Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard: Substation 400 kV side 220 kV side Extension of 400/220 kV Jam Khambhaliya PS (GIS) One and Half Breaker Double Main Scheme Notes: -
AutoNDA by SimpleDocs
Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels ofsubstation/switchyard: Substation 400kV side 220kV side 400/220 kV Fatehgarh-4 P.S One & half breaker (AIS) Double Main & Transfer (AIS) Extn. of 400kV Fatehgarh-3 S/S One & half breaker (AIS) ----- Notes: -
Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard:
Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard: Substation 765 kV side (Future) 400 kV side 220 kV side (Future) 400 kV Bornagar (ISTS) S/s One and Half breaker One and Half breaker Double Main and Transfer i) At 400 kV voltage level, any double circuit line consisting of two numbers of feeders and originating from a transmission or generating switchyard shall not be terminated in one diameter. ii) Two bus reactors of the same HV rating shall also not be connected in the same diameter. iii) A diameter in one and half breaker scheme is a set of 3 circuit breakers with associated isolators, earth switches, current transformers etc. for controlling 2 (two) numbers of feeders. iv) TSP shall plan distribution of line and transformer feeders to bus bar in such a way that all power can be evacuated successfully without crossing the thermal limit at any point of bus bar. v) Connection arrangement of Switchable Line reactors shall be such that it can be used as Line reactor as well as Bus reactor with suitable NGR bypass arrangement.
Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard: Substation 765 kV side 400 kV side Extension of Bareilly (765/400 kV) S/s One and Half breaker One and Half breaker Extension of Bareilly (PG) S/s -- One and Half breaker Notes: -
Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels ofsubstation/switchyard: i) At 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Two transformers of same HV rating shall not be connected in the same diameter and similarly bus reactors of same HV rating shall also not be connected in the same diameter).
Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels ofsubstation/switchyard: Substation 400kV side Extn. of Fatehgarh-3 S/S One & half breaker Extn. of Bhadla-3 S/S One & half breaker Notes: -
AutoNDA by SimpleDocs

Related to Switching Scheme

  • Tandem Switching 4.3.1 The Tandem Switching capability Network Element is defined as: (i) trunk- connect facilities, which include, but are not limited to, the connection between trunk termination at a cross connect panel and switch trunk card; (ii) the basic switch trunk function of connecting trunks to trunks; and (iii) the functions that are centralized in the Tandem Switches (as distinguished from separate end office switches), including but not limited to call recording, the routing of calls to operator services and signaling conversion features.

  • Local Switching Interfaces 4.2.13.1 Global Connection shall order ports and associated interfaces compatible with the services it wishes to provide, as listed in Exhibit B. BellSouth shall provide the following local switching interfaces:

  • Switching and Tagging Rules Each Party shall provide the other Parties a copy of its switching and tagging rules that are applicable to the other Parties’ activities. Such switching and tagging rules shall be developed on a non-discriminatory basis. The Parties shall comply with applicable switching and tagging rules, as amended from time to time, in obtaining clearances for work or for switching operations on equipment.

  • Switching All of the negotiated rates, terms and conditions set forth in this Section pertain to the provision of local and tandem switching.

  • Packet Switching Capability 4.5.1 The packet switching capability network element is defined as the function of routing or forwarding packets, frames, cells or other data units based on address or other routing information contained in the packets, frames, cells or other data units.

  • Local Circuit Switching Capability, including Tandem Switching Capability 4.2.1 Local circuit switching capability is defined as: (A) line-side facilities, which include, but are not limited to, the connection between a loop termination at a main distribution frame and a switch line card; (B) trunk-side facilities, which include, but are not limited to, the connection between trunk termination at a trunk-side cross-connect panel and a switch trunk card; (C) switching provided by remote switching modules; and (D) all features, functions, and capabilities of the switch, which include, but are not limited to: (1) the basic switching function of connecting lines to lines, line to trunks, trunks to lines, and trunks to trunks, as well as the same basic capabilities made available to BellSouth’s customers, such as a telephone number, white page listings, and dial tone; and (2) all other features that the switch is capable of providing, including but not limited to customer calling, customer local area signaling service features, and Centrex, as well as any technically feasible customized routing functions provided by the switch. Any features that are not currently available but are technically feasible through the switch can be requested through the BFR/NBR process.

  • Leave Plan Effective April the Hospital agrees to introduce a leave program, funded solely by the nurse, subject to the following terms and conditions:

  • Provision for Local Switching 4.2.12.1 BellSouth shall perform routine testing (e.g., Mechanized Loop Tests (MLT) and test calls such as 105, 107 and 108 type calls) and fault isolation on a mutually agreed upon schedule.

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!