Transmission Facilities. As to NTD, the transmission facilities over which the ISO shall exercise Operating Authority (as of the date the facilities are placed in service) in accordance with the terms set forth herein shall be: (a) those facilities of NTD listed in Schedule 2.01(a) (hereinafter “NTD Category A Facilities”), as such list of facilities may be added to or deleted from in accordance with Sections 2.01(d) and 2.02 below; (b) those facilities of NTD listed in Schedule 2.01(b) (hereinafter “NTD Category B Facilities”), as such list of facilities may be added to or deleted from, in accordance with Sections 2.01(d) and 2.02 below; and (c) those transmission facilities of NTD within the New England Transmission System with a voltage level of less than 69 kV and all transformers that have no NTD Category A Facilities or NTD Category B Facilities connected to the lower voltage side of the transformer that are not listed on Schedule 2.01(a) and Schedule 2.01(b) (hereinafter “NTD Local Area Facilities”), provided that any excluded facilities of NTD listed on Schedule 4.01(d) shall not be NTD Local Area Facilities. (d) The transmission facilities included on any of the lists of the NTD Category A Facilities or the NTD Category B Facilities contained in Schedule 2.01(a) and Schedule 2.01(b), respectively, may be redesignated on another of those two lists, deleted from such list, or redesignated as a NTD Local Area Facility without the necessity of an amendment to this Agreement, but only in the following manner: (i) at the direction of a Governmental Authority with jurisdiction over the Transmission Facilities in question, provided that the ISO and NTD shall be provided prior written notice of such changes; (ii) as agreed between the ISO and NTD; or (iii) where the operational characteristics of a transmission facility have been materially modified (including a change from a radial transmission facility to a looped transmission facility that contributes to the parallel carrying capability of the New England Transmission System) in accordance with Section 2.01(e); provided that any such changes shall also be subject to ISO review consistent with Section 2.06. (e) All transmission facilities to be redesignated as NTD Category A Facilities, NTD Category B Facilities, or Local Area Facilities or deleted from the lists in Schedule 2.01(a) and Schedule 2.01(b) in accordance with Section 2.01(d)(iii), and all transmission facilities to be added to the lists in Schedule 2.01(a) and Schedule 2.01(b) in accordance with Section 2.02 shall be classified in accordance with the following standards: (i) NTD Category A Facilities shall consist of: all transmission lines with a voltage level of 115 kV and above, except for those 115 kV transmission facilities specifically designated as NTD Category B Facilities in accordance with Section 2.01(e)(ii); all transmission interties between Control Areas; all transformers that have NTD Category A Facilities connected to the lower voltage side of the transformer; all transformers that require an NTD Category A Facility to be taken out of service when the transformer is taken out of service; and all breakers and disconnects connected to, and all shunts, relays, reclosing and associated equipment, dynamic reactive resources, FACTS controllers, special protection systems, PARS, and other equipment specifically installed to support the operation of such transmission lines, interties, and transformers. (ii) NTD Category B Facilities shall consist of: all 115 kV radial transmission lines and all 69 kV transmission lines that are not interties between Control Areas; all transformers that have any NTD Category B Facilities and no NTD Category A Facilities connected to the lower voltage side of the transformer except to the extent such transformers are designated as NTD Category A Facilities in accordance with Section 2.01(e)(i); and all breakers and disconnects connected to, and all shunts, relays, reclosing and associated equipment, dynamic reactive resources, FACTS controllers, special protection systems, PARS, and other equipment specifically installed to support the operation of such NTD Category B Facilities. (iii) NTD Local Area Facilities shall consist of all transmission facilities with a voltage level of less than 69 kV and all transformers that have no NTD Category A Facilities or NTD Category B Facilities connected to the lower voltage side of the transformer. (iv) To the extent there is any dispute between the ISO and NTD as owner of a transmission facility concerning classification of such transmission facility under these standards, such disagreement shall be subject to the dispute resolution provisions of this Agreement, provided that the ISO’s classification of a transmission facility under the standards shall govern pending resolution of the dispute. Collectively, all NTD Category A Facilities, NTD Category B Facilities, and NTD Local Area Facilities shall hereinafter be referred to as the “Transmission Facilities,” provided that “Transmission Facilities” shall not include Excluded Assets as defined in Section 2.04 of this Agreement or Merchant Facilities. The ISO shall maintain on its OASIS a posting of the current versions of Schedule 2.01(a) and Schedule 2.01(b), in each instance, reflecting each such change promptly after such change is made. (f) The classifications set forth in this Section 2.01 are for operational purposes. Rate treatment of Transmission Facilities shall be governed by the ISO OATT, provided that filings for rate treatment under the ISO OATT shall be subject to Section 3.04 of this Agreement.
