Screens and Requirements for Determination of Minimal Impact. 6.1 Area EPS Circuit Level Saturation: The cumulative total of the maximum rated output of all interconnected Generation shall not exceed the following limits, per circuit, for the given Area EPS distribution circuit phase to phase voltage rating: Circuits 20 kV or greater: 100 kW Circuits 10 kV but less than 20 kV: 60 kW Circuits less than 10 kV: 30 kW
Appears in 6 contracts