turi būti sudaryti sistemų techniniai pasai ir sistemų aerodinaminiai išbandymo bei oro kiekių rezultatų suvestinė.
PASTABOS:
Techninėje specifikacijoje aprašyti tik pagrindiniai vamzdynų, įrenginių montavimo ir bandymo reikalavimai.
Transportuojant, sandėliuojant, montuojant, bandant, dažant ir izoliuojant vamzdynus ir įrenginius reikia vadovautis statybos taisyklėmis.
Pmaks. – maksimalus eksploatacinis slėgis;
Tmaks. – maksimali eksploatacinė temperatūra.
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-TS | LAPAS | LAPŲ | LAIDA |
9 | 9 | 0 |
SĄNAUDŲ KIEKIŲ ŽINIARAŠTIS
Pozicija, eil. Nr. | Pavadinimas ir techninės charakteristikos | Žymuo | Mato vnt. | Kiekis | Pastabos |
ŠILDYMAS | |||||
1. | Esamų šildymo sistemos vamzdynų rūsyje, stovų, atšakų ir radiatorių demontavimas | 1.4.10. | t | 5 | |
2. | Šiukšlių išvežimas | 1.4.10. | t | 5 | |
3. | Plieninis radiatorius (buto patalpai), 22KV-500-(H)-700(L) | 1.2.1. | Kompl. | 3 | |
4. | Tas pats, 22KV-500-800 | 1.2.1. | Kompl. | 4 | |
5. | Tas pats, 22KV-500-900 | 1.2.1. | Kompl. | 29 | |
6. | Tas pats, 22KV-500-1000 | 1.2.1. | Kompl. | 24 | |
7. | Tas pats, 22KV-500-1100 | 1.2.1. | Kompl. | 15 | |
8. | Tas pats, 22KV-500-1200 | 1.2.1. | Kompl. | 7 | |
9. | Tas pats, 22KV-500-1300 | 1.2.1. | Kompl. | 8 | |
10. | Tas pats, 22KV-500-1400 | 1.2.1. | Kompl. | 14 | |
11. | Tas pats, 33KV-500-1100 | 1.2.1. | Kompl. | 13 | |
12. | Tas pats, 33KV-500-1200 | 1.2.1. | Kompl. | 6 | |
13. | Tas pats, 33KV-500-1300 | 1.2.1. | Kompl. | 4 | |
14. | Tas pats, 33KV-500-1400 | 1.2.1. | Kompl. | 3 | |
15. | Tas pats, 33KV-500-1600 | 1.2.1. | Kompl. | 2 | |
16. | Tas pats, 33KV-900-900 | 1.2.1. | Kompl. | 2 | |
17. | Plieninis radiatorius (laiptinėms), 33KV-900-(H)-1300(L) | 1.2.1. | Kompl. | 3 | |
18. | Balansinis vožtuvas TA STAD DN15 | 1.1.2. | Vnt. | 17 | |
19. | Balansinis vožtuvas TA STAD DN20 | 1.1.2. | Vnt. | 4 | |
20. | Slėgio perkričio reguliatorius TA STAP DN15 | 1.1.2. | Vnt. | 17 | |
21. | Slėgio perkričio reguliatorius TA STAP DN20 | 1.1.2. | Vnt. | 4 | |
22. | Termostatinė galva TA K | 1.1.4. | Vnt. | 134 | |
23. | Termostatinė galva TA K skirta montavimui viešose patalpose | 1.1.4. | Vnt. | 3 | |
24. | Termostatinis vožtuvas su išankstiniais nustatymais TA V-exact II DN15 | 1.1.4. | Vnt. | 137 | |
25. | Prie radiatoriaus tvirtinamas elektroninis šilumos daliklis su pajungimo priedais | 1.2.2. | Vnt. | 134 | |
26. | Radijo duomenų kaupiklis su radijo ryšio sąsaja | 1.2.3. | Vnt. | 9 | |
27. | Duomenų transformatorius (duomenų surinkimo blokas) | 1.2.4. | Vnt. | 1 | |
28. | Programinės įrangos paketas, skirtas apskaitos prietaisų duomenų nuskaitymui, jų kaupimui, analizei ir atvaizdavimui | 1.2.3. | Vnt. | 1 | |
29. | Nuotolinių duomenų nuskaitymo apskaitos sistemos elektrinis pajungimas, programavimas, paleidimas ir derinimas | 1.2.3. | Vnt. | 1 | |
30. | Rutulinis ventilis DN50 | 1.1.1. | Vnt. | 2 | |
31. | Rutulinis ventilis DN40 | 1.1.1. | Vnt. | 2 | |
32. | Rutulinis ventilis DN25 | 1.1.1. | Vnt. | 10 | |
33. | Rutulinis ventilis DN20 | 1.1.1. | Vnt. | 18 | |
34. | Rutulinis ventilis DN15 | 1.1.1. | Vnt. | 14 | |
35. | Išleidimo ventilis DN15 | 1.1.1. | Vnt. | 46 | |
36. | Plieninis presuojamas vamzdis 15x1.0, komplekte su laikikliais ir kitomis tvirtinimo medžiagomis, fasoninėmis dalimis | 1.3.1. | m | 600 | |
37. | Plieninis presuojamas vamzdis 18x1.2, komplekte su laikikliais ir | 1.3.1. | m | 120 |
0 | 2021 | STATYBOS LEIDIMUI, (KONKURSUI) IR STATYBAI. | ||||
LAIDA | IŠLEIDIMO DATA | LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA) | ||||
KVAL. PATV. DOK. NR. | UAB „POLISTATYBA“ | STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | ||||
STATINIO NUMERIS IR PAVADINIMAS PASTATAS – DAUGIABUTIS GYVENAMASIS NAMAS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014) | ||||||
27833 | PV | X. XXXXXXXXXX | ||||
33244 | PDV | X. XXXXXX | ||||
DOKUMENTO PAVADINIMAS SĄNAUDŲ KIEKIŲ ŽINIARAŠTIS | LAIDA | |||||
0 | ||||||
LT | STATYTOJAS IR (ARBA) UŽSAKOVAS UAB „ŠILALĖS ŠILUMOS TINKLAI“, MAIRONIO G. 20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 | DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-SKŽ | LAPAS | LAPŲ | ||
1 | 2 |
kitomis tvirtinimo medžiagomis, fasoninėmis dalimis | |||||
38. | Plieninis presuojamas vamzdis 22x1.5, komplekte su laikikliais ir kitomis tvirtinimo medžiagomis, fasoninėmis dalimis | 1.3.1. | m | 210 | |
39. | Plieninis presuojamas vamzdis 28x1.5, komplekte su laikikliais ir kitomis tvirtinimo medžiagomis, fasoninėmis dalimis | 1.3.1. | m | 120 | |
40. | Plieninis presuojamas vamzdis 35x1.5, komplekte su laikikliais ir kitomis tvirtinimo medžiagomis, fasoninėmis dalimis | 1.3.1. | m | 115 | |
41. | Plieninis presuojamas vamzdis 42x1.5, komplekte su laikikliais ir kitomis tvirtinimo medžiagomis, fasoninėmis dalimis | 1.3.1. | m | 85 | |
42. | Plieninis presuojamas vamzdis 54x1.5, komplekte su laikikliais ir kitomis tvirtinimo medžiagomis, fasoninėmis dalimis | 1.3.1. | m | 10 | |
43. | Plieninis presuojamas vamzdis 64x2.0, komplekte su laikikliais ir kitomis tvirtinimo medžiagomis, fasoninėmis dalimis | 1.3.1. | m | 10 | |
44. | Akmens vatos kevalas su aliuminio folija 15*20 | 1.3.4. | m | 25 | |
45. | Akmens vatos kevalas su aliuminio folija 18*20 | 1.3.4. | m | 10 | |
46. | Akmens vatos kevalas su aliuminio folija 22*30 | 1.3.4. | m | 50 | |
47. | Akmens vatos kevalas su aliuminio folija 28*30 | 1.3.4. | m | 100 | |
48. | Akmens vatos kevalas su aliuminio folija 35*40 | 1.3.4. | m | 115 | |
49. | Akmens vatos kevalas su aliuminio folija 42*40 | 1.3.4. | m | 85 | |
50. | Akmens vatos kevalas su aliuminio folija 54*40 | 1.3.4. | m | 10 | |
51. | Akmens vatos kevalas su aliuminio folija 64*50 | 1.3.4. | m | 10 | |
52. | Pūsto polietileno izoliacija (kevalai) 15*13 | 1.3.7. | m | 300 | |
53. | Pūsto polietileno izoliacija (kevalai) 18*13 | 1.3.7. | m | 110 | |
54. | Pūsto polietileno izoliacija (kevalai) 22*13 | 1.3.7. | m | 160 | |
55. | Pūsto polietileno izoliacija (kevalai) 28*13 | 1.3.7. | m | 20 | |
56. | Akmens vatos izoliacija vamzdynų fasoninėms dalims ir armatūrai, 20 mm | 1.3.4. | m² | 3 | |
57. | Akmens vatos izoliacija vamzdynų fasoninėms dalims ir armatūrai, 30 mm | 1.3.4. | m² | 10 | |
58. | Akmens vatos izoliacija vamzdynų fasoninėms dalims ir armatūrai, 40 mm | 1.3.4. | m² | 10 | |
59. | Akmens vatos izoliacija vamzdynų fasoninėms dalims ir armatūrai, 50 mm | 1.3.4. | m² | 3 | |
60. | Pūsto polietileno izoliacija vamzdynų fasoninėms dalims ir armatūrai, 13 mm | 1.3.7. | m² | 20 | |
61. | Priešgaisriniai įdėklai vamzdžiams atitvarose | 1.4.1., 1.4.2., 1.4.3. | Vnt. | 240 | |
62. | Angų kirtimas ir užtaisymas | 1.3.2. | Vnt. | 120 | |
63. | Nejudama atrama vamzdžiui d22 | 1.3.5. | Vnt. | 2 | |
64. | Nejudama atrama vamzdžiui d28 | 1.3.5. | Vnt. | 10 | |
65. | Nejudama atrama vamzdžiui d35 | 1.3.5. | Vnt. | 10 | |
66. | Nejudama atrama vamzdžiui d42 | 1.3.5. | Vnt. | 6 | |
67. | Ženklinimas | 1.4.4. | Vnt. | 150 | |
68. | Sistemos praplovimas vandeniu | 1.4.5. | m | 1270 | |
69. | Sistemos šiluminis ir hidraulinis išbandymas | 1.4.5., 1.4.6. | m | 1270 | |
70. | Sistemos paleidimas ir derinimas | 1.4.7. | m | 1270 | |
71. | Visų sistemų balansavimas, pasų sudarymas | 1.4.8., 1.4.9. | Sist. | 1 | |
VĖDINIMAS | |||||
72. | Esamų natūralios ventiliacijos kanalų išvalymas, dezinfekavimas, sandarinimas | 2.2.1. | m | 920 | |
73. | Esamų natūralios ventiliacijos kanalų traukos matavimai ir pasų sudarymai | 2.2.2. | m | 920 | |
74. | Oro ištraukimo grotelių keitimas butuose | 2.1.1. | Butas | 40 |
DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.T-SKŽ | LAPAS | LAPŲ | LAIDA |
2 | 2 | 0 |
PROJEKTO DALIŲ VADOVŲ SUDERINIMAI
Eil. Nr. | Bylos žymuo | Pavadinimas | Pavardė | Parašas | Data |
1. | 1014-1A5p-PA(PM)-TDP-2110-BD | BENDROJI | X.Xxxxxxxxxx | ||
2. | 1014-1A5p-PA(PM)-TDP-2110-SP | SKLYPO PLANO | X. Xxxxxxxxxx | ||
3. | 1014-1A5p-PA(PM)-TDP-2110-SA | X. Xxxxxxxxxx | |||
ARCHITEKTŪROS | |||||
4. | 1014-1A5p-PA(PM)-TDP-2110-SK | X.Xxxxxxxxxx | |||
KONSTRUKCIJŲ | |||||
5. | 1014-1A5p-PA(PM)-TDP-2110-ŠT | ŠILUMOS TIEKIMAS | |||
X. Xxxxxx | |||||
6. | 1014-1A5p-PA(PM)-TDP-2110-ŠV | ŠILDYMAS | |||
VĖDINIMAS | X. Xxxxxx | ||||
7. | 1014-1A5p-PA(PM)-TDP-2110-VN | VANDENTIEKIS NUOTEKOS | X. Xxxxxx | 2021 | |
8. | 1014-1A5p-PA(PM)-TDP-2110-PVA | PROCESŲ | |||
VALDYMAS IR AUTOMATIZACIJA | X. Xxxxxxx | ||||
9. | 1014-1A5p-PA(PM)-TDP-2110-E | ELEKTROTECHNIKA | X. Xxxxxxxx | ||
10. | 1014-1A5p-PA(PM)-TDP-2110-SO | PASIRENGIMAS STATYBAI STATYBOS DARBŲ | X. Xxxxxxxxxx | ||
ORGANIZAVIMAS | |||||
STATYBOS | X. Xxxxxxxxxx | ||||
11. | 4018-1A5p-PA(PM)-TDP-2026-KS | SKAIČIUOJAMOSIOS KAINOS | |||
NUSTATYMAS |
ŽYMUO | DALIS | LAIDA | LAPAS |
1014-1A5p-PA(PM)-TDP-2110 | BD | 0 | 1 |
St. 18
2xd28x1.5
Aukšto Patal
Patalpos
Plotas
2xd15x1.0
R-64
3.97
St. 13
2xd22x1.5
0.451 m3/h
Nr.