Appears in 2 contracts
Samples: Non Incumbent Transmission Developer Operating Agreement, Non Incumbent Transmission Developer Operating Agreement
Transmission Facilities. As to NTDany PTO, the transmission facilities over which the ISO shall exercise Operating Authority (as of the date the facilities are placed in service) in accordance with the terms set forth herein shall be:
(a) those facilities of NTD such PTO listed in Schedule 2.01(a) (hereinafter “NTD Category A Facilities”), as such list of facilities may be added to or deleted from in accordance with Sections 2.01(d) and 2.02 below;
(b) those facilities of NTD such PTO listed in Schedule 2.01(b) (hereinafter “NTD Category B Facilities”), as such list of facilities may be added to or deleted from, in accordance with Sections 2.01(d) and 2.02 below; and
(c) and I those transmission facilities of NTD such PTO within the New England Transmission System with a voltage level of less than 69 kV and all transformers that have no NTD Category A Facilities or NTD Category B Facilities connected to the lower voltage side of the transformer that are not listed on Schedule 2.01(a) and Schedule 2.01(b) (hereinafter “NTD Local Area Facilities”), provided that any excluded facilities of NTD such PTO listed on Schedule 4.01(d) shall not be NTD Local Area Facilities.
(d) The As to each PTO, the transmission facilities included on any of the lists of the NTD Category A Facilities or the NTD Category B Facilities contained in Schedule 2.01(a) and Schedule 2.01(b), respectively, as of the Operations Date may be redesignated on another of those these two lists, deleted from such list, or redesignated as a NTD Local Area Facility without the necessity of an amendment to this Agreement, but only in the following manner:
(i) at the direction of a Governmental Authority with jurisdiction over the Transmission Facilities in question, provided that the ISO and NTD all PTOs shall be provided prior written notice of such changes;
(ii) as agreed between the ISO and NTDthe PTO or PTOs owning the transmission facilities; or
(iii) where the operational characteristics of a transmission facility have been materially modified after the Operations Date (including a change from a radial transmission facility to a looped transmission facility that contributes to the parallel carrying capability of the New England Transmission System) in accordance with Section 2.01(e); provided that any such changes shall also be subject to ISO review consistent with Section 2.06.
(e) All transmission facilities to be redesignated as NTD Category A Facilities, NTD Category B Facilities, or Local Area Facilities or deleted from the lists in Schedule 2.01(a) and Schedule 2.01(b) in accordance with Section 2.01(d)(iii), and all transmission facilities to be added to the lists in Schedule 2.01(a) and Schedule 2.01(b) in accordance with Section 2.02 shall be classified in accordance with the following standards:
(i) NTD Category A Facilities shall consist of: all transmission lines with a voltage level of 115 kV and above, except for those 115 kV transmission facilities specifically designated as NTD Category B Facilities in accordance with Section 2.01(e)(ii); all transmission interties between Control Areas; all transformers that have NTD Category A Facilities connected to the lower voltage side of the transformer; all transformers that require an NTD a Category A Facility to be taken out of service when the transformer is taken out of service; and all breakers and disconnects connected to, and all shunts, relays, reclosing and associated equipment, dynamic reactive resources, FACTS controllers, special protection systems, PARS, and other equipment specifically installed to support the operation of such transmission lines, interties, and transformers.
(ii) NTD Category B Facilities shall consist of: all 115 kV radial transmission lines and all 69 kV transmission lines that are not interties between Control Areas; all transformers that have any NTD Category B Facilities and no NTD Category A Facilities connected to the lower voltage side of the transformer except to the extent such transformers are designated as NTD Category A Facilities in accordance with Section 2.01(e)(i); and all breakers and disconnects connected to, and all shunts, relays, reclosing and associated equipment, dynamic reactive resources, FACTS controllers, special protection systems, PARS, and other equipment specifically installed to support the operation of such NTD Category B Facilities.
