Common use of Power circuits Clause in Contracts

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 circuits terminating in National Electrical Manufacturers Association (NEMA) 5-20R 5 6-30R receptacle for the server room.

Appears in 4 contracts

Samples: apps.azdot.gov, apps.azdot.gov, apps.azdot.gov

AutoNDA by SimpleDocs

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 circuits terminating in National Electrical Manufacturers Association (NEMA) NEMA 5-20R 5 6-30R receptacle for the server room.receptacles and one dedicated isolated ground

Appears in 3 contracts

Samples: apps.azdot.gov, apps.azdot.gov, apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 30 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 31 circuits terminating in National Electrical Manufacturers Association (NEMA) NEMA 5-20R 5 receptacles and one dedicated isolated ground 32 30-amp circuit terminating in a NEMA 6-30R receptacle for the server room.

Appears in 3 contracts

Samples: apps.azdot.gov, apps.azdot.gov, apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 26 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 27 circuits terminating in National Electrical Manufacturers Association (NEMA) 5-20R 5 28 receptacles and one dedicated isolated ground 30-amp circuit terminating in a NEMA 29 6-30R receptacle for the server room.

Appears in 3 contracts

Samples: apps.azdot.gov, apps.azdot.gov, apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 31 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 32 circuits terminating in National Electrical Manufacturers Association (NEMA) 5-20R 5 33 receptacles and one dedicated isolated ground 30-amp circuit terminating in a NEMA 34 6-30R receptacle for the server room.

Appears in 2 contracts

Samples: apps.azdot.gov, apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 40 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 41 circuits terminating in National Electrical Manufacturers Association (NEMA) NEMA 5-20R 5 receptacles and one dedicated isolated ground 30- 42 amp circuit terminating in a NEMA 6-30R receptacle for the server room.

Appears in 1 contract

Samples: apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 34 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 35 circuits terminating in National Electrical Manufacturers Association (NEMA) 5-20R 5 636 receptacles and one dedicated isolated ground 30-amp circuit terminating in a NEMA 6- 37 30R receptacle for the server room.

Appears in 1 contract

Samples: apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 circuits terminating in National Electrical Manufacturers Association (NEMA) NEMA 5-20R 5 receptacles and one dedicated isolated ground 4 30-amp circuit terminating in a NEMA 6-30R receptacle for the server room.

Appears in 1 contract

Samples: apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 40 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 41 circuits terminating in National Electrical Manufacturers Association (NEMA) 5-20R 5 642 receptacles and one dedicated isolated ground 30-amp circuit terminating in a NEMA 6- 43 30R receptacle for the server room.

Appears in 1 contract

Samples: apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 and a 13 minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 circuits 14 terminating in National Electrical Manufacturers Association (NEMA) 5-20R 5 receptacles and one 15 dedicated isolated ground 30-amp circuit terminating in a NEMA 6-30R receptacle for the server 16 room.;

Appears in 1 contract

Samples: apps.azdot.gov

AutoNDA by SimpleDocs

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 26 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 27 circuits terminating in National Electrical Manufacturers Association (NEMA) NEMA 5-20R 5 receptacles and one dedicated isolated ground 30- 28 amp circuit terminating in a NEMA 6-30R receptacle for the server room.

Appears in 1 contract

Samples: apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 22 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 23 circuits terminating in National Electrical Manufacturers Association (NEMA) NEMA 5-20R 5 receptacles and one dedicated isolated ground 30- 24 -amp circuit terminating in a NEMA 6-30R receptacle for the server room.

Appears in 1 contract

Samples: apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 34 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 35 circuits terminating in National Electrical Manufacturers Association (NEMA) NEMA 5-20R 5 receptacles and one dedicated isolated ground 36 30-amp circuit terminating in a NEMA 6-30R receptacle for the server room.

Appears in 1 contract

Samples: apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 32 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 33 circuits terminating in National Electrical Manufacturers Association (NEMA) NEMA 5-20R 5 receptacles and one dedicated isolated ground 34 30-amp circuit terminating in a NEMA 6-30R receptacle for the server room.

Appears in 1 contract

Samples: apps.azdot.gov

Power circuits. Developer shall provide dedicated electrical power circuits for copiers 2 18 and a minimum of six duplex receptacles with three dedicated isolated ground 20-amp 3 19 circuits terminating in National Electrical Manufacturers Association (NEMA) 5-20R 5 620 receptacles and one dedicated isolated ground 30-30R amp circuit terminating in a NEMA 6- 21 -30R receptacle for the server room.

Appears in 1 contract

Samples: apps.azdot.gov

Time is Money Join Law Insider Premium to draft better contracts faster.