pos Nr. 1
pavadinimas (m2)
Patalpa 4.32
2xd15x1.0
0.084 m3/h
R-62 3.64
R-61 3.78
R-60
R-63 4.83
R-59
R-65 4.03
R-66 4.08
R-67 7.19
St. 17.1
2xd22x1.5 2xd22x1.5
0.320 m3/h
R-20 4.75
2xd35x1.5 0.971 m3/h
22138W
R-21
R-19
2xd28x1.5
0.579 m3/h
St. 21
2xd15x1.0
R-6 2.69
St. 12
2xd28x1.5
R-7 2.59
G
R-8 2.60
2 Patalpa 25.66
3 Patalpa 2.69
4 Patalpa 2.52
5 Patalpa 2.54
6 Patalpa 2.69
7 Patalpa 2.59
8 Patalpa 2.60
9 Patalpa 3.18
10 Patalpa 3.18
11 Patalpa 3.20
K
St. 1.1
2xd22x1.5
J
4.07
R-57 5.24
2xd28x1.5
0.478 m3/h
St. 2
2xd15x1.0
R-58 6.07
22.44
R-56 3.34
St. 19
2xd15x1.0
R-69 2.81
R-68 1.51
2xd28x1.5
0.448 m3/h
2xd42x1.5
2.52 m3/h
2xd54x1.5
3.93 m3/h
2xd35x1.5
1.25 m3/h
5.01 8.77
Šildymo sistemos projektavimo riba
Į šilumos punktą d64x2.0, 6.45 m3/h
147190W
2xd64x2.0
6.45 m3/h
R-22
R-18 2.75
R-12 19.03
R-1 4.32
R-3 2.69
R-9 3.18
R-4 2.52
R-10 3.18
R-5 2.54
R-2 25.66
E
12 Patalpa 19.03
13 Patalpa 2.64
14 Patalpa 2.64
15 Patalpa 3.73
16 Patalpa 2.62
17 Patalpa 2.62
18 Patalpa 2.75
19 Patalpa 8.77
20 Patalpa 4.75
21 Patalpa 5.01
22 Patalpa 32.59
23 Patalpa 3.68
24 Patalpa 15.18
25 Patalpa 5.11
R-54 6.74
St. 3
2xd22x1.5
R-53 8.56
R-55 4.81
2xd28x1.5 0.616 m3/h
R-52
R-48 24.30
R-51
R-49 4.84
R-50
St. 16
2xd22x1.5
28532W
St. 9
2xd22x1.5
32.59
2xd28x1.5 0.936 m3/h
R-13 2.64
R-16 2.62
St. 10
2xd28x1.5
R-14 2.64
R-17 2.62
R-15 3.73
R-11 3.20
2xd22x1.5
St. 11
2xd22x1.5
B
A
26 Patalpa 4.79
27 Patalpa 4.86
28 Patalpa 4.79
29 Patalpa 4.30
30 Patalpa 10.74
31 Patalpa 2.66
32 Patalpa 17.23
33 Patalpa 16.35
34 Patalpa 1.86
0 35 Patalpa 5.57
36 Patalpa 5.57
37 Patalpa 3.73
38 Patalpa 22.87
2xd35x1.5
1.05 m3/h
I
3.85
4.05
6.15
R-46 R-47 3.37 3.37
2xd28x1.5
0.796 m3/h
St. 15
2xd18x1.2
St. 14
2xd28x1.5
13 14 15
0.315 m3/h
16 17 18 19
39 Patalpa 3.17
40 Patalpa 3.25
41 Patalpa 3.23
42 Patalpa 3.21
43 Patalpa 3.29
44 Patalpa 3.16
45 Patalpa 14.95
46 Patalpa 3.37
47 Patalpa 3.37
48 Patalpa 24.30
49 Patalpa 4.84
50 Patalpa 6.15
51 Patalpa 4.05
52 Patalpa 3.85
53 Patalpa 8.56
St. 4
2xd18x1.2
R-45 14.95
ŠONINIO RADIATORIAUS PAJUNGIMO MAZGAS
54 Patalpa 6.74
55 Patalpa 4.81
56 Patalpa 3.34
H
2xd35x1.5
1.22 m3/h
2xd35x1.5 0.971 m3/h
2xd35x1.5
1.10 m3/h
R-25 5.11
Montuojamas rankinis nuorintojas
Šilumos
daliklis
Naujas
radiatorius
Radiatoriaus termostatinis
ventilis su termostatine galva (montuojama horizontaliai)
Plieninis
57 Patalpa 5.24
58 Patalpa 6.07
59 Patalpa 22.44
60 Patalpa 4.07
61 Patalpa 3.78
62 Patalpa 3.64
St. 5
2xd28x1.5
R-42 3.21
R-41 3.23
R-43 3.29
R-40 3.25
R-44 3.16
R-39 3.17
St. 20
2xd15x1.0
R-31 2.66
R-26 4.79
R-27 4.86
R-28 4.79
PRINCIPINĖ STOVO APRIŠIMO SCHEMA
vamzdis
SUTARTINIAI ŽYMĖJIMAI:
Tiekiamo šilumnešio izoliuojamas vamzdis Grąžinamo šilumnešio izoliuojamas vamzdis Tiekiamo šilumnešio vamzdis
Grąžinamo šilumnešio vamzdis Rutulinis ventilis
63 Patalpa 4.83
64 Patalpa 3.97
65 Patalpa 4.03
66 Patalpa 4.08
67 Patalpa 7.19
68 Patalpa 1.51
69 Patalpa 2.81
452.91
2xd35x1.5
1.66 m3/h
F
R-34
1.86
R-33 16.35
R-38 22.87
R-35 5.57
R-23 3.68
R-36 5.57
R-24 15.18
R-37 3.73
R-29 4.30
R-30 10.74
2xd35x1.5
1.55 m3/h 35368W
2xd42x1.5
2.68 m3/h 61152W
STAD
Rutulinis ventilis
Magistralinis vamzdynas
Išleidimo ventilis
STAP
Išleidimo ventilis
Automatinis balansavimo ventilis (STAD + STAP) Šoninio pajungimo radiatorius su dalikliu Nejudama atrama
Oro srauto judėjimo kryptis (per orlaides)
Oro srauto judėjimo kryptis (tarp patalpų)
PASTABOS:
1) Aukščiausiose sistemos vietose įrengiami automatiniai nuorintojai, žemiausiose - išleidimo ventiliai;
2) Šildymo sistemos magistraliniai vamzmdynai (rūsyje) izoliuojai akmens vatos izoliacija su aliuminio folija;
St. 6
2xd22x1.5
2xd42x1.5
1.93 m3/h 2xd42x1.5
2.40 m3/h
St. 8
2xd22x1.5
3) Kiekvienas šildymo stovas turi turėti galimybe atsiskirti nuo sistemos rutulinių ventilių pagalba;
4) Šildymo sistemos stovai reguliuojami automatiniais balansiniais ventiliais STAD + STAP;
5) Visi radiatorių pajungimai - d15x1.0;
R-32
St. 7
BALANSINIAI VENTILIAI STOVAMS BALANSUOTI STAD + STAP:
6) Kiekviename bute keičiamos oro ištraukimo grotelės.
D 17.23
C
2xd28x1.5
St. 1 (9005W) DN15 STAD nust. padala - 3.68, STAP slėgio perkrytis 17kPa St. 2 (3132W) DN15 STAD nust. padala - 2.29, STAP slėgio perkrytis 17kPa St. 3 (9805W) DN15 STAD nust. padala - 3.88, STAP slėgio perkrytis 17kPa St. 4,15 (4002W) DN15 STAD nust. padala - 2.58, STAP slėgio perkrytis 17kPa St. 5 (10063W) DN15 STAD nust. padala - 3.96, STAP slėgio perkrytis 17kPa St. 6 (6013W) DN15 STAD nust. padala - 3.04, STAP slėgio perkrytis 17kPa
0
LAIDA
KVAL. PATV.
2021
IŠLEIDIMO DATA
Statybos leidimui, (konkursui) ir statybai
LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA)
STATINIO PROJEKTO PAVADINIMAS
DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS
St. 7 (10876W) DN20 STAD nust. padala - 2.51, STAP slėgio perkrytis 17kPa St. 8 (6351W) DN15 STAD nust. padala - 3.11, STAP slėgio perkrytis 17kPa St. 9,11 (7182W) DN15 STAD nust. padala - 3.28, STAP slėgio perkrytis 17kPa St. 10 (14168W) DN20 STAD nust. padala - 2.92, STAP slėgio perkrytis 17kPa St. 12,14 (10285W) DN20 STAD nust. padala - 2.42, STAP slėgio perkrytis 17kPa St. 13 (8925W) DN15 STAD nust. padala - 3.66, STAP slėgio perkrytis 17kPa St. 16 (7936W) DN15 STAD nust. padala - 3.43, STAP slėgio perkrytis 17kPa
St. 17 (7289W) DN15 STAD nust. padala - 3.30, STAP slėgio perkrytis 17kPa
DOK. NR.
27833
33244
UAB "POLISTATYBA"
PV X. Xxxxxxxxxx PDV X. Xxxxxx
STATINIO NUMERIS IR PAVADINIMAS
PASTATAS - DAUGIABUTIS GYVENAMASIS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014)
DOKUMENTO PAVADINIMAS
RŪSIO PLANAS SU ŠILDYMO SISTEMA, M 1:100
LAIDA
0
1 2 3 4 5 6
7 8 9
10 11
12 13
St. 18 (1905W) DN15 STAD nust. padala - 1.76, STAP slėgio perkrytis 17kPa St. 19,20,21 (2928W) DN15 STAD nust. padala - 2.21, STAP slėgio perkrytis 17kPa
STATYTOJAS IR (ARBA) UŽSAKOVAS
LT UAB "ŠILALĖS ŠILUMOS TINKLAI", MAIRONIO G.