(iii) NTD Local Area Facilities shall consist of all transmission facilities with a voltage level of less than 69 kV and all transformers that have no NTD Category A Facilities or NTD Category B Facilities connected to the lower voltage side of the transformer.
(iv) To the extent there is any dispute between the ISO and NTD as owner of a PTO or PTOs owning a transmission facility concerning classification of such transmission facility under these standards, such disagreement shall be subject to the dispute resolution provisions of this Agreement, provided that the ISO’s classification of a transmission facility under the standards shall govern pending resolution of the dispute. .
(f) Collectively, all NTD Category A Facilities, NTD Category B Facilities, and NTD Local Area Facilities shall hereinafter be referred to as the “Transmission Facilities,” provided that “Transmission Facilities” shall not include Excluded Assets as defined in Section 2.04 of this Agreement or Merchant Facilities. The ISO shall maintain on its OASIS a posting of the current versions of Schedule 2.01(a) and Schedule 2.01(b), in each instance, reflecting each such change promptly after such change is made.
(fg) The classifications set forth in this Section 2.01 are for operational purposes. Rate treatment of Transmission Facilities shall be governed by the ISO OATT, provided that filings for rate treatment under the ISO OATT shall be subject to Section 3.04 of this Agreement.
Appears in 1 contract
Samples: Transmission Operating Agreement (Connecticut Light & Power Co)
Transmission Facilities. As to NTDany PTO, the transmission facilities over which the ISO shall exercise Operating Authority (as of the date the facilities are placed in service) in accordance with the terms set forth herein shall be:
(a) those facilities of NTD such PTO listed in Schedule 2.01(a) (hereinafter “NTD Category A Facilities”), as such list of facilities may be added to or deleted from in accordance with Sections 2.01(d) and 2.02 below;
(b) those facilities of NTD such PTO listed in Schedule 2.01(b) (hereinafter “NTD Category B Facilities”), as such list of facilities may be added to or deleted from, in accordance with Sections 2.01(d) and 2.02 below; and
(c) those transmission facilities of NTD such PTO within the New England Transmission System with a voltage level of less than 69 kV and all transformers that have no NTD Category A Facilities or NTD Category B Facilities connected to the lower voltage side of the transformer that are not listed on Schedule 2.01(a) and Schedule 2.01(b) (hereinafter “NTD Local Area Facilities”), provided that any excluded facilities of NTD such PTO listed on Schedule 4.01(d) shall not be NTD Local Area Facilities.
(d) The As to each PTO, the transmission facilities included on any of the lists of the NTD Category A Facilities or the NTD Category B Facilities contained in Schedule 2.01(a) and Schedule 2.01(b), respectively, as of the Operations Date may be redesignated on another of those these two lists, deleted from such list, or redesignated as a NTD Local Area Facility without the necessity of an amendment to this Agreement, but only in the following manner:
(i) at the direction of a Governmental Authority with jurisdiction over the Transmission Facilities in question, provided that the ISO and NTD all PTOs shall be provided prior written notice of such changes;
(ii) as agreed between the ISO and NTDthe PTO or PTOs owning the transmission facilities; or
(iii) where the operational characteristics of a transmission facility have been materially modified after the Operations Date (including a change from a radial transmission facility to a looped transmission facility that contributes to the parallel carrying capability of the New England Transmission System) in accordance with Section 2.01(e); provided that any such changes shall also be subject to ISO review consistent with Section 2.06.
(e) All transmission facilities to be redesignated as NTD Category A Facilities, NTD Category B Facilities, or Local Area Facilities or deleted from the lists in Schedule 2.01(a) and Schedule 2.01(b) in accordance with Section 2.01(d)(iii), and all transmission facilities to be added to the lists in Schedule 2.01(a) and Schedule 2.01(b) in accordance with Section 2.02 shall be classified in accordance with the following standards:
(i) NTD Category A Facilities shall consist of: all transmission lines with a voltage level of 115 kV and above, except for those 115 kV transmission facilities specifically designated as NTD Category B Facilities in accordance with Section 2.01(e)(ii); all transmission interties between Control Areas; all transformers that have NTD Category A Facilities connected to the lower voltage side of the transformer; all transformers that require an NTD a Category A Facility to be taken out of service when the transformer is taken out of service; and all breakers and disconnects connected to, and all shunts, relays, reclosing and associated equipment, dynamic reactive resources, FACTS controllers, special protection systems, PARS, and other equipment specifically installed to support the operation of such transmission lines, interties, and transformers.
