Common use of Class Year Interconnection Facilities Study Procedures Clause in Contracts

Class Year Interconnection Facilities Study Procedures. The ISO shall coordinate the Class Year Interconnection Facilities Study with the Connecting Transmission Owner and Affected Transmission Owners, and with any other Affected System pursuant to Section 30.3.5 above. The ISO shall utilize existing studies to the extent practicable in performing the Class Year Interconnection Facilities Study, including any deliverability analyses from the System Reliability Impact Study, as applicable. The ISO may request additional information from the Developer and Connecting Transmission Owner as may reasonably become necessary consistent with Good Utility Practice during the course of the Class Year Interconnection Facilities Study. Upon request from the ISO for additional information required for or related to the Class Year Interconnection Facilities Study, the Developer and Connecting Transmission Owner shall provide such additional information in a prompt manner. The ISO shall follow the procedures set forth in Attachment S of the ISO OATT and shall use Reasonable Efforts to complete the study and issue a Class Year Interconnection Facilities Study report to the Class Year Projects within the timeframe called for in Attachment S. At the request of any Class Year Project, or at any time the ISO determines that it will not meet the required time frame for completing the Class Year Interconnection Facilities Study, the ISO shall notify the Class Year Projects as to the schedule status of the Class Year Interconnection Facilities Study. If the ISO is unable to complete the Class Year Interconnection Facilities Study and issue a cost allocation report within the time required, it shall notify the Class Year Projects and provide an estimated completion date and an explanation of the reasons why additional time is required. Upon request, the ISO shall provide each Class Year Project supporting documentation, workpapers, and databases or data developed in the preparation of the Class Year Interconnection Facilities Study, subject to non-disclosure arrangements consistent with Section 30.13.1.

Appears in 30 contracts

Samples: Standard Large Generator Interconnection Agreement, Study Agreement, nyisoviewer.etariff.biz

AutoNDA by SimpleDocs

Class Year Interconnection Facilities Study Procedures. The ISO shall coordinate the Class Year Interconnection Facilities Study with the Connecting Transmission Owner and Affected Transmission Owners, and with any other Affected System pursuant to Section 30.3.5 above. The ISO shall utilize existing studies to the extent practicable in performing the Class Year Interconnection Facilities Study, including any deliverability analyses from the System Reliability Impact Study, as applicable. The ISO may request additional information from the Developer and Connecting Transmission Owner as may reasonably become necessary consistent with Good Utility Practice during the course of the Class Year Interconnection Facilities Study. Upon request from the ISO for additional information required for or related to the Class Year Interconnection Facilities Study, the Developer and Connecting Transmission Owner shall provide such additional information in a prompt manner. The ISO shall follow the procedures set forth in Attachment S of the ISO OATT and shall use Reasonable Efforts to complete the study and issue a Class Year Interconnection Facilities Study report to the Class Year Projects within the timeframe called for in Attachment S. At the request of any Class Year Project, or at any time the ISO determines that it will not meet the required time frame for completing the Class Year Interconnection Facilities Study, the ISO shall notify the Class Year Projects as to the schedule status of the Class Year Interconnection Facilities Study. If the ISO is unable to complete the Class Year Interconnection Facilities Study and issue a cost allocation report within the time required, it shall notify the Class Year Projects and provide an estimated completion date and an explanation of the reasons why additional time is required. Upon request, the ISO shall provide each Class Year Project supporting documentation, workpapers, and databases or data developed in the preparation of the Class Year Interconnection Facilities Study, subject to non-disclosure arrangements consistent with Section 30.13.1.

Appears in 11 contracts

Samples: Service Agreement, Study Agreement, nyisoviewer.etariff.biz

Class Year Interconnection Facilities Study Procedures. The ISO NYISO shall coordinate the Class Year Interconnection Facilities Study with the Connecting Transmission Owner Owners and Affected Transmission Owners, and with any other Affected System pursuant to Section 30.3.5 above. The ISO NYISO shall utilize existing studies to the extent practicable in performing the Class Year Interconnection Facilities Study, including any deliverability analyses from the System Reliability Impact Study, as applicable. The ISO may request additional information from the Developer and Connecting Transmission Owner as may reasonably become necessary consistent with Good Utility Practice during the course of the Class Year Interconnection Facilities Study. Upon request from the ISO for additional information required for or related to the Class Year Interconnection Facilities Study, the Developer and Connecting Transmission Owner shall provide such additional information in a prompt manner. The ISO NYISO shall follow the procedures set forth in Attachment S of the ISO NYISO OATT and shall use Reasonable Efforts to complete the study and issue a Class Year Interconnection Facilities Study report to the Class Year Projects within the timeframe called for in Attachment S. At the request of any Class Year Project, or at any time the ISO NYISO determines that it will not meet the required time frame for completing the Class Year Interconnection Facilities Study, the ISO NYISO shall notify the Class Year Projects as to the schedule status of the Class Year Interconnection Facilities Study. If the ISO NYISO is unable to complete the Class Year Interconnection Facilities Study and issue a cost allocation report within the time required, it shall notify the Class Year Projects and provide an estimated completion date and an explanation of the reasons why additional time is required. Upon request, the ISO NYISO shall provide each Class Year Project supporting documentation, workpapers, and databases or data developed in the preparation of the Class Year Interconnection Facilities Study, subject to non-disclosure arrangements consistent with Section 30.13.1.

