Transient Data Recording Equipment for Facilities above 20 MW. Non-synchronous generating facilities with generating capacities of more than 20 MW must monitor and record data for all frequency ride-through events, transient low-voltage disturbances that initiated reactive current injection, reactive current injection or momentary cessation for transient high-voltage disturbances, and inverter trips. The data may be recorded and stored in a central plant control system. The following data must be recorded: Plant Level
Appears in 3 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, cdn.misoenergy.org
Transient Data Recording Equipment for Facilities above 20 MW. Non-synchronous generating facilities facilitiesIBR plants with generating capacities of more than 20 MW must monitor and record data for all frequency ride-through events, transient low-voltage disturbances that initiated reactive current injection, reactive current injection or momentary cessation for transient high-voltage disturbances, and inverter trips. The data may be recorded and stored in a central plant control system. The following data must be recorded: Plant Level