(ii) NTD Category B Facilities shall consist of: all 115 kV radial transmission lines and all 69 kV transmission lines that are not interties between Control Areas; all transformers that have any NTD Category B Facilities and no NTD Category A Facilities connected to the lower voltage side of the transformer except to the extent such transformers are designated as NTD Category A Facilities in accordance with Section 2.01(e)(i); and all breakers and disconnects connected to, and all shunts, relays, reclosing and associated equipment, dynamic reactive resources, FACTS controllers, special protection systems, PARS, and other equipment specifically installed to support the operation of such NTD Category B Facilities.
(iii) NTD Local Area Facilities shall consist of all transmission facilities with a voltage level of less than 69 kV and all transformers that have no NTD Category A Facilities or NTD Category B Facilities connected to the lower voltage side of the transformer.
(iv) To the extent there is any dispute between the ISO and NTD as owner of a PTO or PTOs owning a transmission facility concerning classification of such transmission facility under these standards, such disagreement shall be subject to the dispute resolution provisions of this Agreement, provided that the ISO’s classification of a transmission facility under the standards shall govern pending resolution of the dispute. .
(f) Collectively, all NTD Category A Facilities, NTD Category B Facilities, and NTD Local Area Facilities shall hereinafter be referred to as the “Transmission Facilities,” provided that “Transmission Facilities” shall not include Excluded Assets as defined in Section 2.04 of this Agreement or Merchant Facilities. The ISO shall maintain on its OASIS a posting of the current versions of Schedule 2.01(a) and Schedule 2.01(b), in each instance, reflecting each such change promptly after such change is made.
(fg) The classifications set forth in this Section 2.01 are for operational purposes. Rate treatment of Transmission Facilities shall be governed by the ISO OATT, provided that filings for rate treatment under the ISO OATT shall be subject to Section 3.04 of this Agreement.
(h) Though the Xxxxxxx SVC Facility is not owned by MEPCO, it is recognized as a Category A Facility under this Agreement. The inclusion of the Xxxxxxx SVC Facility in Schedule 2.01(a) of this agreement by MEPCO, as agent for the Xxxxxxx SVC Partnership, is for the sole purpose of granting Operating Authority (as defined in Section 3.02) to the ISO, specifically excluding those responsibilities under Section 3.03 of this Agreement and shall not change the established cost recovery arrangements or rate treatment. The Chester SVC Facility costs are recovered under a bilateral contract with New England Hydro Corporation (“NE Hydro”). NE Hydro pays the Chester SVC Partnership a monthly support fee that covers the construction cost and ongoing operation and maintenance costs of the Xxxxxxx SVC Facility. NE Hydro bills the Phase II HVDC Interconnection Participants to recover its payments. Most Phase II HVDC Interconnection Participants recover their Xxxxxxx SVC-related support payments through regional rates as originally allowed by the Restated NEPOOL Agreement and now by the ISO OATT Section II.49. Notwithstanding any other provision of this Agreement, the inclusion of the Xxxxxxx SVC Facility for the sole purpose of granting Operating Authority as so limited above, is not meant to subject, in any way, the Xxxxxxx SVC Partnership to regulation as a public utility under the Federal Power Act.
Appears in 1 contract
Samples: Transmission Operating Agreement
Transmission Facilities. As to NTDany PTO, the transmission facilities over which the ISO shall exercise Operating Authority (as of the date the facilities are placed in service) in accordance with the terms set forth herein shall be:
(a) those facilities of NTD such PTO listed in Schedule 2.01(a) (hereinafter “NTD Category A Facilities”), as such list of facilities may be added to or deleted from in accordance with Sections 2.01(d) and 2.02 below;
(b) those facilities of NTD such PTO listed in Schedule 2.01(b) (hereinafter “NTD Category B Facilities”), as such list of facilities may be added to or deleted from, in accordance with Sections 2.01(d) and 2.02 below; and
(c) those transmission facilities of NTD such PTO within the New England Transmission System with a voltage level of less than 69 kV and all transformers that have no NTD Category A Facilities or NTD Category B Facilities connected to the lower voltage side of the transformer that are not listed on Schedule 2.01(a) and Schedule 2.01(b) (hereinafter “NTD Local Area Facilities”), provided that any excluded facilities of NTD such PTO listed on Schedule 4.01(d) shall not be NTD Local Area Facilities.