DOKUMENTO ŽYMUO
1014-1A5p-PA(PM)-TDP-2110-ŠV.B-01
LAPAS LAPŲ
20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 1 1
Šoninio pajungimo radiatorius 1905 W
St. 18 33_900_900
2xd15x1.0
32-9
59.50
+75 m3/h
3810W
20°C
St. 17
2xd22x1.5
2xd22x1.5
Šoninio pajungimo Šoninio pajungimo radiatorius 1104 W radiatorius 869 W 22_500_1300 22_500_1000
St. 13
a-2 1.79
a-1 3.66
Šoninio pajungimo radiatorius 869 W 22_500_1000
869W
Šoninio pajungimo radiatorius 1432 W 33_500_1200
Pirmo aukšto patalpų eksplikacija | ||||
Aukšto Nr. | Buto Nr. | Patal pos Nr. | Patalpos pavadinimas | Plotas (m2) |
1 | 1 | 1 | Koridorius | 6.56 |
2 | WC | 1.34 | ||
3 | Virtuvė | 9.08 | ||
4 | Kambarys | 14.44 | ||
5 | Vonia | 2.59 | ||
6 | Kambarys | 18.53 | ||
52.54 | ||||
2 | 1 | Koridorius | 4.24 | |
2 | Kambarys | 18.03 | ||
3 | Virtuvė | 7.69 | ||
4 | Vonia | 3.11 | ||
5 | Sandėlis | 1.23 | ||
34.30 | ||||
3 | 1 | Koridorius | 6.60 | |
2 | Kambarys | 18.25 | ||
3 | Vonia | 2.12 | ||
4 | Kambarys | 14.56 | ||
5 | Virtuvė | 9.58 | ||
6 | WC | 1.18 | ||
52.29 | ||||
16 | 1 | Koridorius | 5.36 | |
2 | WC | 1.34 | ||
3 | Virtuvė | 9.54 | ||
4 | Kambarys | 14.82 | ||
5 | Vonia | 3.59 | ||
6 | Kambarys | 18.59 | ||
53.24 | ||||
17 | 1 | Koridorius | 5.45 | |
2 | Vonia | 3.62 | ||
3 | Kambarys | 14.39 | ||
4 | Virtuvė | 9.62 | ||
5 | WC | 1.29 | ||
6 | Kambarys | 18.80 | ||
53.17 | ||||
18 | 1 | Koridorius | 11.74 | |
2 | Kambarys | 17.77 | ||
3 | Virtuvė | 7.87 | ||
4 | Kambarys | 12.13 | ||
5 | Kambarys | 10.39 | ||
6 | Sandėlis | 1.88 | ||
7 | Vonia | 2.25 | ||
8 | WC | 1.16 | ||
65.19 | ||||
31 | 1 | Koridorius | 8.14 | |
2 | WC | 1.11 | ||
3 | Virtuvė | 9.58 | ||
4 | Kambarys | 13.05 | ||
5 | Vonia | 2.17 | ||
6 | Kambarys | 18.51 | ||
7 | Kambarys | 11.49 | ||
64.05 | ||||
32 | 9 | Prekybos salė su kavine | 8.84 | |
10 | Koridorius | 13.01 | ||
11 | Prausykla | 11.05 | ||
12 | WC | 18.05 | ||
13 | Virtuvė | 2.17 | ||
14 | Personalo patalpa | 13.02 | ||
85.15 |
G
St. 1
2xd22x1.5
St. 1.1
St. 17.1
2xd22x1.5
0.281 m3/h palubėje
+45 m3/h
2xd22x1.5
3-5
Šoninio pajungimo
radiatorius 2928 W 33_900_1300
20°C 1-3
St. 12
2xd22x1.5
+45 m3/h
2xd22x1.5
Šoninio pajungimo
3-4
9.58 869W
9.08
1-4
0.311 m3/h palubėje
2xd22x1.5
Šoninio pajungimo
radiatorius 1905 W 33_900_900
32-10
5.50
00-00 00-00
3
869W
20°C
32-13
5.09
±36 m3/h
radiatorius 869 W 22_500_1000
14.56
1104W
±36 m3/h
20°C
3 | 6 m3 | /h |
3-6 1.18 |
-
St. 21
2xd15x1.0
-36 m3/h
1-2
±36 m3/h
14.44
1432W
K
Šoninio pajungimo
radiatorius 620 W 22_500_800
32-14
St. 2 12.63
620W
20°C
1.17
2928W
16°C
-190.2m6/h
St. 19
2xd15x1.0
Šoninio pajungimo
radiatorius 2928 W 33_900_1300
a-5
a-6 1.50
20°C
-54 m3/h
3-3
2.
12
3-1
6.60
2928W
16°C
1.34
Duomenų kaupiklis
1-1
6.56
20°C
-54 m3/h
1-5
2.59
E
2xd15x1.0
J
+15 m3/h
859W
Duomenų
kaupiklis
-36 m3/h
31-2
3.59
±36 m3/h
Šoninio pajungimo
1610W
20°C
3-2
2-5
-90 m3/h
1.23
2-4
2-1
4.24
1610W
20°C
3
Šoninio pajungimo
radiatorius 859 W 22_500_1000
31-7
11.49
+30 m3/h
20°C
31-1
8.14
1.11 869W 31-3
20°C 9.58
radiatorius 869 W 22_500_1000
18.28
+45 m3/h
3.11
990W
+90 m3/h
2099W
20°C
2-2
1-6
18.53
+45 m /h
St. 11
Šoninio pajungimo radiatorius 1340 W 33_500_1100
St. 3
2xd22x1.5
31-6
1340W 18.51
31-5
St. 16
2xd22x1.5
31-4
919W 13.05
Šoninio pajungimo radiatorius 919 W 22_500_1100
St. 9
2xd22x1.5
20°C
2-3
7.69
±36 m3/h
18.03
St. 10
2xd28x1.5
2xd22x1.5
B
A
20°C
I
+30 m3/h
-254.m13/7h
919W
20°C
20°C
+30 m3/h
St. 15
2xd15x1.0
Šoninio pajungimo radiatorius 919 W
Šoninio pajungimo radiatorius 1610 W 33_500_1300
Šoninio pajungimo radiatorius 990 W
Šoninio pajungimo radiatorius 2099 W
Šoninio pajungimo radiatorius 1610 W 33_500_1300
Šoninio pajungimo radiatorius 919 W 22_500_1100
+30 m3/h
18-4
12.13
+30 m3/h
18-5
10.39
22_500_1100
Šoninio pajungimo
13
Šoninio pajungimo
22_500_1100
14 15
33_500_1600
16
17 18 19
St. 4
2xd15x1.0
919W
20°C
radiatorius 869 W 22_500_1000
radiatorius 1432 W 33_500_1200
ŠONINIO RADIATORIAUS PAJUNGIMO MAZGAS
H
Šoninio pajungimo
±36 m3/h
18-3
18-6
1.88
a-4 1.93
a-3 3.62
869W
St. 14
Montuojamas rankinis nuorintojas
Šilumos daliklis
Naujas
radiatorius
Radiatoriaus termostatinis ventilis su termostatine galva (montuojama horizontaliai)
radiatorius 990 W 22_500_1100
Šoninio pajungimo
7.87
St. 5
2xd22x1.5
990W
20°C
1253W
20°C
-54 m3/h
18-7
2.25
-36 m3/h
Šoninio pajungimo radiatorius 2928 W 33_900_1300
St. 20
2xd15x1.0
20°C
16-3
9.54
±36 m3/h
-36 m3/h
2xd22x1.5
16-4
14.82
+45 m3/h 1432W
20°C
Plieninis vamzdis
SUTARTINIAI ŽYMĖJIMAI:
Tiekiamo šilumnešio izoliuojamas vamzdis Grąžinamo šilumnešio izoliuojamas vamzdis Tiekiamo šilumnešio vamzdis
Iš viso: 451.87
radiatorius 1253 W 22_500_1400
F
18-2
17.77
+30 m3/h
18-8
1.16
18-1
11.74
2928W
16°C
16-2
1.34
Duomenų 16-1
kaupiklis 5.36
-54 m3/h
16-5
3.59
PRINCIPINĖ STOVO APRIŠIMO SCHEMA
Išleidimo
Grąžinamo šilumnešio vamzdis Rutulinis ventilis
Išleidimo ventilis
Automatinis balansavimo ventilis (STAD + STAP)
Šoninio pajungimo radiatorius su dalikliu Nejudama atrama
+45 m3/h
17-6 1371W
18.80
-36 m3/h
17-5
17-1
5.45
-54 m3/h
17-2
3.62
1429W
+45 m3/h
1432W
16-6
18.59
STAD
Rutulinis ventilis
Magistralinis vamzdynas
ventilis STAP
Oro srauto judėjimo kryptis (per orlaides) Oro srauto judėjimo kryptis (tarp patalpų)
PASTABOS:
1) Aukščiausiose sistemos vietose įrengiami automatiniai nuorintojai, žemiausiose - išleidimo ventiliai;
St. 6
20°C
1.29
990W
20°C
+45 m3/h
17-3
20°C
St. 8
2) Šildymo sistemos magistraliniai vamzmdynai (rūsyje) izoliuojai akmens vatos izoliacija su aliuminio folija;
3) Kiekvienas šildymo stovas turi turėti galimybe atsiskirti nuo sistemos rutulinių ventilių pagalba;
2xd18x1.2
20°C
±36 m3/h
14.39
2xd18x1.2
4) Šildymo sistemos stovai reguliuojami automatiniais balansiniais ventiliais STAD + STAP;
5) Visi radiatorių pajungimai - d15x1.0;
D Šoninio pajungimo
radiatorius 1371 W 33_500_1100
C
17-4
9.62
Šoninio pajungimo radiatorius 990 W 22_500_1100
St. 7
2xd22x1.5
Šoninio pajungimo radiatorius 1429 W 33_500_1100
Šoninio pajungimo radiatorius 1432 W 33_500_1200
BALANSINIAI VENTILIAI STOVAMS BALANSUOTI STAD + STAP:
0 | 2021 | Statybos leidimui, (konkursui) ir statybai | ||||
LAIDA | IŠLEIDIMO DATA | LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA) | ||||
KVAL. PATV. DOK. NR. | UAB "POLISTATYBA" | STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | ||||
STATINIO NUMERIS IR PAVADINIMAS PASTATAS - DAUGIABUTIS GYVENAMASIS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014) | ||||||
27833 | PV | X. Xxxxxxxxxx | ||||
33244 | PDV | X. Xxxxxx | ||||
DOKUMENTO PAVADINIMAS 1 AUKŠTO PLANAS SU ŠILDYMO SISTEMA, M 1:100 | LAIDA | |||||
0 | ||||||
LT | STATYTOJAS IR (ARBA) UŽSAKOVAS UAB "ŠILALĖS ŠILUMOS TINKLAI", MAIRONIO G. 20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 | DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.B-02 | LAPAS | LAPŲ | ||
1 | 1 |
St. 1 (9005W) DN15 STAD nust. padala - 3.68, STAP slėgio perkrytis 17kPa St. 2 (3132W) DN15 STAD nust. padala - 2.29, STAP slėgio perkrytis 17kPa St. 3 (9805W) DN15 STAD nust. padala - 3.88, STAP slėgio perkrytis 17kPa St. 4,15 (4002W) DN15 STAD nust. padala - 2.58, STAP slėgio perkrytis 17kPa St. 5 (10063W) DN15 STAD nust. padala - 3.96, STAP slėgio perkrytis 17kPa St. 6 (6013W) DN15 STAD nust. padala - 3.04, STAP slėgio perkrytis 17kPa St. 7 (10876W) DN20 STAD nust. padala - 2.51, STAP slėgio perkrytis 17kPa St. 8 (6351W) DN15 STAD nust. padala - 3.11, STAP slėgio perkrytis 17kPa St. 9,11 (7182W) DN15 STAD nust. padala - 3.28, STAP slėgio perkrytis 17kPa St. 10 (14168W) DN20 STAD nust. padala - 2.92, STAP slėgio perkrytis 17kPa St. 12,14 (10285W) DN20 STAD nust. padala - 2.42, STAP slėgio perkrytis 17kPa St. 13 (8925W) DN15 STAD nust. padala - 3.66, STAP slėgio perkrytis 17kPa St. 16 (7936W) DN15 STAD nust. padala - 3.43, STAP slėgio perkrytis 17kPa St. 17 (7289W) DN15 STAD nust. padala - 3.30, STAP slėgio perkrytis 17kPa St. 18 (1905W) DN15 STAD nust. padala - 1.76, STAP slėgio perkrytis 17kPa
6) Kiekviename bute keičiamos oro ištraukimo grotelės.
1 2 3 4 5 6
7 8 9
10 11
12 13
St. 19,20,21 (2928W) DN15 STAD nust. padala - 2.21, STAP slėgio perkrytis 17kPa
34-5
Šoninio pajungimo Šoninio pajungimo
i ≥2,5%
Šoninio pajungimo
Šoninio pajungimo
Šoninio pajungimo radiatorius 1047 W
34-4
18.14
3
1047W
20°C
2-54.1m36/h
792W
20°C
34-6
13.13
St. 17
Šoninio pajungimo radiatorius 792 W 22_500_1000
radiatorius 937 W 22_500_1100
radiatorius 739 W 22_500_900
radiatorius 739 W 22_500_900
radiatorius 1173 W 22_500_1400
G
22_500_1200
St. 1
2xd18x1.2
+22.5 m /h
+22.5 m3/h
2xd18x1.2
+45 m3/h
St. 13
2xd18x1.2
6-5
739W
20°C 4-3
St. 12
2xd22x1.5
+45 m3/h
Šoninio pajungimo
640W
3 Šoninio pajungimo
6-4
9.42 739W
8.95
4-4
34-3
20°C
34-1
±36 m /h
34-7
radiatorius 739 W
14.57
±36 m3/h
20°C
±36 m3/h
14.45
radiatorius 640 W 22_500_800
K
Šoninio pajungimo
radiatorius 595 W 22_500_700
10.96
+22.5 m3/h
34-2
St. 2 12.96
595W
20°C
8.79
34-8
1.12
-36 m3/h
739W
20°C 9.68
22_500_900
937W
20°C
-54 m3/h
6-3
2.
