Miscellaneous Loads Sample Clauses

Miscellaneous Loads. 6.1.1.1 Domestic electric water heaters, shall be fed from dedicated 208V, three phase or single phase circuits. 6.1.1.2 Electric unit heaters shall be fed from dedicated 208V (through 10 kW) or ▇▇▇▇ (▇▇▇▇▇ ▇▇ ▇▇), ▇▇▇▇▇-▇▇▇▇▇, ▇▇▇▇▇-▇▇▇▇ circuits. 6.1.1.3 Evaporative coolers, if used, shall be fed from dedicated 480V single-phase, two-pole circuits. 6.1.1.4 Kitchen ovens and range tops will be fed from dedicated 208V, three-phase or single phase circuits. If 240V service is required, the Building Contractor shall furnish and install a suitably sized 480-240/120V single-phase transformer for this purpose. 6.1.1.5 Ventilation and restroom or kitchen exhaust fans will be fed from dedicated 120V circuits. The kitchen sink garbage disposal shall be fed from a dedicated 120V GFCI circuit.
Miscellaneous Loads a. Domestic electric water heaters shall be fed from dedicated 208 V, threephase or single phase circuits. b. Ventilation and restroom or kitchen exhaust fans shall be fed from dedicated 120 V circuits. The kitchen sink garbage disposal shall be fed from a dedicated 120 V GFCI circuit.