Controls and Integration. The existing RTU is sufficient for the scope of this project with the following modifications: o one (1) new I/O card will be installed to accommodate the additions required; o one (1) RE-01 control handle capable of remote operation for breaker R30 shall be installed to allow for the manual trip(open)/close operation and to provide status of the trip coil(s); and o one (1) RE-43A/M control handle capable of remote operation for breaker R30 shall be installed to allow for enabling/disabling of the automatic reclose function.
Appears in 4 contracts
Samples: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Interconnection Agreement
Controls and Integration. The existing RTU is RTUs are sufficient for the scope of this project with the following modifications: o one (1) new I/O card will be installed to accommodate the additions required; o one (1) RE-01 control handle capable of remote operation for breaker R30 R3 shall be installed to allow for the manual trip(open)/close operation and to provide status of the trip coil(s); and o one (1) RE-43A/M control handle capable of remote operation for breaker R30 R3 shall be installed to allow for enabling/disabling of the automatic reclose function.
Appears in 3 contracts
Samples: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Interconnection Agreement