10
-
3 | 6 m3 | /h |
6-6 1.32 |
6-1
6.67
-36 m3/h
4-2
i ≥2,5%
1.29
4-1
6.59
1173W
20°C
-54 m3/h
4-5
2.56
E
J
Šoninio pajungimo
2xd15x1.0
+22.5 m3/h
725W
-36 m3/h
33-2
±36 m3/h
Šoninio pajungimo
1334W
20°C
6-2
5-5
1.23
-90 m3/h
5-4
5-1
4.26
1851W
1334W
20°C
4-6 3
radiatorius 725 W 22_500_900
33-7
11.47
+30 m3/h
20°C
33-1
8.16
1.20
739W 33-3
20°C 9.50
radiatorius 739 W 22_500_900
18.17
+45 m3/h
3.07
834W
+90 m3/h
20°C
5-2
18.56
+45 m /h
St. 11
Šoninio pajungimo radiatorius 1096 W 22_500_1300
St. 3
2xd22x1.5
1096W
33-6
18.42
3
33-5
St. 16
2xd18x1.2
33-4
732W 13.13
3
Šoninio pajungimo radiatorius 732 W 22_500_900
St. 9
2xd18x1.2
20°C
5-3
7.75
±36 m3/h
18.03
St. 10
2xd22x1.5
2xd18x1.2
B
A
20°C
I
+30 m /h
-254.m13/7h
732W
20°C
20°C
+30 m /h
St. 15
2xd15x1.0
Šoninio pajungimo radiatorius 732 W
Šoninio pajungimo radiatorius 1334 W 33_500_1100
Šoninio pajungimo radiatorius 834 W
Šoninio pajungimo radiatorius 1851 W
Šoninio pajungimo radiatorius 1334 W 33_500_1100
Šoninio pajungimo radiatorius 732 W 22_500_900
+30 m3/h
21-4
12.09
+30 m3/h
21-5
10.43
22_500_900
Šoninio pajungimo
13
Šoninio pajungimo
22_500_1000
i ≥2,5%
14 15
33_500_1400
16
17 18 19
St. 4
2xd15x1.0
732W
20°C
radiatorius 739 W 22_500_900
radiatorius 1173 W 22_500_1400
ŠONINIO RADIATORIAUS PAJUNGIMO MAZGAS
H
Šoninio pajungimo radiatorius 834 W
±36 m3/h
21-3
7.85 834W
21-6
1.87
-54 m3/h
739W
20°C
19-3
St. 14
2xd22x1.5
Montuojamas rankinis nuorintojas
Šilumos daliklis
Naujas
radiatorius
Radiatoriaus termostatinis ventilis su termostatine galva (montuojama horizontaliai)
Plieninis
Iš viso:451.29
22_500_1000
Šoninio pajungimo
St. 5
2xd22x1.5
20°C
1043W
20°C
21-7
2.23
-36 m3/h
-36 m3/h
9.49
±36 m3/h
19-4
14.74
+45 m3/h 1173W
20°C
vamzdis
SUTARTINIAI ŽYMĖJIMAI:
Antro aukšto patalpų eksplikacija | ||||
Aukšto Nr. | Buto Nr. | Patal pos Nr. | Patalpos pavadinimas | Plotas (m2) |
2 | 4 | 1 | Koridorius | 6.59 |
2 | WC | 1.29 | ||
3 | Virtuvė | 8.95 | ||
4 | Kambarys | 14.45 | ||
5 | Vonia | 2.56 | ||
6 | Kambarys | 18.56 | ||
52.40 | ||||
5 | 1 | Koridorius | 4.26 | |
2 | Kambarys | 18.03 | ||
3 | Virtuvė | 7.75 | ||
4 | Vonia | 3.07 | ||
5 | Sandėlis | 1.23 | ||
34.34 | ||||
6 | 1 | Koridorius | 6.67 | |
2 | Kambarys | 18.17 | ||
3 | Vonia | 2.10 | ||
4 | Kambarys | 14.57 | ||
5 | Virtuvė | 9.42 | ||
6 | WC | 1.32 | ||
52.25 | ||||
19 | 1 | Koridorius | 5.45 | |
2 | WC | 1.37 | ||
3 | Virtuvė | 9.45 | ||
4 | Kambarys | 14.74 | ||
5 | Vonia | 3.62 | ||
6 | Kambarys | 18.55 | ||
53.18 | ||||
20 | 1 | Koridorius | 5.50 | |
2 | Vonia | 3.63 | ||
3 | Kambarys | 14.31 | ||
4 | Virtuvė | 9.60 | ||
5 | WC | 1.15 | ||
6 | Kambarys | 18.76 | ||
52.95 | ||||
21 | 1 | Koridorius | 11.65 | |
2 | Kambarys | 17.91 | ||
3 | Virtuvė | 7.85 | ||
4 | Kambarys | 12.09 | ||
5 | Kambarys | 10.43 | ||
6 | Sandėlis | 1.87 | ||
7 | Vonia | 2.23 | ||
8 | WC | 1.15 | ||
65.18 | ||||
33 | 1 | Koridorius | 8.16 | |
2 | WC | 1.20 | ||
3 | Virtuvė | 9.50 | ||
4 | Kambarys | 13.13 | ||
5 | Vonia | 2.17 | ||
6 | Kambarys | 18.42 | ||
7 | Kambarys | 11.47 | ||
64.05 | ||||
34 | 1 | Koridorius | 8.79 | |
2 | Kambarys | 12.96 | ||
3 | Kambarys | 10.96 | ||
4 | Kambarys | 18.14 | ||
5 | Vonia | 2.16 | ||
6 | Kambarys | 13.13 | ||
7 | Virtuvė | 9.68 | ||
8 | WC | 1.12 | ||
76.94 |
Tiekiamo šilumnešio izoliuojamas vamzdis Grąžinamo šilumnešio izoliuojamas vamzdis Tiekiamo šilumnešio vamzdis
radiatorius 1043 W 22_500_1200
F
21-2
17.91
+30 m3/h
21-8
1.15
21-1
11.65
19-2
1.37
19-1
5.45
-54 m3/h
19-5
3.62
PRINCIPINĖ STOVO APRIŠIMO SCHEMA
Išleidimo
Grąžinamo šilumnešio vamzdis Rutulinis ventilis
Išleidimo ventilis
Automatinis balansavimo ventilis (STAD + STAP)
Šoninio pajungimo radiatorius su dalikliu Nejudama atrama
+45 m3/h
20-6 1103W
18.76
-36 m3/h
20-5
20-1
5.50
-54 m3/h
20-2
3.63
1199W
+45 m3/h
1173W
19-6
18.55
STAD
Rutulinis ventilis
Magistralinis vamzdynas
ventilis STAP
Oro srauto judėjimo kryptis (per orlaides) Oro srauto judėjimo kryptis (tarp patalpų)
PASTABOS:
1) Aukščiausiose sistemos vietose įrengiami automatiniai nuorintojai, žemiausiose - išleidimo ventiliai;
St. 6
20°C
1.19
834W
20°C
+45 m3/h
20-3
20°C
St. 8
2) Šildymo sistemos magistraliniai vamzmdynai (rūsyje) izoliuojai akmens vatos izoliacija su aliuminio folija;
3) Kiekvienas šildymo stovas turi turėti galimybe atsiskirti nuo sistemos rutulinių ventilių pagalba;
2xd15x1.0
20°C
±36 m3/h
14.31
2xd18x1.2
4) Šildymo sistemos stovai reguliuojami automatiniais balansiniais ventiliais STAD + STAP;
5) Visi radiatorių pajungimai - d15x1.0;
D Šoninio pajungimo
radiatorius 1103 W 22_500_1300
C
20-4
9.60
Šoninio pajungimo radiatorius 834 W 22_500_1000
St. 7
2xd22x1.5
Xxxxxxx pajungimo radiatorius 1199 W 22_500_1400
Šoninio pajungimo radiatorius 1173 W 22_500_1400
BALANSINIAI VENTILIAI STOVAMS BALANSUOTI STAD + STAP:
0 | 2021 | Statybos leidimui, (konkursui) ir statybai | ||||
LAIDA | IŠLEIDIMO DATA | LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA) | ||||
KVAL. PATV. DOK. NR. | UAB "POLISTATYBA" | STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | ||||
STATINIO NUMERIS IR PAVADINIMAS PASTATAS - DAUGIABUTIS GYVENAMASIS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014) | ||||||
27833 | PV | X. Xxxxxxxxxx | ||||
33244 | PDV | X. Xxxxxx | ||||
DOKUMENTO PAVADINIMAS 2 AUKŠTO PLANAS SU ŠILDYMO SISTEMA, M 1:100 | LAIDA | |||||
0 | ||||||
LT | STATYTOJAS IR (ARBA) UŽSAKOVAS UAB "ŠILALĖS ŠILUMOS TINKLAI", MAIRONIO G. 20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 | DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.B-03 | LAPAS | LAPŲ | ||
1 | 1 |
St. 1 (9005W) DN15 STAD nust. padala - 3.68, STAP slėgio perkrytis 17kPa St. 2 (3132W) DN15 STAD nust. padala - 2.29, STAP slėgio perkrytis 17kPa St. 3 (9805W) DN15 STAD nust. padala - 3.88, STAP slėgio perkrytis 17kPa St. 4,15 (4002W) DN15 STAD nust. padala - 2.58, STAP slėgio perkrytis 17kPa St. 5 (10063W) DN15 STAD nust. padala - 3.96, STAP slėgio perkrytis 17kPa St. 6 (6013W) DN15 STAD nust. padala - 3.04, STAP slėgio perkrytis 17kPa St. 7 (10876W) DN20 STAD nust. padala - 2.51, STAP slėgio perkrytis 17kPa St. 8 (6351W) DN15 STAD nust. padala - 3.11, STAP slėgio perkrytis 17kPa St. 9,11 (7182W) DN15 STAD nust. padala - 3.28, STAP slėgio perkrytis 17kPa St. 10 (14168W) DN20 STAD nust. padala - 2.92, STAP slėgio perkrytis 17kPa St. 12,14 (10285W) DN20 STAD nust. padala - 2.42, STAP slėgio perkrytis 17kPa St. 13 (8925W) DN15 STAD nust. padala - 3.66, STAP slėgio perkrytis 17kPa St. 16 (7936W) DN15 STAD nust. padala - 3.43, STAP slėgio perkrytis 17kPa St. 17 (7289W) DN15 STAD nust. padala - 3.30, STAP slėgio perkrytis 17kPa St. 18 (1905W) DN15 STAD nust. padala - 1.76, STAP slėgio perkrytis 17kPa
6) Kiekviename bute keičiamos oro ištraukimo grotelės.
1 2 3 4 5 6
7 8 9
10 11
12 13
St. 19,20,21 (2928W) DN15 STAD nust. padala - 2.21, STAP slėgio perkrytis 17kPa
36-5
Šoninio pajungimo Šoninio pajungimo
i ≥2,5%
Šoninio pajungimo
Šoninio pajungimo
Šoninio pajungimo
radiatorius 1047 W 22_500_1200
St. 1
36-4
18.05
+22.5 m3/h
1047W
20°C
-254.1m37/h
792W
20°C
36-6
13.02
3
St. 17
Šoninio pajungimo radiatorius 792 W 22_500_1000
radiatorius 937 W 22_500_1100
radiatorius 739 W 22_500_900
radiatorius 739 W 22_500_900
radiatorius 1173 W 22_500_1400
G
2xd18x1.2
+22.5 m /h
2xd15x1.0
+45 m3/h
St. 13
2xd15x1.0
9-5
739W
20°C 7-3
St. 12
2xd18x1.2
+45 m3/h
Šoninio pajungimo
36-3
640W
20°C
36-1
±36 m3/h
Šoninio pajungimo
9-4
9.68 739W
±36 m3/h
9.20
3
7-4
radiatorius 640 W 22_500_800
K
Šoninio pajungimo
radiatorius 595 W 22_500_700
11.05
+22.5 m3/h
36-2
St. 2 13.01
595W
20°C
8.85
36-8
1.12
i ≥2,5%
-36 m3/h
739W36-7
20°C 9.94
radiatorius 739 W 22_500_900
14.56
937W
20°C
-54 m3/h
9-3
2.
