ADJUSTING BY OWNER’S TAB SERVICES CONTRACTOR. 2.5.1. Ensure recorded data represents actual measured or observed conditions. 2.5.2. Permanently xxxx settings of valves, dampers, and other adjustment devices to allow settings to be restored. Set and lock memory stops. 2.5.3. After adjustments, take measurement to verify balance has not been disrupted or that such disruption has been rectified. 2.5.4. Leave systems in proper working order, replace belt guards, close access doors, close doors to electrical switch boxes, restore thermostats to specified settings, and restore Direct Digital Control System to normal operation. 2.5.5. At Final Inspection, recheck random selections of data recorded in report. Recheck points or areas as selected and witnessed by the Owner.