Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control center. Each breaker would have two sets of trip circuits which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/local whereas the earth switches shall have local control only.
Appears in 13 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement, Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control center. Each breaker would have two sets of trip circuits which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/local whereas the earth switches shall have local control only.
Appears in 12 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement, Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control center. Each breaker would have two sets of trip circuits which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/remote/ local whereas the earth switches shall have local control only.. [Signatures of LTTCs]
Appears in 1 contract
Samples: Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/substation/ switching stations shall be controlled and synchronized from the switchyard control room/room/ remote control center. Each breaker would have two sets of trip circuits which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/remote/ local whereas the earth switches shall have local control only.
Appears in 1 contract
Samples: Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control center. Each breaker would have two sets of trip circuits circuits, which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/local whereas the earth switches shall have local control only.
Appears in 1 contract
Samples: Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control centercentre. Each breaker would have two sets of trip circuits which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/local whereas the earth switches shall have local control only.
Appears in 1 contract
Samples: Transmission Service Agreement