Conductor resistance test. The D.C. resistance of the conductor of the completed cable shall be measured and, when corrected to 20 Co, shall not exceed the guaranteed values stated in the schedule of particulars and guarantees and also shall not exceed the appropriate value specified in IEC 60228.
Appears in 7 contracts
Samples: Call Off Contract, Call Off Contract, Call Off Contract
Conductor resistance test. The D.C. resistance of the conductor of the completed cable shall be measured and, when corrected to 20 Co20°C, shall not exceed the guaranteed values stated in the schedule of particulars and guarantees and also shall not exceed the appropriate value specified in IEC 60228.
Appears in 1 contract
Samples: Call Off Contract