Common use of Power Factor Requirement Clause in Contracts

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 2 contracts

Samples: Interconnection Service Agreement, Interconnection Service Agreement

AutoNDA by SimpleDocs

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 331.3 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 5 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminalsPoint of Interconnection.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Interconnection Customer shall design its existing 766 1050 MW portion of the Customer Facility shall with theshall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 55 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 25 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 1.1 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminalsPoint of Interconnection.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 42 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 7 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminalspoint of interconnection.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 190 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 0 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminalsPoint of Interconnection.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 26 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 1.0 MW to the Customer Facility associated with this ISA the AF1-194 project shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminalsPoint of Interconnection.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 302.5 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 742 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 6 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminalsPoint of Interconnection.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 100 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 230 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) 0.95 leading to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 840 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 12 MW to the Customer Facility associated with this ISA PJM Queue Number X4-027 shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 26 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 1 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminalsPoint of Interconnection.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 57 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 5 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminalsPoint of Interconnection.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 96 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 1526 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The existing 44 MW portion of the Customer Facility associated with the T77 queue position shall retain its existing ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals. The increase of 10 154 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 1249 MW portion of the Customer Facility Facility, that includes 675 MW for unit #1, 550 MW for unit #2 and 24 MW for unit #3, shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 MW to unit #2 of the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

AutoNDA by SimpleDocs

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Interconnection Customer shall design its existing 766 590 MW portion of the Customer Facility shall with theshall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 20 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 950 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 66 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 675 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 40 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 88 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 12 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 1464 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 2015 MW to the Customer Facility associated with this ISA and the 20 MW associated with the AC2-133 Interconnection Request shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 22.5 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 590 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 8 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminalsPoint of Interconnection.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 1036 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 64 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 non-synchronous 16.9 MW portion of the Customer Facility shall retain its existing the ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 0.95 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement

Power Factor Requirement. Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The existing 766 585 MW portion of the Customer Facility shall retain its existing ability to maintain a power factor of at least 0.95 leading to 0.90 lagging measured at the generator’s terminals. The increase of 10 MW to the Customer Facility associated with this ISA shall be designed with the ability to maintain a power factor of at least 1.0 (unity) to 0.90 lagging measured at the generator’s terminals.

Appears in 1 contract

Samples: Interconnection Service Agreement