Isolation from the Transmission System. 1.2.1. The Customer shall provide an isolating disconnect switch or device at the point or junction between the Transmitter and the Customer, i.e., at the point of the interconnection, which physically and visually opens the main current-carrying path and isolates the Customer’s facility from the transmission system. 1.2.2. The isolating disconnect switch shall meet the following criteria: 1.2.2.1. it shall simultaneously open all phases (i.e., group-operated open/close) to the connection; 1.2.2.2. it shall be lockable in the open and closed positions; 1.2.2.3. when the device is used as part of the HVI failure protection system, it shall be motor-operated and equipped with appropriate control circuitry; and 1.2.2.4. it shall be suitable for safe operation under the conditions of use.
Appears in 5 contracts
Samples: Connection Agreement, Connection Agreement, Connection Agreement
Isolation from the Transmission System. 1.2.1. The Customer shall provide an isolating disconnect switch or device at the point or junction between the Transmitter and the Customer, i.e., at the point of the interconnection, which physically and visually opens the main current-carrying path and isolates the Customer’s =s facility from the transmission system.
1.2.2. The isolating disconnect switch shall meet the following criteria:
1.2.2.1. it shall simultaneously open all phases (i.e., group-operated open/close) to the connection;
1.2.2.2. it shall be lockable in the open and closed positions;
1.2.2.3. when the device is used as part of the HVI failure protection system, it shall be motor-operated and equipped with appropriate control circuitry; and
1.2.2.4. it shall be suitable for safe operation under the conditions of use.
Appears in 3 contracts
Samples: Connection Agreement, Connection Agreement, Connection Agreement
Isolation from the Transmission System. 1.2.1. The Customer shall provide an isolating disconnect switch or device at the point or junction between the Transmitter and the Customer, i.e., at the point of the interconnection, which physically and visually opens the main current-carrying path and isolates the Customer’s facility from the transmission system.
1.2.2. The isolating disconnect switch shall meet the following criteria:
1.2.2.1. it shall simultaneously open all phases (i.e., group-operated open/close) to the connection;
1.2.2.2. it shall be lockable in the open and closed positions;
1.2.2.3. when the device is used as part of the HVI failure protection system, it shall be motor-motor- operated and equipped with appropriate control circuitry; and
1.2.2.4. it shall be suitable for safe operation under the conditions of use.
Appears in 2 contracts
Samples: Connection Agreement, Connection Agreement