Description of New Facility. The Interconnection Customer is expanding the Existing Facility to increase its maximum output capability by 6.4 MW, for a total nameplate capacity of 9.2 MW (“New Facility”). The New Facility will consist of the following equipment: Four (4) Caterpillar Model 3520 Engine Generator Sets, 1.6 MW, 2 MVA, with a power factor range of 0.80 lagging to 0.90 leading, giving a total reactive capability for all four units of +4.8 MVAR to -3.10 MVAR at the generator terminals; One (1) three-phase 4160 (Delta)-480 /277 V (Wye), 500 kVA transformer, 60 kV BIL, 6.5% impedance; One (1) main circuit breaker 4.16 kV, 1200 A, 40 kAIC, 60 kV BIL; One (1) (ancillary circuit load breaker) 4.16 kV, 1200 A, 40 kAIC, 60 kV BIL; Four (4) generator circuit breakers 4.16 kV, 1200 A, 40 kAIC, 60 kV BIL; Two (2) 4.16 kV buses that will accommodate connection and protection controls; Utility interconnection protection equipment and relaying controls; and Two (2) (main feeder switches) 7.2 kV, 1200 A load break switches, 61 kAIC, 60 kV BIL. The interconnection of the new facilities will be completed in four (4) phases. The Interconnection Customer will initially install and energize two of the four new generators (3.2 MW); the remaining 3.2 MW will be installed and energized by the end of 2015. Specifically each of the four phases will encompass the following: Phase 1: Interconnection of two (2) of the four (4) 1.6 MW units; Phase 2: Generator Lead Line relocation modifications (see Section II.B below); Phase 3: Interconnection of the third 1.6 MW unit; and