12
9-1
6.67
20°C
3 | 6 m3 | /h |
9-6 1.18 |
-
-36 m3/h
7-2
1.17
Duomenų kaupiklis
±36 m /h
7-1
6.56
14.44
1173W
20°C
-54 m3/h
7-5
2.59
E
2xd15x1.0
J
+22.5 m3/h
725W
Duomenų
kaupiklis
-36 m3/h
35-2
±36 m3/h
1334W
20°C
8-5
1.23
-90 m3/h
8-4
8-1
4.24
1334W
20°C
Šoninio pajungimo radiatorius 725 W 22_500_900
35-7
11.49
+30 m3/h
20°C
35-1
8.13
1.12 739W 35-3
20°C 9.69
Šoninio pajungimo radiatorius 739 W 22_500_900
9-2
18.25
St. 9
+45 m3/h
3.11
834W
+90 m3/h
1851W
20°C
8-2
7-6
18.53
+45 m3/h
St. 11
Šoninio pajungimo
radiatorius 1096 W 22_500_1300
St. 3
2xd18x1.2
35-6
St. 16
2xd15x1.0
35-4
Šoninio pajungimo radiatorius 732 W
2xd15x1.0
20°C
8-3
7.69
±36 m3/h
18.03
St. 10
2xd18x1.2
2xd15x1.0
B
A
1096W 18.51
20°C +30 m3/h
I
35-5
-254.m13/7h
732W
732W 13.05
20°C +30 m3/h
St. 15
2xd15x1.0
22_500_900
Šoninio pajungimo
Šoninio pajungimo radiatorius 1334 W 33_500_1100
Šoninio pajungimo radiatorius 834 W
Šoninio pajungimo radiatorius 1851 W
Šoninio pajungimo radiatorius 1334 W 33_500_1100
i ≥2,5%
Šoninio pajungimo radiatorius 732 W
20°C
+30 m3/h
+30 m3/h
radiatorius 732 W
22_500_900
13 14
22_500_1000
15
33_500_1400
16
17 18 19
22_500_900
24-4
12.13
St. 4
2xd15x1.0
24-5
10.39
732W
20°C
Šoninio pajungimo radiatorius 739 W 22_500_900
Šoninio pajungimo radiatorius 1173 W 22_500_1400
ŠONINIO RADIATORIAUS PAJUNGIMO MAZGAS
H
Šoninio pajungimo radiatorius 834 W 22_500_1000
±36 m3/h
24-3
7.87
St. 5
Trečio aukšto patalpų eksplikacija | ||||
Aukšto Nr. | Buto Nr. | Patal pos Nr. | Patalpos pavadinimas | Plotas (m2) |
3 | 7 | 1 | Koridorius | 6.56 |
2 | WC | 1.17 | ||
3 | Virtuvė | 9.20 | ||
4 | Kambarys | 14.44 | ||
5 | Vonia | 2.59 | ||
6 | Kambarys | 18.53 | ||
52.49 | ||||
8 | 1 | Koridorius | 4.24 | |
2 | Kambarys | 18.03 | ||
3 | Virtuvė | 7.69 | ||
4 | Vonia | 3.11 | ||
5 | Sandėlis | 1.23 | ||
34.30 | ||||
9 | 1 | Koridorius | 6.57 | |
2 | Kambarys | 18.25 | ||
3 | Vonia | 2.12 | ||
4 | Kambarys | 14.56 | ||
5 | Virtuvė | 9.68 | ||
6 | WC | 1.18 | ||
52.36 | ||||
22 | 1 | Koridorius | 5.36 | |
2 | WC | 1.34 | ||
3 | Virtuvė | 9.64 | ||
4 | Kambarys | 14.82 | ||
5 | Vonia | 3.59 | ||
6 | Kambarys | 18.59 | ||
53.34 | ||||
23 | 1 | Koridorius | 5.45 | |
2 | Vonia | 3.62 | ||
3 | Kambarys | 14.39 | ||
4 | Virtuvė | 9.72 | ||
5 | WC | 1.12 | ||
6 | Kambarys | 18.80 | ||
53.10 | ||||
24 | 1 | Koridorius | 11.74 | |
2 | Kambarys | 17.77 | ||
3 | Virtuvė | 7.87 | ||
4 | Kambarys | 12.13 | ||
5 | Kambarys | 10.39 | ||
6 | Sandėlis | 1.88 | ||
7 | Vonia | 2.25 | ||
8 | WC | 1.16 | ||
65.19 | ||||
35 | 1 | Koridorius | 8.13 | |
2 | WC | 1.12 | ||
3 | Virtuvė | 9.69 | ||
4 | Kambarys | 13.05 | ||
5 | Vonia | 2.17 | ||
6 | Kambarys | 18.51 | ||
7 | Kambarys | 11.49 | ||
64.16 | ||||
36 | 1 | Koridorius | 8.85 | |
2 | Kambarys | 13.01 | ||
3 | Kambarys | 11.05 | ||
4 | Kambarys | 18.05 | ||
5 | Vonia | 2.17 | ||
6 | Kambarys | 13.02 | ||
7 | Virtuvė | 9.94 | ||
8 | WC | 1.12 | ||
77.21 |
834W
20°C
24-6
1.88
-54 m3/h
24-7
2.25
739W
20°C
22-3
9.64
±36 m3/h
St. 14
2xd18x1.2
22-4
14.82
Montuojamas rankinis nuorintojas
Šilumos daliklis
Naujas
radiatorius
Radiatoriaus termostatinis ventilis su termostatine galva (montuojama horizontaliai)
Plieninis vamzdis
SUTARTINIAI ŽYMĖJIMAI:
Tiekiamo šilumnešio izoliuojamas vamzdis
Iš viso:452.15
Šoninio pajungimo radiatorius 1043 W 22_500_1200
F
2xd18x1.2 1043W
20°C
24-2
17.77
+30 m3/h
-36 m3/h
24-8
1.16
24-1
11.74
-36 m3/h
22-2
1.34
Duomenų 22-1
kaupiklis 5.36
+45 m3/h 1173W
20°C
-54 m3/h
22-5
3.69
PRINCIPINĖ STOVO APRIŠIMO SCHEMA
Išleidimo
Grąžinamo šilumnešio izoliuojamas vamzdis Tiekiamo šilumnešio vamzdis
Grąžinamo šilumnešio vamzdis Rutulinis ventilis
Išleidimo ventilis
Automatinis balansavimo ventilis (STAD + STAP)
Šoninio pajungimo radiatorius su dalikliu Nejudama atrama
+45 m3/h
23-6 1103W
18.80
-36 m3/h
23-5
23-1
5.46
-54 m3/h
23-2
3.62
1199W
+45 m3/h
1173W
22-6
18.59
STAD
Rutulinis ventilis
Magistralinis vamzdynas
ventilis STAP
Oro srauto judėjimo kryptis (per orlaides) Oro srauto judėjimo kryptis (tarp patalpų)
PASTABOS:
1) Aukščiausiose sistemos vietose įrengiami automatiniai nuorintojai, žemiausiose - išleidimo ventiliai;
St. 6
20°C
1.12
834W
20°C
+45 m3/h
23-3
20°C
St. 8
2) Šildymo sistemos magistraliniai vamzmdynai (rūsyje) izoliuojai akmens vatos izoliacija su aliuminio folija;
3) Kiekvienas šildymo stovas turi turėti galimybe atsiskirti nuo sistemos rutulinių ventilių pagalba;
2xd15x1.0
20°C
±36 m3/h
14.39
2xd15x1.0
4) Šildymo sistemos stovai reguliuojami automatiniais balansiniais ventiliais STAD + STAP;
5) Visi radiatorių pajungimai - d15x1.0;
D Šoninio pajungimo
radiatorius 1103 W 22_500_1300
C
23-4
9.72
Šoninio pajungimo radiatorius 834 W 22_500_1000
St. 7
2xd18x1.2
Xxxxxxx pajungimo radiatorius 1199 W 22_500_1400
Šoninio pajungimo radiatorius 1173 W 22_500_1400
BALANSINIAI VENTILIAI STOVAMS BALANSUOTI STAD + STAP:
0 | 2021 | Statybos leidimui, (konkursui) ir statybai | ||||
LAIDA | IŠLEIDIMO DATA | LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA) | ||||
KVAL. PATV. DOK. NR. | UAB "POLISTATYBA" | STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | ||||
STATINIO NUMERIS IR PAVADINIMAS PASTATAS - DAUGIABUTIS GYVENAMASIS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014) | ||||||
27833 | PV | X. Xxxxxxxxxx | ||||
33244 | PDV | X. Xxxxxx | ||||
DOKUMENTO PAVADINIMAS 3 AUKŠTO PLANAS SU ŠILDYMO SISTEMA, M 1:100 | LAIDA | |||||
0 | ||||||
LT | STATYTOJAS IR (ARBA) UŽSAKOVAS UAB "ŠILALĖS ŠILUMOS TINKLAI", MAIRONIO G. 20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 | DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.B-04 | LAPAS | LAPŲ | ||
1 | 1 |
St. 1 (9005W) DN15 STAD nust. padala - 3.68, STAP slėgio perkrytis 17kPa St. 2 (3132W) DN15 STAD nust. padala - 2.29, STAP slėgio perkrytis 17kPa St. 3 (9805W) DN15 STAD nust. padala - 3.88, STAP slėgio perkrytis 17kPa St. 4,15 (4002W) DN15 STAD nust. padala - 2.58, STAP slėgio perkrytis 17kPa St. 5 (10063W) DN15 STAD nust. padala - 3.96, STAP slėgio perkrytis 17kPa St. 6 (6013W) DN15 STAD nust. padala - 3.04, STAP slėgio perkrytis 17kPa St. 7 (10876W) DN20 STAD nust. padala - 2.51, STAP slėgio perkrytis 17kPa St. 8 (6351W) DN15 STAD nust. padala - 3.11, STAP slėgio perkrytis 17kPa St. 9,11 (7182W) DN15 STAD nust. padala - 3.28, STAP slėgio perkrytis 17kPa St. 10 (14168W) DN20 STAD nust. padala - 2.92, STAP slėgio perkrytis 17kPa St. 12,14 (10285W) DN20 STAD nust. padala - 2.42, STAP slėgio perkrytis 17kPa St. 13 (8925W) DN15 STAD nust. padala - 3.66, STAP slėgio perkrytis 17kPa St. 16 (7936W) DN15 STAD nust. padala - 3.43, STAP slėgio perkrytis 17kPa St. 17 (7289W) DN15 STAD nust. padala - 3.30, STAP slėgio perkrytis 17kPa St. 18 (1905W) DN15 STAD nust. padala - 1.76, STAP slėgio perkrytis 17kPa
6) Kiekviename bute keičiamos oro ištraukimo grotelės.
