General technical characteristics. a) Thermal limit transmission capacity The minimum thermal limit capacity (design power) of the lines shall be: TRANSMISSION LINE MINIMUM TRANSMISSION CAPACITY PER THERMAL LIMIT L.T. 220 xX Xxxxxxx – Nueva Tumbes 250 MVA Compliance with the indicated capacity shall be verified for the environmental conditions set out in Chapter 1, Paragraph 3.1.1, of Annex 1 of PR-20, the main requirements of which are: - The temperature in phase conductors shall not exceed the thermal limit of 75 °C. - The maximum room temperature is the maximum average temperature of the region in which the line is installed. It represents the average of the annual maximums for a minimum period of 10 years. - The solar radiation is the maximum recorded in the region in which the line is installed. - Minimum wind of 0,61 m/s perpendicular to the conductor. The safety distances shall be respected in all operating conditions. It is recommended to consider, to ensure compliance with the safety distances, a minimum reserve margin of 0,30 m during the distribution of the structures.
Appears in 2 contracts
General technical characteristics. a) Thermal limit transmission capacity The minimum thermal limit capacity (design power) of the lines shall be: TRANSMISSION LINE MINIMUM THERMAL LIMIT TRANSMISSION CAPACITY PER THERMAL LIMIT L.T. 220 xX Xxxxxxx kV Nueva Xxxxx Xxxxx – Nueva Tumbes Aguaytía, TL 250 MVA Compliance with the indicated capacity shall be verified for the environmental conditions set out in Chapter 1, Paragraph 3.1.1, of Annex 1 of PR-20, the main requirements of which are: - The temperature in phase conductors shall not exceed the thermal limit of 75 °C. - The maximum room temperature is the maximum average temperature of the region in which the line is installed. It represents the average of the annual maximums for a minimum period of 10 years. - The solar radiation is the maximum recorded in the region in which the line is installed. - Minimum wind of 0,61 m/s perpendicular to the conductor. The safety distances shall be respected in all operating conditions. It is recommended to consider, to ensure compliance with the safety distances, a minimum reserve margin of 0,30 m during the distribution of the structures.
Appears in 2 contracts
General technical characteristics. a) Thermal limit transmission capacity The minimum thermal limit capacity (design power) of the lines shall be: TRANSMISSION LINE MINIMUM THERMAL LIMIT TRANSMISSION CAPACITY PER THERMAL LIMIT L.T. 220 xX Xxxxxxx kV Nueva Tingo María – Nueva Tumbes Aguaytía, TL 250 MVA Compliance with the indicated capacity shall be verified for the environmental conditions set out in Chapter 1, Paragraph 3.1.1, of Annex 1 of PR-20, the main requirements of which are: - The temperature in phase conductors shall not exceed the thermal limit of 75 °C. - The maximum room temperature is the maximum average temperature of the region in which the line is installed. It represents the average of the annual maximums for a minimum period of 10 years. - The solar radiation is the maximum recorded in the region in which the line is installed. - Minimum wind of 0,61 m/s perpendicular to the conductor. The safety distances shall be respected in all operating conditions. It is recommended to consider, to ensure compliance with the safety distances, a minimum reserve margin of 0,30 m during the distribution of the structures.
Appears in 1 contract
Samples: SGT Concession Contract