Common use of Power Factor Requirement Clause in Contracts

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Generation Interconnection Customer shall design its non-synchronous Customer Facility with the ability to maintain a power factor of at least 0.95 leading to 0.95 lagging measured at the high-side of the facility substation transformers.

Appears in 35 contracts

Samples: Interconnection Service Agreement, Interconnection Service Agreement, Interconnection Service Agreement

AutoNDA by SimpleDocs

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Generation Interconnection Customer shall design its non-synchronous Customer Facility with the ability to maintain a power factor of at least 0.95 leading to 0.95 lagging measured at the high-side of the facility substation transformersgenerator’s terminals.

Appears in 25 contracts

Samples: Interconnection Service Agreement, Interconnection Service Agreement, Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Generation Interconnection Customer shall design its non-synchronous Customer Facility with the ability to maintain a power factor of at least 0.95 leading to 0.95 0.90 lagging measured at the high-side of the facility substation transformersgenerator’s terminals.

Appears in 20 contracts

Samples: Interconnection Service Agreement, Interconnection Service Agreement, Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Generation Interconnection Customer shall design its non-synchronous Customer Facility with the ability to maintain a power factor of at least 0.95 leading to 0.95 lagging measured at the high-high side of the facility substation transformers.

Appears in 14 contracts

Samples: Interconnection Service Agreement, Interconnection Service Agreement, Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Generation Interconnection Customer shall design its non-synchronous Customer Facility with the ability to maintain a power factor of at least 0.95 leading to 0.95 0.90 lagging measured at the high-side Point of the facility substation transformersInterconnection.

Appears in 3 contracts

Samples: Interconnection Service Agreement, Interconnection Service Agreement, Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Generation Interconnection Interconnectionexisting 19.9 MW portion of the Customer Facility shall design designretain its non-synchronous Customer Facility with the theexisting ability to maintain a power factor of at least 0.95 leading to 0.95 0.90 lagging measured at the high-side Point of the facility substation transformersInterconnection.

Appears in 1 contract

Samples: Interconnection Service Agreement

AutoNDA by SimpleDocs

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Generation Interconnection Customer shall design its non-synchronous Customer Facility with the ability to maintain a power factor of at least 0.95 leading to 0.95 0.90 lagging measured at the high-side of the facility substation transformersgenerator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Generation Interconnection Customer shall design its nonwind-synchronous powered Customer Facility with the ability to maintain a power factor of at least 0.95 leading to 0.95 lagging measured at the high-side of the facility substation transformerstransformer.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Generation Interconnection Customer shall design its nonwind-synchronous powered Customer Facility with the ability to maintain a power factor of at least 0.95 leading to 0.95 lagging measured at the highgenerator’s terminalshigh-side of the facility substation transformers.

Appears in 1 contract

Samples: Interconnection Service Agreement