1 2 3 4 5 6
7 8 9
10 11
12 13
St. 19,20,21 (2928W) DN15 STAD nust. padala - 2.21, STAP slėgio perkrytis 17kPa
38-5
Šoninio pajungimo Šoninio pajungimo
i ≥2,5%
Šoninio pajungimo
Šoninio pajungimo
Šoninio pajungimo radiatorius 1047 W
38-4
18.21
1047W
20°C
-254.2m31/h
792W
20°C
38-6
13.07
Šoninio pajungimo radiatorius 792 W 22_500_1000
radiatorius 937 W 22_500_1100
radiatorius 739 W 22_500_900
radiatorius 739 W 22_500_900
radiatorius 1173 W 22_500_1400
G
22_500_1200
St. 1
2xd15x1.0
+22.5 m3/h
+22.5 m3/h
St. 17
2xd15x1.0
+45 m3/h
St. 13
2xd15x1.0
12-5
739W
20°C10-3
St. 12
2xd15x1.0
+45 m3/h
Šoninio pajungimo
38-3
640W
20°C
38-1
±36 m3/h
Šoninio pajungimo
12-4
9.64 739W
±36 m3/h
9.07
±36 m3/h
10-4
radiatorius 640 W 22_500_800
K
Šoninio pajungimo
radiatorius 595 W 22_500_700
10.93
+22.5 m3/h
38-2
St. 2 13.14
595W
20°C
8.79
38-8
1.26
-36 m3/h
739W38-7
20°C 9.62
radiatorius 739 W 22_500_900
14.49
937W
20°C
-54 m3/h
12-3
2.23
12-1
6.69
20°C
3 | 6 m3 | /h |
9-6 1.18 |
-
-36 m3/h
10-2
i ≥2,5%
1.24
10-1
6.21
14.30
1173W
20°C
-54 m3/h
10-5
2.60
E
2xd15x1.0
J
+22.5 m3/h
725W
-36 m3/h
37-2
±36 m3/h
Šoninio pajungimo
1334W
20°C
11-5
1.22
-90 m3/h
11-4
11-1
4.32
1334W
20°C
Šoninio pajungimo radiatorius 725 W 22_500_900
37-7
11.54
+30 m3/h
20°C
37-1
8.09
1.27
739W 37-3
20°C 9.51
radiatorius 739 W 22_500_900
12-2
18.34
St. 9
+45 m3/h
3.04
834W
+90 m3/h
1851W
20°C
11-2
10-6
18.41
+45 m3/h
St. 11
Šoninio pajungimo radiatorius 1096 W 22_500_1300
I
St. 3
2xd15x1.0
1096W
20°C
37-6
18.40
+30 m3/h
37-5
-254.m13/6h
732W
St. 16
2xd15x1.0
37-4
732W 13.03
20°C +30 m3/h
St. 15
2xd15x1.0
Šoninio pajungimo radiatorius 732 W 22_500_900
Šoninio pajungimo
2xd15x1.0
Šoninio pajungimo radiatorius 1334 W 33_500_1100
20°C
11-3
7.73
±36 m3/h
Šoninio pajungimo radiatorius 834 W
17.95
St. 10
2xd15x1.0
Šoninio pajungimo radiatorius 1851 W
2xd15x1.0
B
A
Šoninio pajungimo radiatorius 1334 W 33_500_1100
Šoninio pajungimo
20°C
+30 m3/h
+30 m3/h
radiatorius 732 W
22_500_900
22_500_1000
33_500_1400
radiatorius 732 W 22_500_900
27-4
12.16
27-5
10.42
i ≥2,5%
Šoninio pajungimo
13
Šoninio pajungimo
14 15
16 17 18 19
St. 4
2xd15x1.0
732W
20°C
radiatorius 739 W 22_500_900
radiatorius 1173 W 22_500_1400
ŠONINIO RADIATORIAUS PAJUNGIMO MAZGAS
H
Šoninio pajungimo radiatorius 834 W 22_500_1000
±36 m3/h
27-3
7.90
St. 5
834W
20°C
27-6
1.82
-54 m3/h
27-7
2.22
739W
20°C
25-3
9.57
±36 m3/h
St. 14
2xd15x1.0
25-4
14.87
Montuojamas rankinis nuorintojas
Šilumos daliklis
Naujas
radiatorius
Radiatoriaus termostatinis ventilis su termostatine galva (montuojama horizontaliai)
Plieninis vamzdis
SUTARTINIAI ŽYMĖJIMAI:
Tiekiamo šilumnešio izoliuojamas vamzdis
Iš viso:451.06
Šoninio pajungimo radiatorius 1043 W 22_500_1200
F
2xd15x1.0 1043W
20°C
27-2
17.73
+30 m3/h
-36 m3/h
27-8
1.13
27-1
11.58
-36 m3/h
25-2
1.38
25-1
6.25
+45 m3/h 1173W
Ketvirto aukšto patalpų eksplikacija | ||||
Aukšto Nr. | Buto Nr. | Patal pos Nr. | Patalpos pavadinimas | Plotas (m2) |
4 | 10 | 1 | Koridorius | 6.21 |
2 | WC | 1.24 | ||
3 | Virtuvė | 9.07 | ||
4 | Kambarys | 14.30 | ||
5 | Vonia | 2.60 | ||
6 | Kambarys | 18.41 | ||
51.83 | ||||
11 | 1 | Koridorius | 4.32 | |
2 | Kambarys | 17.95 | ||
3 | Virtuvė | 7.73 | ||
4 | Vonia | 3.04 | ||
5 | Sandėlis | 1.22 | ||
34.26 | ||||
12 | 1 | Koridorius | 6.69 | |
2 | Kambarys | 18.34 | ||
3 | Vonia | 2.23 | ||
4 | Kambarys | 14.49 | ||
5 | Virtuvė | 9.64 | ||
6 | WC | 1.24 | ||
52.63 | ||||
25 | 1 | Koridorius | 5.25 | |
2 | WC | 1.38 | ||
3 | Virtuvė | 9.57 | ||
4 | Kambarys | 14.87 | ||
5 | Vonia | 3.55 | ||
6 | Kambarys | 18.59 | ||
53.21 | ||||
26 | 1 | Koridorius | 5.47 | |
2 | Vonia | 3.66 | ||
3 | Kambarys | 14.40 | ||
4 | Virtuvė | 9.48 | ||
5 | WC | 1.14 | ||
6 | Kambarys | 18.79 | ||
52.94 | ||||
27 | 1 | Koridorius | 11.58 | |
2 | Kambarys | 17.73 | ||
3 | Virtuvė | 7.90 | ||
4 | Kambarys | 12.16 | ||
5 | Kambarys | 10.42 | ||
6 | Sandėlis | 1.82 | ||
7 | Vonia | 2.22 | ||
8 | WC | 1.13 | ||
64.96 | ||||
37 | 1 | Koridorius | 8.09 | |
2 | WC | 1.27 | ||
3 | Virtuvė | 9.51 | ||
4 | Kambarys | 13.03 | ||
5 | Vonia | 2.16 | ||
6 | Kambarys | 18.40 | ||
7 | Kambarys | 11.54 | ||
64.00 | ||||
38 | 1 | Koridorius | 8.79 | |
2 | Kambarys | 13.14 | ||
3 | Kambarys | 10.93 | ||
4 | Kambarys | 18.21 | ||
5 | Vonia | 2.21 | ||
6 | Kambarys | 13.07 | ||
7 | Virtuvė | 9.62 | ||
8 | WC | 1.26 | ||
77.23 |
20°C
-54 m3/h
25-5
3.55
PRINCIPINĖ STOVO APRIŠIMO SCHEMA
Išleidimo
Grąžinamo šilumnešio izoliuojamas vamzdis Tiekiamo šilumnešio vamzdis
Grąžinamo šilumnešio vamzdis Rutulinis ventilis
Išleidimo ventilis
Automatinis balansavimo ventilis (STAD + STAP)
Šoninio pajungimo radiatorius su dalikliu Nejudama atrama
+45 m3/h
26-6 1103W
18.79
-36 m3/h
23-5
26-1
5.47
-54 m3/h
26-2
3.66
1199W
+45 m3/h
1173W
25-6
18.59
STAD
Rutulinis ventilis
Magistralinis vamzdynas
ventilis STAP
Oro srauto judėjimo kryptis (per orlaides) Oro srauto judėjimo kryptis (tarp patalpų)
PASTABOS:
1) Aukščiausiose sistemos vietose įrengiami automatiniai nuorintojai, žemiausiose - išleidimo ventiliai;
St. 6
20°C
1.12
834W
20°C
+45 m3/h
26-3
20°C
St. 8
2) Šildymo sistemos magistraliniai vamzmdynai (rūsyje) izoliuojai akmens vatos izoliacija su aliuminio folija;
3) Kiekvienas šildymo stovas turi turėti galimybe atsiskirti nuo sistemos rutulinių ventilių pagalba;
2xd15x1.0
20°C
±36 m3/h
14.40
2xd15x1.0
4) Šildymo sistemos stovai reguliuojami automatiniais balansiniais ventiliais STAD + STAP;
5) Visi radiatorių pajungimai - d15x1.0;
D Šoninio pajungimo
radiatorius 1103 W 22_500_1300
C
26-4
9.48
Šoninio pajungimo radiatorius 834 W 22_500_1000
St. 7
2xd15x1.0
Xxxxxxx pajungimo radiatorius 1199 W 22_500_1400
Šoninio pajungimo radiatorius 1173 W 22_500_1400
BALANSINIAI VENTILIAI STOVAMS BALANSUOTI STAD + STAP:
0 | 2021 | Statybos leidimui, (konkursui) ir statybai | ||||
LAIDA | IŠLEIDIMO DATA | LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA) | ||||
KVAL. PATV. DOK. NR. | UAB "POLISTATYBA" | STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | ||||
STATINIO NUMERIS IR PAVADINIMAS PASTATAS - DAUGIABUTIS GYVENAMASIS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014) | ||||||
27833 | PV | X. Xxxxxxxxxx | ||||
33244 | PDV | X. Xxxxxx | ||||
DOKUMENTO PAVADINIMAS 4 AUKŠTO PLANAS SU ŠILDYMO SISTEMA, M 1:100 | LAIDA | |||||
0 | ||||||
LT | STATYTOJAS IR (ARBA) UŽSAKOVAS UAB "ŠILALĖS ŠILUMOS TINKLAI", MAIRONIO G. 20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 | DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.B-05 | LAPAS | LAPŲ | ||
1 | 1 |
St. 1 (9005W) DN15 STAD nust. padala - 3.68, STAP slėgio perkrytis 17kPa St. 2 (3132W) DN15 STAD nust. padala - 2.29, STAP slėgio perkrytis 17kPa St. 3 (9805W) DN15 STAD nust. padala - 3.88, STAP slėgio perkrytis 17kPa St. 4,15 (4002W) DN15 STAD nust. padala - 2.58, STAP slėgio perkrytis 17kPa St. 5 (10063W) DN15 STAD nust. padala - 3.96, STAP slėgio perkrytis 17kPa St. 6 (6013W) DN15 STAD nust. padala - 3.04, STAP slėgio perkrytis 17kPa St. 7 (10876W) DN20 STAD nust. padala - 2.51, STAP slėgio perkrytis 17kPa St. 8 (6351W) DN15 STAD nust. padala - 3.11, STAP slėgio perkrytis 17kPa St. 9,11 (7182W) DN15 STAD nust. padala - 3.28, STAP slėgio perkrytis 17kPa St. 10 (14168W) DN20 STAD nust. padala - 2.92, STAP slėgio perkrytis 17kPa St. 12,14 (10285W) DN20 STAD nust. padala - 2.42, STAP slėgio perkrytis 17kPa St. 13 (8925W) DN15 STAD nust. padala - 3.66, STAP slėgio perkrytis 17kPa St. 16 (7936W) DN15 STAD nust. padala - 3.43, STAP slėgio perkrytis 17kPa St. 17 (7289W) DN15 STAD nust. padala - 3.30, STAP slėgio perkrytis 17kPa St. 18 (1905W) DN15 STAD nust. padala - 1.76, STAP slėgio perkrytis 17kPa
6) Kiekviename bute keičiamos oro ištraukimo grotelės.
1 2 3 4 5 6
7 8 9
10 11
12 13
St. 19,20,21 (2928W) DN15 STAD nust. padala - 2.21, STAP slėgio perkrytis 17kPa
40-5
2.135
Šoninio pajungimo Šoninio pajungimo radiatorius 1076 W radiatorius 848 W
i ≥2,5%
Šoninio pajungimo radiatorius 848 W
Šoninio pajungimo radiatorius 1400 W
Šoninio pajungimo radiatorius 1282 W
40-4
18.12
1282W
20°C
-54 m /h
979W
20°C
40-6
13.06
Šoninio pajungimo
radiatorius 979 W 22_500_1200
22_500_1300
22_500_1000
22_500_1000
33_500_1200
G
33_500_1100
St. 1
2xd15x1.0
+22.5 m3/h
+22.5 m3/h
St. 17
2xd15x1.0
+45 m3/h
St. 13
2xd15x1.0
15-5
848W
20°C13-3
St. 12
2xd15x1.0
+45 m3/h
Šoninio pajungimo
radiatorius 757 W 22_500_900
40-3
11.12
3
757W
20°C
40-1
8.91
±36 m3/h
40-7
40-8 848W 9.86
Šoninio pajungimo
radiatorius 848 W 22_500_1000
15-4
