Examples of Under Voltage in a sentence
All Facilities must meet performance requirements set forth in relevant sections of IEEE Standard 1547, in particular the attachments specific to Under Voltage Ride Through, Under Frequency Ride Through and VAr control.
Batteries au lithium-ion (LiFePO₄)Les batteries au lithium-ion ne sont pas sujettes à la sulfutation et elles n'ont pas besoin d'être régulièrement chargées entièrement.Mais les batteries au lithium-ion sont très sensibles à la sous-tension ou à la surtension.C'est pourquoi, les batteries au lithium-ion sont souvent équipées d'un système intégré pour l'équilibrage des cellules et pour les protéger contre les tensions faibles (UVP : Under Voltage Protection — protection contre la sous-tension).
Under Voltage The input voltage is higher than the high voltage threshold, and the UPS is using batteries to supply power.
Each system or Facility that performs automatic load shedding, without human operator initiation, of 300 MW or more implementing Under Voltage Load Shedding (UVLS) or Under Frequency Load Shedding (UFLS) as required by the regional load shedding program.1.14.
Ashish Sharma, “Modeling and Analysis of Loads Under Voltage Dips Caused by Three Phase Faults”, Polytechnic Institute of NYU, Brooklyn, NY, May 2012.
There is one main automatic scheme installed to prevent voltage collapse, a scheme for low voltage demand disconnection known as Automatic Under Voltage Load Shedding (UVLS).
Status indicator remains flashing in red until the error condition is resolved.Temporary error conditions include: Over Current, Over Voltage, Under Voltage, Over Temperature.For Over Current condition, there are two automatic retries allowed for each charging session.When a charging session is interrupted due to a CCID trip, the Power Max 2 Charging Station will retry after 15 min- utes, for up to 4 times.
Each Participating TO shall coordinate its Critical Protective Systems with the CAISO, other Transmission Owners, and Generators to ensure that its Remedial Action Schemes (“RAS”), Underfrequency Load Shedding (“UFLS”), and Under Voltage Load Shedding (“UVLS”) schemes function on a coordinated and complementary basis in accordance with WECC and NERC planning, reliability, and protection policies and standards.
The phase protector shall be programmed as follows: Line Voltage: Nameplate Voltage Delay on Break: 1 minute Fault Interrogation: 8 seconds Over/ Under Voltage: 8% Phase Unbalance: 5% Reset Mode: Automatic L.
Over current, short circuit, earth fault, input phase loss, DC over voltage, DC under voltage, motor over temperature, output phase loss, motor thermal overload, under load protection, Over-voltage, Under Voltage, Over-speed, IGBT over Temperature heat sink Over-temperature motor stall function with adjustable time and frequency settings.