Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/ switchyard: i) At 765kV & 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Transformers of same HV rating shall be placed in different diameters.

Appears in 1 contract

Samples: Transmission Service Agreement

AutoNDA by SimpleDocs

Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/ substation/switchyard:: 765 kV Fatehgarh-II PS One & half breaker (AIS) 765 kV Bhadla-II PS One & half breaker (AIS) i) At 765kV & 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Transformers of same HV rating shall be placed in different diameters.

Appears in 1 contract

Samples: Transmission Service Agreement

Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/ substation/switchyard: i) At 765kV & 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Transformers of same HV rating shall be placed in different diameters.

Appears in 1 contract

Samples: Transmission Service Agreement

Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/ substation/switchyard:: Notes: - i) At 765kV & 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Transformers and bus reactors of same HV rating shall be placed in different diametersdiameters (i.e two transformers of same HV rating shall not be connected in the same diameter and similarly, two bus reactors of same HV rating shall also not be connected in the same diameter).

Appears in 1 contract

Samples: Transmission Service Agreement

AutoNDA by SimpleDocs

Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/ ofsubstation/switchyard: i) At 765kV & 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Transformers Two transformers of same HV rating shall not be placed connected in different diametersthe same diameter and similarly bus reactors of same HV rating shall also not be connected in the same diameter).

Appears in 1 contract

Samples: Standard Transmission Service Agreement