AMF Panel and Engine Trial Clause Samples
AMF Panel and Engine Trial. AMF Panel and engine control panel shall be tested for automatic operation by injecting proper current one voltage by a separate source. The satisfactory working of automatic operation shall be tested & necessary adjustment shall be done for relays in the presence of the Independent Engineer and the result shall be recorded in the test sheet at 30 minutes interval. Alternator efficiency as determined in works test shall be used as the basis of calculation for fuel consumption rate. Test providing the satisfactory performance of all safety and operating controls shall be carried out. Starting time of sets shall be tested at least five times and the sufficient time interval to allow for cold start. A set of tools and tackles has to be supplied along with each set and shall be included in the cost of DG set.