Illumination. Normal & emergency AC & DC illumination shall be provided adequately in the control room & other buildings of the substation. The switchyard shall also be provided with adequate illumination. Lighting of the entire control room building, fire-fighting pump house, other building (if any) and switchyard shall be done by LED based low power consumption luminaires.
Appears in 10 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement, Transmission Service Agreement
Illumination. Normal & and emergency AC & and DC illumination shall be provided adequately in the control room & and other buildings of the substation. The switchyard shall also be provided with adequate illumination. Lighting The lighting of the entire control room building, fire-fighting pump house, other building (if any) and switchyard shall be done by LED based low power consumption luminairesluminaries.
Appears in 7 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement, Transmission Service Agreement
Illumination. Normal & emergency AC & DC illumination shall be provided adequately in the control room & other buildings of the substation. The switchyard shall also be provided with adequate illumination. Lighting of the entire control room building, fire-fighting pump house, other building (if any) and switchyard shall be done by LED based low power consumption luminairesluminaries.
Appears in 5 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement, Transmission Service Agreement
Illumination. Normal & and emergency AC & and DC illumination shall be provided adequately in the control room & and other buildings of the substation. The switchyard shall also be provided with adequate illumination. Lighting of the entire control room building, fire-fighting pump house, other building (if any) and switchyard shall be done by LED based low power consumption luminairesluminaries.
Appears in 4 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement, Transmission Service Agreement
Illumination. Normal & and emergency AC & and DC illumination shall be provided adequately in the control room & and other buildings of the substation. The switchyard shall also be provided with adequate illumination. Lighting The lighting of the entire control room building, fire-fighting pump house, other building buildings (if any) and switchyard shall be done by LED based low power consumption luminairesluminaries.
Appears in 3 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement, Transmission Service Agreement
Illumination. Normal & emergency AC & DC illumination shall be provided adequately in the control switchyard panel room & other buildings of the substation. The switchyard shall also be provided with adequate illumination. Lighting of the entire control switchyard panel room building, fire-fighting pump house, building and other building (if any) and switchyard shall be done by LED based low power consumption luminairesluminaries.
Appears in 2 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement
Illumination. Normal & and emergency AC & and DC illumination shall be provided adequately in the control room & and other buildings of the substation. The switchyard shall also be provided with adequate illumination. The Lighting of the entire control room building, fire-fighting pump house, other building (if any) and switchyard shall be done by LED based low power consumption luminairesluminaries.
Appears in 2 contracts
Samples: Transmission Service Agreement, Transmission Service Agreement
Illumination. Normal & emergency AC & and DC illumination shall be provided adequately in the control room & and other buildings of the substation. The switchyard shall also be provided with adequate illumination. Lighting of the entire control room building, fire-fighting pump house, other building (if any) and switchyard switch yard shall be done by LED based low power consumption luminaires.
Appears in 1 contract
Samples: Transmission Service Agreement
Illumination. Normal & and emergency AC & and DC illumination shall be provided adequately in the control room & and other buildings of the substation. The switchyard shall also be provided with adequate illumination. Lighting The lighting of the entire control room building, fire-fighting pump house, other building (if any) and switchyard shall be done by LED based low power consumption luminaires.
Appears in 1 contract
Samples: Transmission Service Agreement
Illumination. Normal & emergency AC & DC illumination shall be provided adequately in the control room & other buildings of the substation. The switchyard shall also be provided with adequate illumination. Lighting of the entire control room building, fire-fighting pump house, other building (if any) and switchyard shall be done by LED based low power consumption luminaires.
Appears in 1 contract
Samples: Transmission Service Agreement