Voltage and Power Quality Screen. In aggregate with existing generation on the line section: (1) the voltage regulation on the line section can be maintained in compliance with relevant requirements under all system conditions;
Appears in 3 contracts
Samples: Facilities Study Agreement, Facilities Study Agreement, Facilities Study Agreement
Voltage and Power Quality Screen. In aggregate with existing generation on the line section: (1) the voltage regulation on the line section can be maintained in compliance with relevant requirements under all system conditions;; (2) the voltage fluctuations is within acceptable limits as defined by Institute of Electrical and Electronics Engineers (IEEE) Standard 1453, or utility practice similar to IEEE Standard 1453; and (3) the harmonic levels meet IEEE Standard 519 limits.
Appears in 2 contracts
Samples: Interconnection Agreement, Interconnection Agreement
Voltage and Power Quality Screen. In aggregate with existing generation on the line section: (1) the voltage regulation on the line section can be maintained in compliance with relevant requirements under all system conditions;; (2) the voltage fluctuation is within acceptable limits as defined by Institute of Electrical and Electronics Engineers (IEEE) Standard 1453, or utility practice similar to IEEE Standard 1453; and (3) the harmonic levels meet IEEE Standard 519 limits.
Appears in 2 contracts
Samples: starw1.ncuc.net, www.oatioasis.com