14.57
1076W
9.63 848W
±36 m3/h 20°C
-36 m3/h
-36 m3/h
9.25
±36 m3/h
13-4
14.36
1400W
K
i ≥2,5%
Šoninio pajungimo radiatorius 727 W
+22.5 m /h
40-2
727W
20°C
1.25
-36 m3/h
20°C
20°C
-54 m3/h
15-3
2.17
15-1
6.63
15-6
1.20
13-2
1.25
Duomenų kaupiklis
13-1
6.21
20°C
-54 m3/h
13-5
2.62
22_500_900
St. 2 13.13 E
2xd15x1.0
J
+22.5 m3/h
836W
Duomenų kaupiklis
-36 m3/h
39-2
±36 m3/h
Šoninio pajungimo
1570W
20°C
14-5
1.21
-90 m3/h
14-4
14-1
4.27
1570W
20°C
Šoninio pajungimo radiatorius 836 W 22_500_1000
39-7
11.56
+30 m3/h
20°C
39-1
8.18
1.25 848W 39-3
20°C 9.63
radiatorius 848 W 22_500_1000
15-2
18.29
St. 9
+45 m3/h
3.06
967W
+90 m3/h
2057W
20°C
14-2
13-6
18.49
+45 m3/h
St. 11
Šoninio pajungimo radiatorius 1307 W 33_500_1100
I
St. 3
2xd15x1.0
1307W
20°C
39-6
18.42
+30 m3/h
39-5
-254.m13/7h
887W
887W
20°C
St. 16
2xd15x1.0
39-4
13.10
+30 m3/h
St. 15
2xd15x1.0
Šoninio pajungimo radiatorius 887 W 22_500_1100
Šoninio pajungimo radiatorius 887 W
2xd15x1.0
Šoninio pajungimo radiatorius 1570 W 33_500_1300
20°C
14-3
7.73
±36 m3/h
Šoninio pajungimo radiatorius 967 W
17.84
St. 10
2xd15x1.0
Šoninio pajungimo radiatorius 2057 W
2xd15x1.0
B
A
Šoninio pajungimo radiatorius 1570 W 33_500_1300
Šoninio pajungimo
20°C
+30 m3/h
+30 m3/h
22_500_1100
22_500_1100
33_500_1600
radiatorius 887 W 22_500_1100
30-4
12.20
30-5
10.38
i ≥2,5%
Šoninio pajungimo
13
Šoninio pajungimo
14 15
16 17 18 19
St. 4
2xd15x1.0
887W
20°C
radiatorius 848 W 22_500_1000
radiatorius 1400 W 33_500_1200
ŠONINIO RADIATORIAUS PAJUNGIMO MAZGAS
H
Šoninio pajungimo radiatorius 967 W
±36 m3/h
30-3
7.77 967W
30-6
1.89
-54 m3/h
848W
20°C
28-3
St. 14
2xd15x1.0
Montuojamas rankinis nuorintojas
Šilumos daliklis
Naujas
radiatorius
Radiatoriaus termostatinis ventilis su termostatine galva (montuojama horizontaliai)
Plieninis
Iš viso:450.96
22_500_1100
Šoninio pajungimo
St. 5
2xd15x1.0
20°C
1222W
20°C
30-7
2.23
-36 m3/h
-36 m3/h
9.57
±36 m3/h
28-4
14.83
+45 m3/h 1400W
20°C
vamzdis
SUTARTINIAI ŽYMĖJIMAI:
Penkto aukšto patalpų eksplikacija | ||||
Aukšto Nr. | Buto Nr. | Patal pos Nr. | Patalpos pavadinimas | Plotas (m2) |
5 | 13 | 1 | Koridorius | 6.21 |
2 | WC | 1.25 | ||
3 | Virtuvė | 9.25 | ||
4 | Kambarys | 14.36 | ||
5 | Vonia | 2.62 | ||
6 | Kambarys | 18.49 | ||
52.18 | ||||
14 | 1 | Koridorius | 4.27 | |
2 | Kambarys | 17.84 | ||
3 | Virtuvė | 7.75 | ||
4 | Vonia | 3.06 | ||
5 | Sandėlis | 1.21 | ||
34.13 | ||||
15 | 1 | Koridorius | 6.63 | |
2 | Kambarys | 18.29 | ||
3 | Vonia | 2.17 | ||
4 | Kambarys | 14.57 | ||
5 | Virtuvė | 9.63 | ||
6 | WC | 1.26 | ||
51.29 | ||||
28 | 1 | Koridorius | 5.35 | |
2 | WC | 1.35 | ||
3 | Virtuvė | 9.57 | ||
4 | Kambarys | 14.83 | ||
5 | Vonia | 3.56 | ||
6 | Kambarys | 18.60 | ||
53.26 | ||||
29 | 1 | Koridorius | 5.50 | |
2 | Vonia | 3.61 | ||
3 | Kambarys | 14.40 | ||
4 | Virtuvė | 9.69 | ||
5 | WC | 1.17 | ||
6 | Kambarys | 18.71 | ||
53.08 | ||||
30 | 1 | Koridorius | 11.65 | |
2 | Kambarys | 17.83 | ||
3 | Virtuvė | 7.77 | ||
4 | Kambarys | 12.20 | ||
5 | Kambarys | 10.38 | ||
6 | Sandėlis | 1.89 | ||
7 | Vonia | 2.23 | ||
8 | WC | 1.16 | ||
65.11 | ||||
39 | 1 | Koridorius | 8.18 | |
2 | WC | 1.25 | ||
3 | Virtuvė | 9.63 | ||
4 | Kambarys | 13.10 | ||
5 | Vonia | 2.17 | ||
6 | Kambarys | 18.42 | ||
7 | Kambarys | 11.56 | ||
64.31 | ||||
40 | 1 | Koridorius | 8.91 | |
2 | Kambarys | 13.13 | ||
3 | Kambarys | 11.12 | ||
4 | Kambarys | 18.12 | ||
5 | Vonia | 2.15 | ||
6 | Kambarys | 13.06 | ||
7 | Virtuvė | 9.86 | ||
8 | WC | 1.25 | ||
77.60 |
Tiekiamo šilumnešio izoliuojamas vamzdis Grąžinamo šilumnešio izoliuojamas vamzdis Tiekiamo šilumnešio vamzdis
radiatorius 1222 W 22_500_1400
F
30-2
17.83
+30 m3/h
30-8
1.16
30-1
11.65
28-2
1.35
Duomenų 28-1
kaupiklis 5.35
-54 m3/h
28-5
3.56
PRINCIPINĖ STOVO APRIŠIMO SCHEMA
Išleidimo
Grąžinamo šilumnešio vamzdis Rutulinis ventilis
Išleidimo ventilis
Automatinis balansavimo ventilis (STAD + STAP)
Šoninio pajungimo radiatorius su dalikliu Nejudama atrama
+45 m3/h
29-6 1333W
18.71
-36 m3/h
29-5
29-1
5.50
-54 m3/h
29-2
3.61
1391W
+45 m3/h
1400W
28-6
18.60
STAD
Rutulinis ventilis
Magistralinis vamzdynas
ventilis STAP
Oro srauto judėjimo kryptis (per orlaides) Oro srauto judėjimo kryptis (tarp patalpų)
PASTABOS:
1) Aukščiausiose sistemos vietose įrengiami automatiniai nuorintojai, žemiausiose - išleidimo ventiliai;
St. 6
20°C
1.17
967W
20°C
+45 m3/h
29-3
20°C
St. 8
2) Šildymo sistemos magistraliniai vamzmdynai (rūsyje) izoliuojai akmens vatos izoliacija su aliuminio folija;
3) Kiekvienas šildymo stovas turi turėti galimybe atsiskirti nuo sistemos rutulinių ventilių pagalba;
2xd15x1.0
20°C
±36 m3/h
14.40
2xd15x1.0
4) Šildymo sistemos stovai reguliuojami automatiniais balansiniais ventiliais STAD + STAP;
5) Visi radiatorių pajungimai - d15x1.0;
D Šoninio pajungimo
radiatorius 1333 W 33_500_1100
C
29-4
9.69
Šoninio pajungimo radiatorius 967 W 22_500_1100
St. 7
2xd15x1.0
Šoninio pajungimo radiatorius 1391 W 33_500_1100
Šoninio pajungimo radiatorius 1400 W 33_500_1200
BALANSINIAI VENTILIAI STOVAMS BALANSUOTI STAD + STAP:
0 | 2021 | Statybos leidimui, (konkursui) ir statybai | ||||
LAIDA | IŠLEIDIMO DATA | LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA) | ||||
KVAL. PATV. DOK. NR. | UAB "POLISTATYBA" | STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | ||||
STATINIO NUMERIS IR PAVADINIMAS PASTATAS - DAUGIABUTIS GYVENAMASIS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014) | ||||||
27833 | PV | X. Xxxxxxxxxx | ||||
33244 | PDV | X. Xxxxxx | ||||
DOKUMENTO PAVADINIMAS 5 AUKŠTO PLANAS SU ŠILDYMO SISTEMA, M 1:100 | LAIDA | |||||
0 | ||||||
LT | STATYTOJAS IR (ARBA) UŽSAKOVAS UAB "ŠILALĖS ŠILUMOS TINKLAI", MAIRONIO G. 20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 | DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.B-06 | LAPAS | LAPŲ | ||
1 | 1 |
St. 1 (9005W) DN15 STAD nust. padala - 3.68, STAP slėgio perkrytis 17kPa St. 2 (3132W) DN15 STAD nust. padala - 2.29, STAP slėgio perkrytis 17kPa St. 3 (9805W) DN15 STAD nust. padala - 3.88, STAP slėgio perkrytis 17kPa St. 4,15 (4002W) DN15 STAD nust. padala - 2.58, STAP slėgio perkrytis 17kPa St. 5 (10063W) DN15 STAD nust. padala - 3.96, STAP slėgio perkrytis 17kPa St. 6 (6013W) DN15 STAD nust. padala - 3.04, STAP slėgio perkrytis 17kPa St. 7 (10876W) DN20 STAD nust. padala - 2.51, STAP slėgio perkrytis 17kPa St. 8 (6351W) DN15 STAD nust. padala - 3.11, STAP slėgio perkrytis 17kPa St. 9,11 (7182W) DN15 STAD nust. padala - 3.28, STAP slėgio perkrytis 17kPa St. 10 (14168W) DN20 STAD nust. padala - 2.92, STAP slėgio perkrytis 17kPa St. 12,14 (10285W) DN20 STAD nust. padala - 2.42, STAP slėgio perkrytis 17kPa St. 13 (8925W) DN15 STAD nust. padala - 3.66, STAP slėgio perkrytis 17kPa St. 16 (7936W) DN15 STAD nust. padala - 3.43, STAP slėgio perkrytis 17kPa St. 17 (7289W) DN15 STAD nust. padala - 3.30, STAP slėgio perkrytis 17kPa St. 18 (1905W) DN15 STAD nust. padala - 1.76, STAP slėgio perkrytis 17kPa
6) Kiekviename bute keičiamos oro ištraukimo grotelės.
1 2 3 4 5 6
7 8 9
10 11
12 13
St. 19,20,21 (2928W) DN15 STAD nust. padala - 2.21, STAP slėgio perkrytis 17kPa
33_500_1100
Nust.-3.8
22_500_900
757 W
Nust.-3.0
1047 W
22_500_1200
Nust.-3.5
595 W
2xd15x1.0
640 W
22_500_800
0.089 m3/h
Nust.-2.7
1047 W
22_500_1200
Nust.-3.5
595 W
2xd18x1.2
640 W
22_500_800
0.163 m3/h
Nust.-2.7
22_500_1200
1047 W
2xd18x1.2
22_500_800
640 W
0.237 m3/h
Nust.-2.7
St. 1.1
2xd22x1.5
Nust.-3.5
Nust.-3.1
834 W
22_500_1000
Nust.-3.1
Nust.-3.1
Nust.-3.4
792 W
22_500_1000
Nust.-3.0
22_500_1000
792 W
22_500_1000
595 W
Nust.-3.4
834 W
22_500_1000
834 W
22_500_1000
792 W
Nust.-3.0
Nust.-3.0
2xd22x1.5
0.311 m3/h palubėje
1905 W
33_900_900
Nust.-5.3
St. 2
2xd15x1.0
0.032 m3/h
2xd15x1.0
0.058 m3/h
2xd15x1.0
0.084 m3/h
2xd15x1.0
0.110 m3/h
22_500_900
St. 3
Nust.-2.9
22_500_700
Nust.-2.5
1307 W
Nust.-3.9
33_500_1100
2xd15x1.0
1096 W
22_500_1300
0.094 m3/h
22_500_700
Nust.-2.5
Nust.-3.5
2xd18x1.2
1096 W
22_500_1300
0.174 m3/h
22_500_700
Nust.-2.5
Nust.-3.5
2xd22x1.5
1096 W
22_500_1300
0.254 m3/h
22_500_800
Nust.-2.6
Nust.-3.5
2xd22x1.5
1340 W
0.334 m3/h
22_500_1000
St. 4,15
Nust.-3.1
725 W
Nust.-2.9
22_500_900
2xd15x1.0
0.039 m3/h
Nust.-2.9
725 W
22_500_900
2xd15x1.0
725 W
0.071 m3/h
Nust.-2.9
22_500_900
2xd15x1.0
859 W
0.103 m3/h
22_500_1000
Nust.-3.2
2xd15x1.0
0.135 m3/h
22_500_1100
St. 5
Nust.-3.2
732 W
1222 W
22_500_1400
Nust.-3.7
Nust.-2.9
22_500_900
2xd15x1.0
1043 W
22_500_1200
0.096 m3/h
Nust.-2.9
732 W
22_500_900
Nust.-3.5
