Common use of Description of New Facility Clause in Contracts

Description of New Facility. As depicted in Figure 1 to Appendix A, the New Facility is comprised of the following additions to the Existing Facility: ● One (1) new min flow generator: 3-phase, 2.7 MW (nameplate @ 0.9 power factor)/3 MVA; ● One (1) turbine (Unit 2): 3,420 HP, 600 RPM, rated for 100.8 feet of head; ● Six (6) 5.1kV MCOV station class surge arrestors; ● Three (3) surge capacitors (0.25 µF); ● One (1) air circuit breaker (generator breaker R22): 4.16 kV, 1200 A, 550 kV BIL, 25 kA; ● One (1) three phase, two winding, 13.2 kV/480 V delta-delta, 450 kVA station service transformer with an impedance of 5.1% replacing the existing station service transformer;