Auto Transformer Protection. These shall have the following protections: i) Numerical Differential protection ii) Numerical Restricted earth fault protection iii) Numerical Back-up Over-current and earth fault protection on HV & MV side
Appears in 2 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement
Auto Transformer Protection. These shall have the following protections:
- i) Numerical Differential protection
Protection - ii) Numerical Restricted earth fault protection
Earth Fault Protection - iii) Numerical Back-up Over-current Current and earth fault protection Earth Fault Protection on HV & MV High Voltage (HV) and Intermediate Voltage (IV) side
Appears in 2 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement
Auto Transformer Protection. These shall have the following protections:
i) Numerical Differential protection
ii) Numerical Restricted earth fault protection
iii) Numerical Back-up Over-current and earth fault protection on HV & MV side
iv) Numerical Over fluxing protection on HV & MV side
v) Numerical Overload alarm
Appears in 1 contract
Samples: Transmission Service Agreement