Determination of Rated Capacity and Creation of Ambient Facility Output Table. The Seller shall perform the calculation of Rated Capacity correcting the measured data to the following adjustments: The net output for each data interval shall be adjusted to Contract Conditions by first adjusting for differences, if any, between the ambient relative humidity for that data interval and Contract Conditions using the performance curves provided by the manufacturer then adjusting that result for differences, if any, between the ambient barometric pressure for that data interval and Contract Conditions using the performance curves provided by the manufacturer, and, finally, adjusting that result for differences, if any, between the ambient temperature for that data interval and Contract Conditions using the manufacturer’s performance curve . Using the resulting net output data from this sequential, three-step adjustment process, the net kW output at Contract Conditions at the Energy Delivery Point shall be calculated for each of the sixteen (16) consecutive fifteen (15) minute intervals comprising the test. The average of the sixteen average net kW values thus calculated shall be the Rated Capacity.