2xd18x1.2
732 W
1043 W
22_500_1200
0.178 m3/h
Nust.-2.9
Nust.-3.5
22_500_900
2xd22x1.5
919 W
1043 W
22_500_1200
0.261 m3/h
22_500_1100
Nust.-3.3
Nust.-3.5
2xd22x1.5
1253 W
0.343 m3/h
St. 6
727 W
836 W
887 W
967 W
1282 W
1333 W
33_500_1100
Nust.-3.9
2xd15x1.0
0.058 m3/h
1103 W
22_500_1300
Nust.-3.6
2xd15x1.0
0.107 m3/h
1103 W
22_500_1300
Nust.-3.6
2xd15x1.0
0.155 m3/h
1103 W
22_500_1300
Nust.-3.6
2xd18x1.2
0.204 m3/h
1371 W
33_500_1100
Nust.-4.0
2xd22x1.5
967 W
22_500_1100
Nust.-3.4
834 W
22_500_1000
Nust.-3.1
834 W
22_500_1000
Nust.-3.1
834 W
22_500_1000
Nust.-3.1
990 W
22_500_1100
Nust.-3.4
St. 7
1391 W
33_500_1100
Nust.-4.1
2xd15x1.0
0.103 m3/h
1199 W
22_500_1400
Nust.-3.7
2xd18x1.2
0.193 m3/h
1199 W
22_500_1400
Nust.-3.7
2xd22x1.5
0.282 m3/h
1199 W
22_500_1400
Nust.-3.7
2xd22x1.5
0.371 m3/h
1429 W
33_500_1100
Nust.-4.2
2xd28x1.5
1400 W
33_500_1200
Nust.-4.1
2xd15x1.0
0.061 m3/h
1173 W
22_500_1400
Nust.-3.7
2xd15x1.0
0.113 m3/h
1173 W
22_500_1400
Nust.-3.7
2xd18x1.2
0.164 m3/h
1173 W
22_500_1400
Nust.-3.7
2xd18x1.2
0.216 m3/h
1432 W
33_500_1200
Nust.-4.2
2xd22x1.5
St. 8
St. 9,11
1570 W
33_500_1300
Nust.-4.7
2xd15x1.0
0.069 m3/h
1334 W
33_500_1100
Nust.-3.9
2xd15x1.0
0.127 m3/h
1334 W
33_500_1100
Nust.-3.9
2xd18x1.2
0.186 m3/h
1334 W
33_500_1100
Nust.-3.9
2xd22x1.5
0.244 m3/h
1610 W
33_500_1300
Nust.-4.8
2xd22x1.5
967 W
22_500_1100
Nust.-3.4
834 W
22_500_1000
Nust.-3.1
834 W
22_500_1000
Nust.-3.1
834 W
22_500_1000
Nust.-3.1
990 W
22_500_1100
Nust.-3.4
St. 10
2057 W
33_500_1600
Nust.-5.5
2xd15x1.0
0.133 m3/h
1851 W
33_500_1400
Nust.-5.2
2xd18x1.2
0.250 m3/h
1851 W
33_500_1400
Nust.-5.2
2xd22x1.5
0.368 m3/h
1851 W
33_500_1400
Nust.-5.2
2xd28x1.5
0.486 m3/h
2099 W
33_500_1600
Nust.-5.6
2xd28x1.5
St. 12,14
848 W
22_500_1000
Nust.-3.1
739 W
22_500_900
Nust.-2.9
739 W
22_500_900
Nust.-2.9
739 W
22_500_900
Nust.-2.9
869 W
22_500_1000
Nust.-3.2
1400 W
33_500_1200
Nust.-4.1
2xd15x1.0
0.099 m3/h
1173 W
22_500_1400
Nust.-3.7
2xd18x1.2
0.182 m3/h
1173 W
22_500_1400
Nust.-3.7
2xd22x1.5
0.266 m3/h
1173 W
22_500_1400
Nust.-3.7
2xd22x1.5
0.350 m3/h
1432 W
33_500_1200
Nust.-4.2
2xd28x1.5
1076 W
22_500_1300
Nust.-3.5
937 W
22_500_1100
Nust.-3.3
937 W
22_500_1100
Nust.-3.3
937 W
22_500_1100
Nust.-3.3
1104 W
22_500_1300
Nust.-3.6
St. 13
848 W
22_500_1000
Nust.-3.1
2xd15x1.0
0.084 m3/h
739 W
22_500_900
Nust.-2.9
2xd15x1.0
0.158 m3/h
739 W
22_500_900
Nust.-2.9
2xd18x1.2
0.231 m3/h
739 W
22_500_900
Nust.-2.9
2xd22x1.5
0.305 m3/h
869 W
22_500_1000
Nust.-3.2
2xd22x1.5
22_500_1100
St. 16
887 W
22_500_1100
Nust.-3.2
2xd15x1.0
732 W
22_500_900
0.076 m3/h
Nust.-2.9
2xd15x1.0
732 W
22_500_900
0.141 m3/h
Nust.-2.9
2xd18x1.2
732 W
22_500_900
0.205 m3/h
Nust.-2.9
2xd22x1.5
919 W
0.270 m3/h
979 W
22_500_1200
848 W
22_500_1000
St. 17
Nust.-3.1
739 W
22_500_900
Nust.-2.9
848 W
22_500_1000
Nust.-3.1
2xd15x1.0
739 W
739 W
22_500_900
0.080 m3/h
22_500_900
Nust.-2.9
Nust.-2.9
2xd15x1.0
739 W
22_500_900
739 W
0.147 m3/h
22_500_900
Nust.-2.9
Nust.-2.9
2xd18x1.2
739 W
22_500_900
0.214 m3/h
869 W
Nust.-3.2
Nust.-2.9
22_500_1000
St. 17.1
620 W
990 W
22_500_1100
2xd22x1.5
0.281 m3/h palubėje
Nust.-3.4
St. 18
1905 W
33_900_900
Nust.-5.3
2xd15x1.0
St. 19,20,21
2928 W
33_900_1300
Nust.-6.8
2xd15x1.0
869 W
0.395 m3/h 9005W
2xd15x1.0
0.137 m3/h 3132W
2xd22x1.5
33_500_1100
Nust.-4.0
0.430 m3/h 9805W
2xd18x1.2
0.175 m3/h 4002W
2xd28x1.5
Nust.-3.8
22_500_1400
0.441 m3/h 10063W
0.264 m3/h 6013W
0.477 m3/h 10876W
0.278 m3/h 6351W
0.315 m3/h 7182W
0.621 m3/h
14168W
0.451 m3/h 10285W
0.391 m3/h 8925W
2xd22x1.5
Nust.-3.3
22_500_1100
0.348 m3/h 7936W
2xd22x1.5
22_500_1000
Nust.-3.2
0.320 m3/h 7289W
0.084 m3/h 1905W
0.128 m3/h 2928W
St. 1.1
2xd22x1.5
0.395 m3/h 9005W
St. 2
2xd15x1.0
0.137 m3/h
0.002
St. 33132W
2xd22x1.5
0.430 m3/h 9805W
-0.432
2xd35x1.5
1.05 m3/h
2xd18x1.2
0.175 m3/h
2xd15x1.0
0.084 m3/h
2xd28x1.5 0.616 m3/h
0.002
St. 4
2xd15x1.0
0.002
0.084 m3/h 1905W
2xd28x1.5
0.478 m3/h
St. 18
2xd15x1.0
0.128 m3/h 2928W
2xd28x1.5 0.796 m3/h
St. 19
2xd28x1.5
0.448 m3/h
2xd22x1.5
0.320 m3/h 7289W
0.002
2xd22x1.5
0.320 m3/h
0.002
St. 16
2xd22x1.5
0.348 m3/h 7936W
-0.400
-0.400
St. 17.1
2xd35x1.5
0.002
1.22 m3/h
4002W
St. 15
2xd18x1.2
0.002
0.175 m3/h
ŠONINIO RADIATORIAUS PAJUNGIMO MAZGAS
2xd28x1.5
0.441 m3/h 10063W
2xd35x1.5
1.66 m3/h
-0.468
St. 5
0.002
2xd35x1.5 0.971 m3/h
St. 20
2xd15x1.0
0.128 m3/h
2xd35x1.5
1.10 m3/h 0.002
4002W
2xd28x1.5
0.451 m3/h 10285W
0.002
2xd35x1.5
1.55 m3/h
St. 14
St. 13
2xd22x1.5
0.391 m3/h
2xd28x1.5
St. 12
Montuojamas rankinis nuorintojas
Šilumos daliklis
Naujas
radiatorius
Radiatoriaus termostatinis ventilis su termostatine galva (montuojama horizontaliai)
Plieninis vamzdis
SUTARTINIAI ŽYMĖJIMAI:
Tiekiamo šilumnešio izoliuojamas vamzdis Grąžinamo šilumnešio izoliuojamas vamzdis
2928W
2xd42x1.5
35368W
0.002
2xd42x1.5
2.52 m3/h
-0.520
0.002
2xd35x1.5 0.971 m3/h
-0.510
22138W
2xd28x1.5
0.579 m3/h
8925W
0.002
0.002
0.002
2xd28x1.5
0.451 m3/h
0.002
0.451 m3/h 10285W
-0.400
PRINCIPINĖ STOVO APRIŠIMO SCHEMA
Tiekiamo šilumnešio vamzdis Grąžinamo šilumnešio vamzdis Rutulinis ventilis
Išleidimo ventilis
Automatinis balansavimo ventilis (STAD + STAP) Šoninio pajungimo radiatorius su dalikliu
St. 6
2xd22x1.5
0.264 m3/h 6013W
2xd42x1.5
1.93 m3/h
-0.494
0.002
St. 7
2xd28x1.5
0.477 m3/h 10876W
2xd42x1.5
2.40 m3/h
0.002
St. 8
2xd22x1.5
0.002
0.278 m3/h 6351W
2.68 m3/h 61152W
2xd35x1.5
1.25 m3/h 28532W
0.002
2xd54x1.5
3.93 m3/h
2xd64x2.0
6.45 m3/h
Šildymo sistemos projektavimo riba
Į šilumos punktą d64x2.0, 6.45 m3/h
147190W
St. 21
2xd15x1.0
0.128 m3/h 2928W
2xd22x1.5
0.315 m3/h 7182W
0.002
St. 11
0 | 2021 | Statybos leidimui, (konkursui) ir statybai | ||||
LAIDA | IŠLEIDIMO DATA | LAIDOS STATUSAS. KEITIMO PRIEŽASTIS (JEI TAIKOMA) | ||||
KVAL. PATV. DOK. NR. | UAB "POLISTATYBA" | STATINIO PROJEKTO PAVADINIMAS DAUGIABUČIO GYVENAMOJO NAMO, D. POŠKOS G. 7, ŠILALĖS M., ATNAUJINIMO (MODERNIZAVIMO) PROJEKTAS | ||||
STATINIO NUMERIS IR PAVADINIMAS PASTATAS - DAUGIABUTIS GYVENAMASIS, D. POŠKOS G. 7, ŠILALĖ (unikalus Nr. 8799-1000-1014) | ||||||
27833 | PV | X. Xxxxxxxxxx | ||||
33244 | PDV | X. Xxxxxx | ||||
DOKUMENTO PAVADINIMAS ŠILDYMO SISTEMOS AKSONOMETRINĖS SCHEMOS | LAIDA | |||||
0 | ||||||
LT | STATYTOJAS IR (ARBA) UŽSAKOVAS UAB "ŠILALĖS ŠILUMOS TINKLAI", MAIRONIO G. 20B, LT-75136, ŠILALĖ, ĮM. K. 176502533 | DOKUMENTO ŽYMUO 1014-1A5p-PA(PM)-TDP-2110-ŠV.B-07 | LAPAS | LAPŲ | ||
1 | 1 |
-0.400
STAD
Rutulinis ventilis
Magistralinis vamzdynas
Išleidimo ventilis
STAP
Nejudama atrama
Oro srauto judėjimo kryptis (per orlaides) Oro srauto judėjimo kryptis (tarp patalpų)
PASTABOS:
1) Aukščiausiose sistemos vietose įrengiami automatiniai nuorintojai, žemiausiose - išleidimo ventiliai;
2) Šildymo sistemos magistraliniai vamzmdynai (rūsyje) izoliuojai akmens vatos izoliacija su aliuminio folija;
3) Kiekvienas šildymo stovas turi turėti galimybe atsiskirti nuo sistemos rutulinių ventilių pagalba;
4) Šildymo sistemos stovai reguliuojami automatiniais balansiniais ventiliais STAD + STAP;
5) Visi radiatorių pajungimai - d15x1.0;
St. 9
2xd22x1.5
0.315 m3/h 7182W
2xd28x1.5 0.936 m3/h
St. 10
2xd28x1.5 0.621 m3/h
14168W
0.002
2xd22x1.5
0.315 m3/h
BALANSINIAI VENTILIAI STOVAMS BALANSUOTI STAD + STAP:
St. 1 (9005W) DN15 STAD nust. padala - 3.68, STAP slėgio perkrytis 17kPa St. 2 (3132W) DN15 STAD nust. padala - 2.29, STAP slėgio perkrytis 17kPa St. 3 (9805W) DN15 STAD nust. padala - 3.88, STAP slėgio perkrytis 17kPa St. 4,15 (4002W) DN15 STAD nust. padala - 2.58, STAP slėgio perkrytis 17kPa St. 5 (10063W) DN15 STAD nust. padala - 3.96, STAP slėgio perkrytis 17kPa St. 6 (6013W) DN15 STAD nust. padala - 3.04, STAP slėgio perkrytis 17kPa St. 7 (10876W) DN20 STAD nust. padala - 2.51, STAP slėgio perkrytis 17kPa St. 8 (6351W) DN15 STAD nust. padala - 3.11, STAP slėgio perkrytis 17kPa St. 9,11 (7182W) DN15 STAD nust. padala - 3.28, STAP slėgio perkrytis 17kPa St. 10 (14168W) DN20 STAD nust. padala - 2.92, STAP slėgio perkrytis 17kPa St. 12,14 (10285W) DN20 STAD nust. padala - 2.42, STAP slėgio perkrytis 17kPa St. 13 (8925W) DN15 STAD nust. padala - 3.66, STAP slėgio perkrytis 17kPa St. 16 (7936W) DN15 STAD nust. padala - 3.43, STAP slėgio perkrytis 17kPa St. 17 (7289W) DN15 STAD nust. padala - 3.30, STAP slėgio perkrytis 17kPa St. 18 (1905W) DN15 STAD nust. padala - 1.76, STAP slėgio perkrytis 17kPa St. 19,20,21 (2928W) DN15 STAD nust. padala - 2.21, STAP slėgio perkrytis 17kPa
6) Kiekviename bute keičiamos oro ištraukimo grotelės.