Control Room Environmental Features Sample Clauses

Control Room Environmental Features. Contractor shall provide a HMI console with due attention and consideration of environmental and ergonomic features. · CR access shall be controlled (e.g., via swipe card/electronic key) · CR shall house only Operations personnel under normal Plant conditions · Ceiling finish treatment shall be dark grey color and designed for glare reduction · Ceiling height shall be 12 feet minimum. · Full-spectrum, DC lighting shall be used to avoid flicker · Controlled exterior lighting shall be used · Indirect lighting shall be used to the maximum extent · Lighting design shall be provided by a licensed Alaska electrical designer/consultant engineer. · 100% CR lighting shall be on UPS · Monitor shall not flicker, particularly if AC lighting is used, and non-glare screens · Ergonomic evaluation shall consider the use of two or single tier levels for the monitor screens · The ergonomic evaluation shall consider using adjustable height control consoles, possibly with independent splits Control Room Miscellaneous Features: The following miscellaneous Control Room features shall be included: · Remote monitoring for all administrative support systems shall be located in CR (security, fire protection, water analysis, HVAC, CEMS, weather, etc.) · Electronic copies and hardcopies of Plant technical data shall be available in the CR. · Contractor shall be formally design the routing and layout of DCS cabling and shall provide an accessible, expandable DCS cable management system.