(d) The As to each PTO, the transmission facilities included on any of the lists of the NTD Category A Facilities or the NTD Category B Facilities contained in Schedule 2.01(a) and Schedule 2.01(b), respectively, as of the Operations Date may be redesignated on another of those these two lists, deleted from such list, or redesignated as a NTD Local Area Facility without the necessity of an amendment to this Agreement, but only in the following manner:
(i) at the direction of a Governmental Authority with jurisdiction over the Transmission Facilities in question, provided that the ISO and NTD all PTOs shall be provided prior written notice of such changes;
(ii) as agreed between the ISO and NTDthe PTO or PTOs owning the transmission facilities; or
(iii) where the operational characteristics of a transmission facility have been materially modified after the Operations Date (including a change from a radial transmission facility to a looped transmission facility that contributes to the parallel carrying capability of the New England Transmission System) in accordance with Section 2.01(e); provided that any such changes shall also be subject to ISO review consistent with Section 2.06.
(e) All transmission facilities to be redesignated as NTD Category A Facilities, NTD Category B Facilities, or Local Area Facilities or deleted from the lists in Schedule 2.01(a) and Schedule 2.01(b) in accordance with Section 2.01(d)(iii), and all transmission facilities to be added to the lists in Schedule 2.01(a) and Schedule 2.01(b) in accordance with Section 2.02 shall be classified in accordance with the following standards:
(i) NTD Category A Facilities shall consist of: all transmission lines with a voltage level of 115 kV and above, except for those 115 kV transmission facilities specifically designated as NTD Category B Facilities in accordance with Section 2.01(e)(ii); all transmission interties between Control Areas; all transformers that have NTD Category A Facilities connected to the lower voltage side of the transformer; all transformers that require an NTD a Category A Facility to be taken out of service when the transformer is taken out of service; and all breakers and disconnects connected to, and all shunts, relays, reclosing and associated equipment, dynamic reactive resources, FACTS controllers, special protection systems, PARS, and other equipment specifically installed to support the operation of such transmission lines, interties, and transformers.
(ii) NTD Category B Facilities shall consist of: all 115 kV radial transmission lines and all 69 kV transmission lines that are not interties between Control Areas; all transformers that have any NTD Category B Facilities and no NTD Category A Facilities connected to the lower voltage side of the transformer except to the extent such transformers are designated as NTD Category A Facilities in accordance with Section 2.01(e)(i); and all breakers and disconnects connected to, and all shunts, relays, reclosing and associated equipment, dynamic reactive resources, FACTS controllers, special protection systems, PARS, and other equipment specifically installed to support the operation of such NTD Category B Facilities.
(iii) NTD Local Area Facilities shall consist of all transmission facilities with a voltage level of less than 69 kV and all transformers that have no NTD Category A Facilities or NTD Category B Facilities connected to the lower voltage side of the transformer.
(iv) To the extent there is any dispute between the ISO and NTD as owner of a PTO or PTOs owning a transmission facility concerning classification of such transmission facility under these standards, such disagreement shall be subject to the dispute resolution provisions of this Agreement, provided that the ISO’s classification of a transmission facility under the standards shall govern pending resolution of the dispute. .
(f) Collectively, all NTD Category A Facilities, NTD Category B Facilities, and NTD Local Area Facilities shall hereinafter be referred to as the “Transmission Facilities,” provided that “Transmission Facilities” shall not include Excluded Assets as defined in Section 2.04 of this Agreement or Merchant Facilities. The ISO shall maintain on its OASIS a posting of the current versions of Schedule 2.01(a) and Schedule 2.01(b), in each instance, reflecting each such change promptly after such change is made.
(fg) The classifications set forth in this Section 2.01 are for operational purposes. Rate treatment of Transmission Facilities shall be governed by the ISO OATT, provided that filings for rate treatment under the ISO OATT shall be subject to Section 3.04 of this Agreement.
Appears in 1 contract