Design and Operating Requirements. Each generation facility which is or can be connected to the Company's electric system shall be designed and operated so as to prevent or protect against the following adverse conditions on the Company's system. These conditions can cause electric service degradation, equipment damage, or harm to persons: 1. Inadvertent and unwanted re-energization of a utility dead line or bus. 2. Interconnection while out of synchronization.
Appears in 10 contracts
Samples: Power Purchase Contract (Ormat Technologies, Inc.), Power Purchase Agreement (Berry Petroleum Co), Power Purchase Agreement (Berry Petroleum Co)
Design and Operating Requirements. Each generation facility which is or can be connected to the Company's electric system shall be designed and operated so as to prevent or protect against the following adverse conditions on the Company's system. These conditions can cause electric service degradation, equipment damage, or of harm to persons:
1. Inadvertent and unwanted re-energization of a utility dead line or bus.
2. Interconnection while out of synchronizationsynchronizaton.
Appears in 1 contract
Design and Operating Requirements. Each generation facility which is or can be connected to the Company's electric system shall be designed and operated so as to prevent or protect against the following adverse conditions on the Company's system. These conditions can cause electric service degradation, equipment damage, or harm to persons:
1. Inadvertent and unwanted re-energization of a utility dead line or bus.
2. Interconnection while out of synchronizationsynchronizaton.
Appears in 1 contract
Design and Operating Requirements. Each generation facility which is or can be connected to the Company's electric system shall be designed and operated so as to prevent or protect against the following adverse conditions on the Company's system. These conditions can cause electric service degradation, equipment damage, or harm to persons:.
1. Inadvertent and unwanted re-energization of a utility dead line or bus.
2. Interconnection while out of synchronization.
3. Overcurrent
4. Utility system load imbalance 5. Ground faults
Appears in 1 contract
Samples: Parallel Generation Agreement (Ridgewood Electric Power Trust I)
Design and Operating Requirements. Each generation facility which is or can be connected to the Company's electric system shall be designed and operated so as to prevent or protect against the following adverse conditions on the Company's system. These conditions can cause electric service degradation, equipment damage, or harm to persons:
1. Inadvertent and unwanted re-energization of a utility dead line deadline or bus.
2. Interconnection while out of synchronization.
Appears in 1 contract
Samples: Power Purchase Contract (Zond Windsystem Partners LTD Series 85-B)
Design and Operating Requirements. Each generation facility which is or can be connected to the Company's electric system shall be designed and operated so as to prevent or protect against the following adverse conditions on the Company's system. These conditions can cause electric service degradation, equipment damage, or harm ____ to persons:
1. Inadvertent and unwanted re-energization of a utility dead ____ line or bus.
2. Interconnection while out of synchronization.
Appears in 1 contract