Common use of Conductor resistance test Clause in Contracts

Conductor resistance test. The D.C. resistance of the conductor of the completed cable shall be measured and, when corrected to 20 Co, shall not exceed the guaranteed values stated in the schedule of particulars and guarantees and also shall not exceed the appropriate value specified in IEC 60228.

Appears in 7 contracts

Samples: Call Off Contract, Call Off Contract, Call Off Contract

AutoNDA by SimpleDocs

Conductor resistance test. The D.C. resistance of the conductor of the completed cable shall be measured and, when corrected to 20 Co20°C, shall not exceed the guaranteed values stated in the schedule of particulars and guarantees and also shall not exceed the appropriate value specified in IEC 60228.

Appears in 1 contract

Samples: Call Off Contract