Smoke Detectors and Duct Detectors - Sensitivity. (See frequency of testing herein.) (1) Test sensitivity in accordance with the manufacturers specifications using appropriate and approved testing devices (2) Record results of sensitivity test (greater than 0.5 but less than 3.8) (3) Clean any detector that fails sensitivity test (4) Retest any detector that fails sensitivity test (5) Replace any detector that fails a second sensitivity test
Appears in 4 contracts
Samples: Facility Security Equipment, Systems and Services, Subordinate Contract for Facility Security Equipment, Systems and Services, Fire Alarm System Maintenance Repair Contract
Smoke Detectors and Duct Detectors - Sensitivity. (See frequency of testing herein.)
(1) Test sensitivity in accordance with the manufacturers specifications using appropriate and approved testing devices
(2) Record results of sensitivity test (greater than 0.5 but less than 3.8)
(3) Clean any detector that fails sensitivity test
(4) Retest any detector that fails sensitivity test
(5) Replace any detector that fails a second sensitivity test
Appears in 1 contract
Samples: Subordinate Contract for Facility Security Equipment, Systems and Services
Smoke Detectors and Duct Detectors - Sensitivity. (See frequency of testing herein.)
(1) Test sensitivity in accordance with the manufacturers specifications using appropriate and approved testing devices
(2) Record results of sensitivity test (greater than 0.5 but less than 3.8)
(3) Clean any detector that fails sensitivity test
(4) Retest any detector that fails sensitivity test
(5) Replace any detector that fails a second sensitivity test
Appears in 1 contract
Samples: Subordinate Contract for Facility Security Equipment, Systems and Services