Common use of Switching Scheme Clause in Contracts

Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard: 765 kV Sikar-II PS One & half breaker (AIS) 765 kV Aligarh PS One & half breaker (GIS) i) At 765kV & 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Transformers of same HV rating shall be placed in different diameters.

Appears in 1 contract

Samples: Transmission Service Agreement

AutoNDA by SimpleDocs

Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard: 765 kV Sikar-II 400/220kV Ananthapuram PS One & half breaker (AIS) 765 kV Aligarh Double Main & Transfer (AIS) with sectionalization 400/220kV Cuddappah PS Extn. One & half breaker (GIS)) ----- 400/220 kV Kurnool-III PS Extn. One & half breaker (AIS) ----- i) At 765kV & 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Transformers of same HV rating shall be placed in different diameters.

Appears in 1 contract

Samples: Transmission Service Agreement

Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard: 765 kV Sikar-II PS 765/400/220kV Narela GIS S/s One & half breaker (GIS) One & half breaker (GIS) 765kV Khetri (PG) S/s Extn. One & half breaker (AIS) 765 kV Aligarh PS One & half breaker (GIS)----- i) At 765kV & 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Transformers of same HV rating shall be placed in different diameters.

Appears in 1 contract

Samples: Transmission Service Agreement

Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard: 765 kV Sikar400/220kV Bikaner-II PS One & half breaker (AIS) 765 kV Aligarh PS Double Main & Transfer (AIS) 400kV Bhiwadi GIS S/S Extn. One & half breaker (GIS)) ----- i) At 765kV & 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Transformers of same HV rating shall be placed in different diameters.

Appears in 1 contract

Samples: Transmission Service Agreement

AutoNDA by SimpleDocs

Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard: 765 kV Sikar-II PS 765/400/220kV Dausa S/s One & half Half breaker (AIS) 765 kV Aligarh PS One & half Half breaker (GIS)AIS) Double Main & Transfer (AIS) 765kV Beawar S/s One & Half breaker (AIS) ---- ---- i) At 765kV & 400kV voltage level, each circuit of a double circuit transmission line shall be terminated in different diameters. ii) Transformers and bus reactors of same HV rating shall be placed in different diameters.diameters (i.

Appears in 1 contract

Samples: Transmission Service Agreement

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!