Fault Protection. Since there is no plant step up (“PSU”) transformer, the Interconnection Customer must provide protection that will operate instantaneously for all faults on its 34.5kV system. Two (2) independent protection systems must be used as the protection is required for coordination. Each of the two schemes must operate separate lockout relays to trip and block the necessary breakers.