Appears in 9 contracts

Samples: nyisoviewer.etariff.biz, nyisoviewer.etariff.biz, nyisoviewer.etariff.biz

Class Year Interconnection Facilities Study Procedures. The ISO NYISO shall coordinate the Class Year Interconnection Facilities Study with the Connecting Transmission Owner Owners and Affected Transmission Owners, and with any other Affected System pursuant to Section 30.3.5 above. The ISO NYISO shall utilize existing studies to the extent practicable in performing the Class Year Interconnection Facilities Study, including any deliverability analyses from the System Reliability Impact Study, as applicable. The ISO may request additional information from the Developer and Connecting Transmission Owner as may reasonably become necessary consistent with Good Utility Practice during the course of the Class Year Interconnection Facilities Study. Upon request from the ISO for additional information required for or related to the Class Year Interconnection Facilities Study, the Developer and Connecting Transmission Owner shall provide such additional information in a prompt manner. The ISO NYISO shall follow the procedures set forth in Attachment S of the ISO NYISO OATT and shall use Reasonable Efforts to complete the study and issue a Class Year Interconnection Facilities Study report to the Class Year Projects DeveloperProjects within the timeframe called for in Attachment S. At the request of any Class Year ProjectDeveloperProject, or at any time the ISO NYISO determines that it will not meet the required time frame for completing the Class Year Interconnection Facilities Study, the ISO NYISO shall notify the Class Year Projects DevelopersProjects as to the schedule status of the Class Year Interconnection Facilities Study. If the ISO NYISO is unable to complete the Class Year Interconnection Facilities Study and issue a cost allocation report within the time required, it shall notify the Class Year Projects DevelopersProjects and provide an estimated completion date and an explanation of the reasons why additional time is required. Upon request, the ISO NYISO shall provide each Class Year Project DeveloperProject supporting documentation, workpapers, and databases or data developed in the preparation of the Class Year Interconnection Facilities Study, subject to confidentiality non-disclosure arrangements consistent with Section 30.13.1.

Appears in 2 contracts

Samples: nyisoviewer.etariff.biz, nyisoviewer.etariff.biz

AutoNDA by SimpleDocs

Class Year Interconnection Facilities Study Procedures. The ISO NYISOISO shall coordinate the Class Year Interconnection Facilities Study with the Connecting Transmission Owner Owners and Affected Transmission Owners, and with any other Affected System pursuant to Section 30.3.5 above. The ISO NYISOISO shall utilize existing studies to the extent practicable in performing the Class Year Interconnection Facilities Study, including any deliverability analyses from the System Reliability Impact Study, as applicable. The ISO may request additional information from the Developer and Connecting Transmission Owner as may reasonably become necessary consistent with Good Utility Practice during the course of the Class Year Interconnection Facilities Study. Upon request from the ISO for additional information required for or related to the Class Year Interconnection Facilities Study, the Developer and Connecting Transmission Owner shall provide such additional information in a prompt manner. The ISO NYISOISO shall follow the procedures set forth in Attachment S of the ISO NYISOISO OATT and shall use Reasonable Efforts to complete the study and issue a Class Year Interconnection Facilities Study report to the Class Year Projects within the timeframe called for in Attachment S. At the request of any Class Year Project, or at any time the ISO NYISOISO determines that it will not meet the required time frame for completing the Class Year Interconnection Facilities Study, the ISO ISONYISO shall notify the Class Year Projects as to the schedule status of the Class Year Interconnection Facilities Study. If the ISO NYISOISO is unable to complete the Class Year Interconnection Facilities Study and issue a cost allocation report within the time required, it shall notify the Class Year Projects and provide an estimated completion date and an explanation of the reasons why additional time is required. Upon request, the ISO NYISOISO shall provide each Class Year Project supporting documentation, workpapers, and databases or data developed in the preparation of the Class Year Interconnection Facilities Study, subject to non-disclosure arrangements consistent with Section 30.13.1.

Appears in 2 contracts

Samples: nyisoviewer.etariff.biz, nyisoviewer.etariff.biz